Summary of Contents for Xiamen Milesight AM100 Series
Page 1
AM100 Series User Guide Xiamen Milesight IoT Co., Ltd.
Page 2
All information in this guide is protected by copyright law. Whereby, no organization or individual shall copy or reproduce the whole or part of this user guide by any means without written authorization from Xiamen Milesight IoT Co., Ltd. For assistance, please contact Milesight technical support: Email: iot.support@milesight.com...
Page 3
AM100 Series User Guide Revision History Date Doc Version Description Apr. 7, 2020 V 1.0 Initial version May 19, 2020 V 1.1 APP pictures replacement Add screen display mode and configuration Aug. 26, 2020 V 1.2 examples(Firmware 1.17) Sept. 14, 2020 V 1.3 Add screen alarm settings (Firmware 1.19) Nov.
AM100 Series User Guide 1. Product Introduction 1.1 Overview AM100 series is a compact indoor ambience monitoring sensor including motion, humidity, temperature, light, TVOC, CO , barometric pressure for wireless LoRa network. AM100 series is a battery powered device and is designed to be wall-mounted. It is equipped with NFC (Near Field Communication) and can easily be configured via a smartphone or a PC software.
AM100 Series User Guide 2.2 Product Overview Front Panel: ①E-ink screen ② NFC Area ③ LoRa Antenna (Internal) ④PIR Sensor ⑤Light Sensor Back Panel: ⑥Power button ⑦Battery Cover ⑧Mounting Holes ⑨Type-C Port 2.3 E-link Screen 2.3.1 Screen Description AM100 series provide 3 types of display modes: AM104 Mode 1 Mode 2...
Page 7
AM100 Series User Guide Mode 1 Mode 2 Mode 3 To learn what an icon means, find it below. Icon Description Screen Update Battery level Once per day Sync time with software or mobile APP 1 min The device joins the network. According to join status The device fails to join the network.
AM100 Series User Guide Show CO history tendency from 0 to 1400ppm. 2 min Show alarm when CO exceeds the threshold value.(1200 ppm by default) Note: AM100 series will do a full-screen refresh every 30 minutes in order to remove ...
AM100 Series User Guide 2.4 Dimensions(mm) 3. Power Supply Remove the battery cover and install two new AA/LR6 batteries. Batteries can be replaced on the fly. Note: AM100 series can also be powered by type-C USB port (5V, 100mA). When batteries ...
AM100 Series User Guide 4. Basic Configuration AM100 series sensor can be monitored and configured through one of the following methods: Mobile APP (NFC); Windows software (NFC or Type-C port). In order to protect the security of sensor, password validation is required when first configuration.
AM100 Series User Guide 4. Click “Read” to fetch the current data of sensor. 4.1.2 Template Settings Template settings are used for easy and quick device configuration in bulk. Note: Template function works only for sensors with the same model and LoRa frequency band.
Page 12
AM100 Series User Guide 4. Keep the two devices close until the APP shows a successful prompt. 5. Slide the template item left to edit or delete the template. www.milesight-iot.com...
AM100 Series User Guide 4.2 Configuration via PC Preparation: Dedicated NFC Reader or Type-C USB cable PC (Windows 10 is recommended) Toolbox: https://www.milesight-iot.com/software-download/ 4.2.1 Log in the Toolbox Make sure “Toolbox” is downloaded on your computer. Select one of the following methods to log in Toolbox.
AM100 Series User Guide 2. Select type as “NFC” and serial port as NFC reader port on Toolbox. 4.2.2 Basic Configuration 1. Click “Read” to read current data of the sensor. 2. When you perform one of the following operations, type the password and click “Enter”, then wait a few seconds until toolbox shows a successful prompt.
AM100 Series User Guide 4.2.3 Upgrade 1. Download AM firmware to your computer. 2. Go to “Maintenance -> Upgrade” page of Toolbox. 3. Click “Browse” and select the firmware from computer. 4. Click “Upgrade” to upgrade the device. Note: If NFC connection is selected, please keep the two devices close and don’t move them in order to get the best connectivity as possible when upgrading.
AM100 Series User Guide 3. Click”Browse” to select the correct template from computer. 4. Click”Import”to import the template to the device. 4.3 Configuration Examples 4.3.1 LoRa Channel Settings The configuration of LoRaWAN channel of AM104/AM107 must match the gateway’s. ® Refer to Appendix to check default channel settings of AM104/AM107.
AM100 Series User Guide 1-40, 60: Enabling Channel 1 to Channel 40 and Channel 60 All: Enabling all channels Null: Indicates that all channels are disabled 4.3.2 Time Synchronization Mobile APP Configuration: Open Toolbox APP and go to “Device ->Status”to click “sync” to sync the time on the screen.
AM100 Series User Guide 4.3.3 Alarm Settings AM100 series will upload the current data instantly after the threshold is triggered. AM107 will also show alarms of CO and TVOC on the screen. Mobile APP Configuration: Open Toolbox APP and go to “Device -> Setting -> Threshold Settings”to enable the threshold settings and input the threshold.
AM100 Series User Guide 5. Installation 5.1 Installation Note In order to ensure the best detection and LoRaWAN ® communication effect, it is recommended to install AM100 series as follows: There should not be any isolates or barriers in PIR and light detection range. ...
AM100 Series User Guide 6.1 Add a Milesight Gateway 1. Enable “Milesight” type network server and “Milesight IoT Cloud” mode in gateway web GUI. Note: Ensure gateway has accessed the Internet. 2.Go to “My Devices” page and click “+New Devices” to add gateway to Milesight IoT Cloud via SN.
AM100 Series User Guide 3. Check if gateway is online in Milesight IoT Cloud. 6.2 Add AM100 Series to Cloud 1. Go to “Device->My Devices” and click “Add Device”. Fill in the SN of AM sensor and select associated gateway. 2.After sensor is connected to Milesight IoT Cloud, you could check the device information and data and create dashboard for it.
AM100 Series User Guide 7. Sensor Payload All data are based on following format(HEX): Channel1 Type1 Data1 Channel2 Type2 Data2 Channel 3 1 Byte 1 Byte N Bytes 1 Byte 1 Byte M Bytes 1 Byte 7.1 Basic Information AM500 series sensors report basic information of sensor everytime joining the network. Channel Type Data Example...