6v 11w 120/277v 60hz emergency luminaire damp location standard wet loc. / battery heater optional

Advertisement

OPERATING INSTRUCTIONS
(1): Energize AC power to equipment and check that pilot lamp illuminates red.
(2): Press test switch and verify pilot lamp turns off and lamp heads illuminate.
(3): Leave AC connected for a minimum of 24 hours before performing any extended testing. Full
recharge of battery may take up to one (1) week.
A.
This equipment is provided with a lockout feature whereby connecting battery leads prior to
energizing AC power will not turn on the emergency lamps. After AC power is energized, the
emergency lamps will turn on upon AC power failure.
B.
This equipment is provided with a low battery disconnect feature which prevents full discharge
of battery. If the building is to be unoccupied for an extended period and AC is shut off, the battery
should be disconnected from the charger to prevent damage.
C.
The battery in this unit is sealed and requires no maintenance.
(1): For servicing, remove tamper proof screw (if installed). Then remove cover by inserting a small
screwdriver or similar tool into the hole in the bottom of the cover and press upward to release locking
tab. Pull over up and off of unit.
(2): Remove electronics module from backplate by inserting a flat bladed screwdriver between
backplate and module and prying module away from backplate.
Philips Lighting North America Corporation
200 Franklin Square Drive
Somerset, NJ 08873, USA
Phone: 855-486-2216
www.philips.com/luminaires
NOTE
SERVICING
Philips Lighting Canada Ltd.
281 Hillmount Road,
Markham, ON, Canada L6C 2S3
Phone: 800-668-9008
www.philips.com/luminaires
9140052682 February 2016

Advertisement

loading