EXA Modulating Valve Series

CONNECTIONS

Step 1: Remove 2 screws holding cover.
Step 2: Switch power and control signal off.
Step 3: Connect switched OFF 24V (AC/DC) power source to
terminals 3 and 4. Note polarity when using a DC power
source or if one leg of an AC transformer secondary is
externally grounded or is sharing power with another
half-wave device (see figure 2, page 2).
Step 4: Set DIP switches to match available control signal
(see table 3, page 2).
Step 5: Connect control signal to terminals 1 and 2.
Observe polarity. Note that the return, or signal
ground, must be connected to terminal 2 (see figure
2, page 2).
Step 6: Switch power and control signal ON.
Step 7: Set valve (see "Valve Setting" in section below).
Step 8: Replace cover.

VALVE SETTING

The EXA STAR modulating valve series has two (2) buttons and
a communication LED for the user interface. The buttons are
used to set the valve for high and low fire settings (see figure 4).
1. High Fire Setting (LED will be solid red)
2. Low Fire Setting (LED will be blinking red)
3. Operating Mode (LED will be OFF)
Button 1
Figure 4: EXA Modulating Valve Series Adjustment Controls
Maxitrol Company
23555 Telegraph Rd., P.O. Box 2230
Southfield, MI 48037-2230 U.S.A.
EXA_X1_MS_EN_06.2019

HIGH FIRE SETTING - BUTTON #1

To enter the high fire setting mode, press and hold Button #1
until the LED lights solid red. Release. The valve is now in the
high fire setting mode. Buttons #1 and #2 are used to set desired
high fire setting.
To increase gas flow slowly, press button #1. Each button
press will increase gas flow by the minimum available
step size. To increase gas flow rapidly, hold button #1.
Holding the button down allows the valve to auto step
and eliminates the need to repeatedly press the button.
To decrease gas flow slowly, press button #2. Each button press
will decrease gas flow by the minimum available step size. To
decrease gas flow rapidly, hold button #2. Holding the button
down allows the valve to auto step and eliminates the need to
repeatedly press the button.
To save the high fire setting, simultaneously hold buttons #1 and
#2 until the LED turns OFF.
NOTE: Controls left in any setting mode will default to the

LOW FIRE SETTING - BUTTON #2

To enter into the low fire setting mode, press and hold Button
#2 until the LED light blinks red. Release. The valve is now in
the low fire setting mode. buttons #1 and #2 are used to set the
desired low fire setting.
To decrease gas flow slowly, press button #2. Each button press
will decrease gas flow by the minimum available step size. To
decrease gas flow rapidly, hold button #2. Holding the button
down allows the valve to auto step and eliminates the need to
repeatedly press the button.
To increase gas flow slowly, press button #1. Each button press
Button 2
will increase gas flow by the minimum available step size. To
increase gas flow rapidly, hold button #1. Holding the button
down allows the valve to auto step and eliminates the need to
LED
repeatedly press the button.
To save the low fire setting, simultaneously hold Buttons #1 and
#2 until the blinking LED turns OFF.
NOTE: Controls left in any setting mode will default to the
© 2019 Maxitrol
4
current settings and return to normal operating mode
after 5 minutes of inactivity.
current settings and return to normal operating mode
after 5 minutes of inactivity.
www.maxitrol.com
© 2019 Maxitrol Company,
All Rights Reserved.