Switch mode power supply for fire

Advertisement

Quick Links

Elmdene International Ltd
3 Keel Close, Interchange Park,
Portsmouth, Hampshire, PO3 5QD, UK
27.6 Vdc 2 Amp Switch Mode Power Supply for Fire – EN54-4:1997 +A1 +A2
STX2402-E
STX2402-C
F
EATURES
The STX2402-x is an EN54-4:1997 +A1 +A2 approved power supply ideal for use in Fire and Smoke and
ventilation control Systems. Its regulated 27.6V dc output will supply up to 2 Amps continuous into
the load, in addition to providing up to 700 mA for charging the standby batteries up to 18 Ah. The
power supply output features electronic short circuit protection under both mains and standby
battery operation. Maximum battery life is assured through continuous active battery monitoring and
the use of a two stage charger, comprising bulk and temperature compensated final float phase
depending upon battery condition. Once fully charged the product operates in Eco power saving
mode, whereby the batteries are charged for 4 hours in every 24 hour period while still being
continuously monitored. This reduces wasted energy in charging already fully charged batteries and
extends their working life. Deep discharge protection prevents premature battery failure when
operating from standby for extended periods. Two sets of volt free solid state relay fault output signal
(i) loss of mains and (ii) battery fault, charger fault and loss of output. In addition there is an optional
plug in serial interface that can provide diagnostic and fault reporting information to supervisory
systems.
Certified by UL to EN54-4:1997 +A1 +A2.
Up to 2A current to load at 27.6V dc nominal regulated output.
Charging capability to support 7 or 17/18Ah batteries.
Electronic overload protection shuts down output until overload or short circuit is removed.
Battery Monitor detects battery missing, low battery, short-circuit or reverse connection or circuit
impedance (Ri) in excess of 500m caused by connector or wiring problem/corrosion within 4 hours.
Battery charging circuit is energised only when a battery is correctly connected and the battery voltage
is greater than 14 V.
No loss of output during automatic connection of battery to load on loss of mains.
Deep discharge protection disconnects battery from load when battery voltage falls below 21 V.
Diagnostic indicator LED (Orange) (Internal).
Fault indicator LED (Yellow) flashes on detection of output fault, battery fault, charger fault and mains
failure.
Mains indicator LED (Green) showing mains present Indicators check at start-up.
Optional RS232 serial interface for fault reporting and diagnostics.
Technical Support: +44(0)23 9269 6638 (option 3)
Tel: +44(0)23 9269 6638
Fax: +44(0)23 9266 0483
Web:
PAK200582_02B August 2016
0843-CPR-0214
2014
www.elmdene.co.uk
©2016 ELMDENE INTERNATIONAL LTD
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the Elmdene STX2402-E and is the answer not in the manual?

Questions and answers

Summary of Contents for Potter Elmdene STX2402-E

  • Page 1 0843-CPR-0214 2014 Elmdene International Ltd Tel: +44(0)23 9269 6638 Fax: +44(0)23 9266 0483 3 Keel Close, Interchange Park,  Portsmouth, Hampshire, PO3 5QD, UK Web: www.elmdene.co.uk 27.6 Vdc 2 Amp Switch Mode Power Supply for Fire – EN54-4:1997 +A1 +A2 STX2402-E STX2402-C EATURES...
  • Page 2: Specification

    PECIFICATION Mains Input Rated Voltage 110 – 240V ac (Operational voltage) (90 – 264V ac) Frequency 50 Hz Input current < 1.0 Amps at full load Inrush current 5A Max at 25 °C 110V ac for 10 ms Fuse T2.0 A 20mm, 250V ac HRC Output Voltage at full load Mains power...
  • Page 3 Connections and Signalling outputs Load Output +/ - Screw terminals Voltage output to load GEN PSU Fault (normally 0.10 A @ 60 Vdc 16Ω solid state relay contacts, volt free closed contact) Open if Mains failed and battery voltage < 23 V or fault PSU fault condition, (see below) EPS Fault (normally closed 0.10A @ 60 Vdc 16Ω...
  • Page 4: Installation

    Fault Diagnostic table – Internal - Engineer Orange LED Green LED Condition Possible Cause Action Diagnostic Mains Normal Mains present None operation Battery fully charged Standby Mains Lost. No faults present Investigate loss of mains Operation Battery driving load Check and replace output Output fuse blown fuse LASH...
  • Page 5 Mounting – C Box – 7 Ah The C box is designed to support two 7 Ah or 2.1 Ah batteries and as such weighs a total of 8 Kg when loaded. Ensure that wall fixings are appropriate to support this weight. Mounting –...
  • Page 6 OMMISSIONING Mains Power Up With no external connections made to the PSE, connect the mains input wires to the terminal block, ensuring that the mains isolator (disconnect device) is open. Fasten wiring in place with cable tie to saddle. Note: Equipment must be earthed. Apply mains input.
  • Page 7: Maintenance

    Standby Battery Mount the appropriate batteries as shown in Figure 2. Where a dual box solution is used all cabling between the two boxes should be routed to use separate case entry/exit holes from other cabling and use suitable bushes to protect the cables Connect the two 12 V standby batteries in series using the single cable provided.
  • Page 8 OMPLIANCE This power supply unit meets the essential requirements of the following EU Directives: CPR: 305/2011 EU 0843 EMC: 2004/108/EC Low Voltage: 2006/95/EC Elmdene International Ltd 3 Keel Close WEEE: 2012/19/EU Portsmouth PO35QD RoHS: 2011/65/EU 0843-CPR-0214 EN54-4:1997 +A1 +A2 Functional Standard: EN54-4:1997 +A1 +A2 Power Supplies intended for use in fire detection and fire alarm systems...

This manual is also suitable for:

Elmdene stx2402-c