LG MULTI F Engineering Manual page 17

Multi-zone heat pump systems, 1.5 to 5 tons
Hide thumbs Also See for MULTI F:
Table of Contents

Advertisement

F
MULTI
F
MULTI
MAX
Table 9:
System
Combined With
Non-Ducted
Indoor Units
LMU180HV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Table 10:
System
Combined With
Non-Ducted
Indoor Units
LMU18CHV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Table 11:
System
Combined With
Non-Ducted
Indoor Units
LMU240HV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Table 12:
System
Combined With
Non-Ducted
Indoor Units
LMU24CHV
Ducted Indoor Units
Mixed Non-Ducted and
Ducted Indoor Units
Rated capacity is rated 0 ft. above sea level with 25 ft. of refrigerant line per indoor unit and a 0 ft. level difference between outdoor and indoor
1
units. All capacities are net with a combination ratio between 95 – 105%.
Rated cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet bulb (WB) and outdoor ambient conditions
of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Rated heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet bulb (WB) and outdoor ambient conditions
of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
2
values.
At least two indoor units must be connected. For allocated capacity information, see the combination tables in the "Multi F / Multi F MAX Combina-
tion Data Manual" on www.lghvac.com. For performance data, see "Multi F / Multi F MAX Performance Data Manual" on www.lghvac.com.
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
18,000
13.5
17,200
12.5
17,600
13.0
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
17,000
13.0
14,000
10.7
15,500
11.8
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
23,600
13.5
22,000
12.5
22,800
13.0
1,2
Rated Cooling
EER
Capacity (Btu/h)
(95°F)
20,000
13.5
17,800
11.5
18,900
12.5
©
MULTI F OUTDOOR UNIT
Rated Heating
COP
SEER
Capacity (Btu/h)
(47°F)
22.5
22,000
3.60
18.5
20,000
3.27
20.5
21,000
3.43
Rated Heating
COP
SEER
Capacity (Btu/h)
(47°F)
22.0
22,000
3.2
17.2
19,800
2.9
19.6
20,900
3.0
Rated Heating
COP
SEER
Capacity (Btu/h)
(47°F)
22.5
24,600
4.20
18.5
23,000
3.47
20.5
23,800
3.81
Rated Heating
COP
SEER
Capacity (Btu/h)
(47°F)
21.7
24,000
3.9
17.5
22,500
3.4
19.6
23,250
3.7
General Data
Low Heating
COP
HSPF
Capacity (Btu/h)
(17°F)
11.0
14,500
2.66
9.6
13,000
2.47
10.3
13,750
2.57
Low Heating
COP
HSPF
Capacity (Btu/h)
(17°F)
9.7
13,500
2.4
9.7
13,000
2.4
9.7
13,250
2.4
Low Heating
COP
HSPF
Capacity (Btu/h)
(17°F)
11.0
15,200
2.89
9.8
14,500
2.64
10.4
14,850
2.76
Low Heating
COP
HSPF
Capacity (Btu/h)
(17°F)
10.6
14,500
2.7
9.8
14,000
2.5
10.2
14,250
2.6
MULTI F OUTDOOR UNIT | 17