5. Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
Indoor temperature of 30°C and humidity of 85% is the standard condition. If install in a high humidity condition, use one grade thicker
insulator by referring to the table below. If installing in an unfavorable conditions,use thicker one.
Insulator's heat-resistance temperature should be more than 120°C.
Pipe
Pipe size
ø
6.35~
Liquid
ø
pipe
12.70~
Gas
Pipe
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
 You can contact the gas side and liquid side pipes but the pipes
should not be pressed.
 W hen contacting the gas side and gas side pipe, use 1 grade thicker
insulator.
Refrigerant pipe after EEV kit and MCU
 Install the gas side and liquid side pipes, leave 10mm of space.
 W hen contacting the gas side and liquid side pipe, use 1 grade
thicker insulation.
• I nstall the insulation not to get wider and use the adhesives on the connection part of it to
prevent moisture from entering.
• W ind the refrigerant pipe with insulation tape
if it is exposed to outside sunlight.
• I nstall the refrigerant pipe respecting that the
insulation does not get thinner on the bent
part or hanger of pipe.
• Add the additional insulation
if the insulation plate gets thinner.
Standard
[30°C, 85%]
ø
9.52
ø
50.80
ø
6.35
ø
9.52
ø
12.70
ø
15.88
ø
19.05
ø
22.23
ø
25.40
ø
28.58
ø
31.75
ø
38.10
ø
44.45
ø
50.80
Additional insulation
Insulation Type(Heating/Cooling)
High humidity
[30°C, over85%]
EPDM, NBR
9t
13t
13t
19t
25t
Insulation
Gas pipe
10mm
a
a×3
Remarks
9t
13t
19t
25t
Internal temperature
is higher than 120°C
32t
38t
Insulation
Liquid pipe
10mm
10mm
10mm
Gas pipe
Liquid pipe
Hanger
Refrigerant pipe insulation
15