DMTech FP9000A Instruction Manual For Installation

DMTech FP9000A Instruction Manual For Installation

Addressable fire alarm panel
Hide thumbs Also See for FP9000A:

Advertisement

DMTech LTD, Pleven
Addressable Fire Alarm Panel
FP9000A
Instruction manual for installation, setup and
exploitation
Revision 01.19

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FP9000A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DMTech FP9000A

  • Page 1 DMTech LTD, Pleven Addressable Fire Alarm Panel FP9000A Instruction manual for installation, setup and exploitation Revision 01.19...
  • Page 2: Introduction

    FAULT, etc. are being stored in the memory, creating a log file of events. The log file contains time and date, address and name of device, number and name of zone, etc. DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 2 - of 20...
  • Page 3: Main Technical Characteristics

    Under normal conditions the fire alarm panel is power supplied by the electrical grid. In case of failure in the power supply from the mains, a backup battery provides supply to the panel. Characteristics of the main supply unit: DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 3 - of 20...
  • Page 4 List of fuses • Main power supply: 4А, T-type, slow-melting, 5х20 mm • Storage battery: 6.0А, T-type, slow-melting, 5х20 mm • Contents of delivery: Addressable Fire Alarm System FP9000A Fire alarm panel FP 9000А 1 pc 1 pc Fuse 6,3А 1 pc Fuse 4,0А...
  • Page 5: Installation

    • Replace the front lid by mounting the lid to the circuit board box and fasten with the screw following the description on Fig.2 in reverse order. • Proceed to initiation and testing of the system. DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 5 - of 20...
  • Page 6 218 mm – Central mounting holes – Holes for pulling cables through – Holes for pulling main supply cable through – Additional holes for cable pulling DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 6 - of 20...
  • Page 7: System Elements

    Fault condition in controllable outputs – the indicator for fault in controllable outputs illuminates in continuous yellow light OUTS The indicator for output delay illuminates in continuous yellow light DELAY OUT DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 7 - of 20...
  • Page 8 Fire condition and Fault condition - Functional button for suppressing the Alarm button local sounder – illuminates in red Functional button for Fire Alarm Mode resetting. Requires access level 2 Line reset button password. DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 8 - of 20...
  • Page 9: Position Of Modules In The Box

    12V 4.5-5 Ah 12V 4.5-5 Ah buttons 5 – Space for storage batteries, 2 х 12V/ 4.5–5Ah 6 – Coupling for USB connection to a computer DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 9 - of 20...
  • Page 10: Description Of Main Pcb

    BATT – Pin connector (red and black pins) for connection to the storage battery. An additional Ø5mm cable ear connector is installed to each cable terminal (M5) DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 10 - of 20...
  • Page 11: Connecting The Main Supply

    WARNING: Storage battery must be charged at maximum current value I = 2A and voltage U = 27.2V ±1%. battery червен мост с кабелни обувки 12V Ah 12V Ah Fig. 7 Connecting the storage batteries DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 11 - of 20...
  • Page 12: Connecting Devices

    Fig. 8 Example of devices connected in a loop 2.3.2. Connecting devices to a conventional line 1 ... n < 32 4.7k Fig. 9. Example of devices connected to conventional line DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 12 - of 20...
  • Page 13: Connecting Signaling Devices

    0.5A. A 4.7 кОhm terminating resistor must be connected in parallel to the loop. 4.7k Fig. 10 – Example of an exit sign device connected to an output DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 13 - of 20...
  • Page 14: Program Menus And Settings Of The Fire Alarm Panel

    9 Passwords Level Pass 10 Default Param - Menu/OK 11 Clear Archive - Exit from menu (+1) and DOWN (-1) Fig. 11 General diagram of menus DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 14 - of 20...
  • Page 15: List Menu

    3. Removed Det ON/OFF – starting and suspending the check 3 Removed Det ON/OFF 4 No Checks 2 for removed fire detector 4. N Checks 2 - number of checks to be performed DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 15 - of 20...
  • Page 16: Addressing Devices In A Loop

    Auto addressing – as soon as a device is attached to its base, the 4 Device Param fire alarm panel recognizes it and assigns a sequential address. 5 Conv Line Param 6 Zones > 7 Initialization DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 16 - of 20...
  • Page 17: Assigning Names To Devices And Adding Devices To A Loop

    FIRE ALARM mode. Coincidence Mode: OFF Delayed Outputs: - Delayed Outputs: After a delay is set, the zone will be activated ZONE1 DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 17 - of 20...
  • Page 18 Analogically, for floor 2, all sounders available on floor 2 and 3 shall be added. For floor 3 – only the sounders available on floor 3. DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 18 - of 20...
  • Page 19: Table Of Contents

    3.2. SYSTEM FUNCTIONS……………………………………………………... 15 3.3. SETUP Menu………………………………………………………………… 15 4. Addressing devices in a loop ……………………………………………….. 16 5. Assigning names to devices and adding devices to a LOOP…………….. 17 DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 19 - of 20...
  • Page 20 Instruction manual Fire Alarm Panel FP9000A DMTech LTD, 16 N.Haytov Street, Pleven Tel.: 0889992660 e-mail:office@dmtech-ltd.com page - 20 - of 20...