Trend Logs; Restart - Bard W3RV2-R Literature Assembly

Wall-mounted variable capacity environmental control unit
Table of Contents

Advertisement

Trend Logs: The controller can be enabled to show a history log of recorded information, specific to
input sensors installed on the unit. Space temperature has been set up as a factory default log, with 10
min. samples taken continuously.
To access Trend Logs from the Home Screen, press:
1. Right button to access the Main Menu Screen
2. Down button through entries to highlight Trend Viewer
3. Enter button to select Trend Viewer & enter Trend Viewer Screen
4. Down button through entries to highlight chosen Log
5. Enter button to select Log and view recorded results
6. Left button to navigate back to Trend Viewer Screen
7. Left button to navigate back to Main Menu
8. Left button to navigate back to Home Screen
To program Trend Logs from the Home Screen, press:
1. Right button to access Main Menu Screen
2. Down button through entries to highlight Advanced
3. Enter button to select Advanced and enter Advanced Screen
4. Down button through entries to highlight Trend Logs
5. Enter button to select Trend Logs and enter Logs Screen
6. Down button to highlight chosen Trend Logs
- Trend 1 is factory default set-up to trend space temp
- Trend 2 - Trend 8 are programmable
7. Enter button to select chosen Log and enter Setup Screen
8. Down button to highlight Object Ref.
9. Select button to select Object Ref. and choose from the following:
- AI1 Space Temperature (Factory Default Trend 1)
- BV1 Occupancy
10. Down button to highlight Log Enable
11. Enter button to select Log Enable
12. Up/Down button(s) to toggle False to True
13. Enter button to save True Setting
14. Down button to highlight Interval (Mins)
15. Enter button to select Interval (Mins)
16. Up/Down button(s) to adjust minutes of interval between readings
17. Enter button to save new setting
18. Left button to navigate back to Trend Log Screen
19. Left button to navigate back to Advanced Screen
20. Left button to navigate back to Main Menu Screen
21. Left button to navigate back to Home Screen
Restart: Should the controller exhibit erratic/haphazard performance during programming or operation, a
"soft-start" function has been enabled into the programming.
To initiate a Restart from Home Screen, press:
1. Right button to access the Main Menu Screen
2. Down button through entries to highlight Advanced
3. Enter button to select/enter Advanced Screen
4. Down button through entries to highlight Restart/Restore
5. Select button to select/enter Restart/Restore Screen
6. Controller will ask for Admin Level Password
Factory Default Admin Level Password: BARD
- BO1 Indoor Fan
-AV1 Minimum Deadband
Manual
2100-560
Page
7 of 8