LG MULTI F Engineering Manual page 19

Multi-zone heat pump systems, 1.5 to 5 tons
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
Electrical Data
Table 15: Electrical Data.
Nominal
Unit Model No.
Tons
1.5
LMU180HV
1.5
LMU18CHV
2
LMU240HV
2
LMU24CHV
2.5
LMU30CHV
3
LMU36CHV
Voltage tolerance is ±10%.
Maximum allowable voltage unbalance is 2%.
RLA = Rated Load Amps.
MCA = Minimum Circuit Ampacity.
Voltage
Hertz Voltage
Range
(Min. to Max.)
60
208 - 230
187 - 253
Maximum Overcurrent Protection (MOP) is calculated as follows: (Largest
motor FLA x 2.25) + (Sum of other motor FLA) rounded down to the nearest
standard fuse size.
Indoor Fan Motor (FLA) is based on the maximum combination of indoor
units.
The max combination for each outdoor unit is:
©
MULTI F OUTDOOR UNIT
Compressor
Compressor
MCA MOP
Quantity
Motor RLA
15.8
20
1
13.3
20
1
16.0
20
1
14.3
20
1
16.6
25
1
17.9
25
1
- 18,000 ODU (LMU180HV / LMU18CHV): 12,000 IDU x 2
- 24,000 ODU (LMU240HV / LMU24CHV): 12,000 IDU x 2 + 9,000 IDU x 1
- 30,000 ODU (LMU30CHV): 12,000 IDU x 3
- 36,000 ODU (LMU36CHV): 12,000 IDU x 4
Electrical Data
Outdoor Fan Motor
kW
FLA
12.0
0.085
0.40
8.9
0.09
0.59
12.0
0.085
0.40
9.4
0.09
0.59
10.8
0.12
0.73
11.2
0.12
0.73
MULTI F OUTDOOR UNIT | 19
Indoor
Fan Motor
FLA
0.40
1.60
0.60
2.00
2.40
3.20