Installation, Maintenance & Troubleshooting guide | Version 03
LMR-A: Auto mode
7A : Keep the LMR-A in Auto mode.
7B : Switch ON the 3-Phase incoming main supply.
7C : Turn ON the rocker switch.
7D : Amber LED will start blinking for a period of min 0.5 min.
7E : 0.5 min is the default setting which can vary from min 0.5 min to max.5min.
7F : After the ON-delay duration, amber LED will ON continously indicating that the incoming supply is
healthy(Assuming incoming supply is healthy).
7G : Not applicable (No need to press ON push button)
7H : Starter gets switched ON automatically.
7I : Green LED turns ON indicating that the starter is ON.
7J : Starter switches OFF automatically after the above step '1K'
7K : Green LED turns OFF indicating that the starter is OFF.
7L : Amber LED indication remains continous ON.
7M : Switch OFF the 3-phase incoming main supply.
7N : Amber LED indication gets turned OFF indicating that there is no incoming main supply.
LMR-A: Bypass mode
7A : Keep the LMR-A in Bypass mode.
7B : Switch ON the 3-Phase incoming main supply.
(*Customer may switch ON the starter directly after switching ON the 3 phase incoming supply irresepctive of Blinking
status as there is only indication for incoming supply faults and no Protection in Bypass mode).
7C : Turn ON the rocker switch.
7D : Amber LED will start blinking for a period of min 0.5 min.
7E : 0.5 min is the default setting which can vary from min 0.5 min to max.5min.
7F : After the ON-delay duration, amber LED will ON continously indicating that the incoming supply is healthy
(Assuming incoming supply is healthy).
7G : Press the green push putton for switching ON the starter.
7H : Starter gets switched ON.
7I : Green LED turns ON indicating that the starter is ON.
7J : Starter switches OFF automatically after delivery tank water level reach P3 sensor level.
7K : Green LED turns OFF indicating that the starter is OFF.
7L : Amber LED indication remains continous ON.
7M : Switch OFF the 3-phase incoming main supply.
7N : Amber LED indication gets turned OFF indicating that there is no incoming main supply.