For a new MSS spare, the MSS will has a default address on the Ethernet port
connected to the QCS server network of 192.168.10.101. If this is not the correct
address, it can be changed from the MSS Web address.
1. If the QCS server can temporarily be set up at the 192.168.10.* address,
use the server to access the MSS Webpage as described. Otherwise,
connect a PC to the scanner network or to the second MSS Ethernet
interface and browse to the fixed address of http://192.168.0.1.
2. The present MSS IP addresses (eth0) RAE LAN are always displayed on
the main MSS page.
Use the Configure MSS (Network Settings or Ethernet Settings in older
releases) option on the left side to set the MSS IP address and server IP
address. Configure MSS page allows to configure MSS Type also while in
previous releases, MSS Type must be set by selecting this option from the
left menu. See figure xx for the setup used at UPMP
Figure 17 MSS Configuration used for UPMP
From the main MSS Web page (see Chapter 6), use the Set MSS Time
option on the left hand side. The MSS does not automatically correct for
daylight savings time. It is expected that the MSS clock will drift a few
minutes per month relative to the QCS server.
Figure 16 MSS Web main page