Reliable EX Series Manual

Reliable EX Series Manual

For single interlock preaction system type a

Advertisement

Features
Redundant Solenoid Valve Release
Externally Resetable Clapper
One Main Drain
Product Description
Reliable Single Interlock Preaction Systems are designed for
water-sensitive areas that require protection from inadvertent
water flow into the sprinkler system piping. A single event, the
activation of the electrical detection system, causes the valve to
operate and flow water into the piping network.
Sprinkler piping in single interlock systems can effectively
be supervised by means of the Reliable Model A Pressure
Maintenance Device (provided) and a tank-mounted air
compressor. Loss of supervising pneumatic pressure, due to
a damaged sprinkler or sprinkler pipe will not cause water to
flow through the Model EX Valve and into the system piping. A
significant loss of pneumatic pressure will activate a trouble-
annunciating device when the system pressure falls below a
predetermined pressure level.
The system incorporates two normally closed solenoid valves on
the releasing trim. These solenoid valves, when closed, retain
sufficient AIR pressure on the pneumatic actuator, which in turn
preserves sufficient WATER pressure in the push rod chamber
of the Model EX Valve in order to maintain it closed. When the
electrical detection system senses the presence of fire, the
electrical releasing control panel activates fire alarm devices and
energizes the two redundant, normally-closed solenoid valves into
the open position.
Energizing the solenoid valves relieves the air pressure on the
pneumatic actuator, thereby releasing the water pressure that it
was retaining. This in turn relieves the pressure in the push rod
chamber of the Model EX Valve. Venting the push rod chamber
will open the Model EX Valve and allow water to flow into the
sprinkler system.
Water flowing into the sprinkler system piping will simultaneously
produce water pressure that causes the transfer of contacts in
the pressure switch mounted in the trim. This pressure switch can
Valve Size
2" (50mm), 2-1/2" (65mm), 76mm &
3" (80mm)
4" (100mm)
6" (150mm) & 165mm
8" (200mm)
Availability: UK
electrically initiate the shutdown or startup of equipment, such as
computers or other second alarm devices. The flow of water into
the sprinkler system piping effectively converts the dry system
into a wet pipe system. In the event that the fire subsequently
produces sufficient heat to operate a fire sprinkler, water will flow
from that sprinkler, controlling or suppressing the fire.
The major benefits of a single interlock preaction system, when
compared with a wet pipe (deluge) system are as follows:
1.
A fire alarm sounds prior to the operation of a sprinkler,
which may enable extinguishing the fire by handheld means
before the actual operation of any sprinklers and subsequent
water damage.
2.
A trouble annunciator signals whenever the integrity of the
piping or sprinklers is accidentally or intentionally disturbed;
however, no water flow or water damage will occur at that
time.
3.
Speedy detection and an early fire alarm are provided by
fire detectors, without the delay associated with water flow
detection in the event of a fire. Note: with a wet pipe system,
the fire alarm is delayed until after water has begun flowing
from an operated sprinkler.
End Connection
Groove/ Groove
Groove/ Groove
Flange/ Groove
Flange/ Flange
Groove/ Groove
Flange/ Groove
Flange/ Flange
Groove/Groove
Flange/Flange
www.reliablesprinkler.com
Bulletin 739 January 2021
Model EX Single Interlock
Preaction Type A (LPCB)
2", 2-1/2", 76mm, 3", 4", 6", 165mm, & 8"
Approx. Shipping Weight
44lbs (20kg)
74lbs (34kg)
105lbs (48kg)
158lbs (72kg)
Table A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EX Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Reliable EX Series

  • Page 1 Sprinkler piping in single interlock systems can effectively be supervised by means of the Reliable Model A Pressure Maintenance Device (provided) and a tank-mounted air compressor. Loss of supervising pneumatic pressure, due to a damaged sprinkler or sprinkler pipe will not cause water to flow through the Model EX Valve and into the system piping.
  • Page 2 Model EX Single Interlock Preaction System Type A Technical Data Listings and Approvals Technical Specifications LPCB Pressure Rating: 175 psi (12,1 bar) End Connections Minimum Water Supply Pressure: See Table A 20psi (1,4 bar) Minimum Water Supply Temperature: Specifications 40°F (4°C) Groove: ANSI/AWWA C606 Maximum Water Supply Temperature: Flange: ASME B 16.5 or ISO 7005-2 PN16...
  • Page 3: System Operation

    The nylon cable piping. The Reliable Model EX Valve is shown in both closed and tie is designed to allow, in case of an emergency, forceful turning of open positions in Fig.2.
  • Page 4: System Design Considerations

    Note: During the initial system set-up, a higher pneumatic pressure may be required in order to properly seat the internal diaphragm of the pneumatic actuator. Refer to Reliable Bulletin 251 for instructions on how to modify these pressure settings. Friction Loss...
  • Page 5 Single Interlock Preaction System Air Pressure Settings Figure 3 Bulletin 739 Page 5 of 9 January 2021 www.reliablesprinkler.com...
  • Page 6 Model EX Type A Components Figure 4 Resetting the Model EX Single Interlock 11. Open the main drain approximately two turns. 12. Open the pushrod chamber supply valve. System (Ref. Fig. 5) 13. Slightly open the main control valve until water can just be heard running out the main drain.
  • Page 7: Inspection And Testing

    O-rings, proceed to step 8. in proper operating condition. Any system maintenance or testing Using Reliable P/N 6881603000 Seat Wrench for 2” (50mm), that involves placing a control valve or detection/control system out 2½” (65mm), 76mm and 3” (80mm) valve sizes, Reliable of service may eliminate the fire protection that is provided by the fire P/N 6881604000 for 4”...
  • Page 8: Troubleshooting

    Solenoid Valve Clapper Gasket and Seat Replacement Procedure (cont.) WARNING: The owner is responsible for maintaining the 8 (cont). Reach into the valve and grasp the seat and remove fire protection system in proper operating condition. Any it from the valve. Then remove the clapper-mounting ring system maintenance or testing that involves placing a control subassembly from the valve.
  • Page 9: Listing & Approvals

    Ordering Information CONDITION TWO (System Air coming out of the bleed hole): Specify: System air coming out of the bleed hole is caused by a worn O-ring Model EX Single Interlock Preaction System Type A assembled to the pushrod guide. Remove the piston-pushrod •...

Table of Contents

Save PDF