The fresh warm air is channelled draught-free and noise-free into the premises in necessary quantities. ENSURE THE QUALITY OF AIR EXCHANGE! DEEKAX Air Oy Patruunapolku 4 Puh. 0207 912550 79100 LEPPÄVIRTA www.deekaxair.fi...
Page 2
Talteri heat recovery system SYSTEM COMPONENTS EXHAUST AIR DLVS-200/435 Picture 1 **** 1 Air exchange unit..DIVK-C140 DEMA däv-200 2 Adjustment cover..DX-ULTRA 3 Exhaust air outlets..DLVS-200/435 DIVK 4 Channel noise deductor..SUPPLY AIR EXTRACT AIR OUTDOOR AIR 5 Exhaust air for the system..200 6 Outdoor air for the system..
Page 3
INSTALLING THE CHANNELLING The channels for exhaust air and incoming air should be installed, if possible, in a warm space below the vapour barrier to suspended ceilings or casing. The vapour barrier remains intact and the channels do not need heat insulation.
Page 4
TALTERI INSTALLATION The air exchange unit is meant for warm inner facilities. Suitable installation spots are, among others, office, dressing or household facilities and technical or warm storages. In case the temperature of the installation location is lower than room temperature, the factory settings of the appliance must be changed to obtain faultless functioning. The unit can not be installed into cold outer premises or garages.
ELECTRICAL CONNECTIONS The following can be connected as accessories: Electrical connections must be done following the installation manual - Carbon dioxide transmitter; and wiring diagram. - Humidity transmitter; - Separate overpressure or Extended time switch ELECTRICAL CONNECTIONS CAN BE DONE ONLY BY (pulse switch);...
Page 6
C 140 DEMA A/D+ B/D- O O O ON OFF BIAS B O O O ON OFF Term O O O ON OFF BIAS A PRE- Circuit board HEATER CONTROL PRE- POST- HEATER PANEL HEATER 1000W OUT-OF-HOUSE/ OVERPRESSURE/ CO2/%RH1 CO2/%RH2 BOOSTING REMOTE FILTER...
Page 7
Water heater (VKL) Talteri installation is equipped with a note - The desingn must take into account the water temperatures used and chech the adequacy of the the heating power under the design conditions. - The afterheating coil is connected inside the machine with a copper or similar plastic tube - The water entering the machine must be pre-adjusted after the boiler.
Page 8
DIVK C-140 DEMA air flow EXTRACT AIR SUPPLY AIR 100% 100% dm3/s Air flow dm3/s Air flow EC speeds preselection is performed from the control panel maintenance menu. Inlet and outlet fans can be individually adjusted for five different speeds with fan speeds of 20-100% INTRODUCTION OF THE AIR EXCHANGE SYSTEM...
INTRODUCTION OF THE AHU CONTROL PANEL Settings are applied via the service menu SERVICE MENU Note: swipe right at SETTINGS the top of the screen 0-10V SPEED CONTROL WITH COOKER HOOD 0-10V external control (0-10V hood,remote monitoring) select the deployment SENSOR 1 "EXT"...
OPERATING PANEL USER INSTRUCTION MAIN DISPLAY AND ADJUSTMENT OF BLOWING SPEED CLOCK THE DISPLAY ALSO SHOWS POSSIBLE INCREASED EFFICIENCY AND MALFUNCTIONS EDIT Touch screen buttons: HUMIDITY AND CARBON DIOXIDE VALUE Fan speed adjustment 1..5 IF SENSORS ARE INSTALLED (accessory equipment) TEMPERATURE DISPLAY FOR Out-of-house mode TEMPERATURE OFOUTSIDE AIR,...
SETUP MENU SETTINGS Fan speed adjustment 1..5 Touch screen buttons: Fan speed adjustment 1..5 Out-of-house mode Fireplace switch (pressure compensation) Boosting The button can be used to browse menu upwards and change settings. Maintenance interval and reset The button can be used to browse menu downwards and change setting value.
MAINTENANCE MENU SETTINGS Touch screen buttons: Fan speed adjustment 1..5 Out-of-house mode Office-mode (extended time) NOTE!:SWIPE RIGHT AT THE TOP OF THE SCREEN Boosting HOME overpressure activated The button can be used to browse menu upwards and change settings. OFFICE continuation time activated The button can be used to browse menu downwards and change setting value.
Page 13
Regulation of Inlet Air and Pre-heating value Freeze-alert settings -10…10 The value of pre-heating should be regulated to be approx 5c higher than the limit of cold exhaust air Overpressure duration specification 0 and 5...20min. In 0 position with different switch pre-data Overpressure limit regulation 1...4 (inlet air impeller Anti-freeze appliance’s control higher than outlet air impeller)
OPERATIONAL DESCRIPTION 1. Operating panel The operation is directed according to settings inserted by the user or installer/manufacturer through the operating panel as well as according to temperature sensors and set periods. The operating panel returns from processing state to basic state 2 minutes after the last button pressing. The return time from normal position is 2 minutes.
3.7. Office mode The installer can select the office mode from the maintenance menu – this is useful in case the air exchange system is installed into an office where activities take place mostly during daytime. The mode is equipped with co ntinuation switch that enables persons who remain in the office for longer to prolong the functioning of the appliance by set interval.
Page 16
The channels must be checked if the impeller works but the air exchange is inadequate or the temperature changes in the channels between the interior and the machine. Temperature changes and humidity concentration in channels must be prevented by improving the isolation. DEEKAX Air Oy Patruunapolku 4 Puh. 0207 912550...