5 DIMENSIONS
MU1H-0511GE23 R0720
159 mm
GB
6 ERROR CODE DESCRIPTION
Code Description
2
No flow despite correct dT difference
4
Power sensor error
8
Return sensor error
16
Reverse temperature difference error
32
(Maximum) flow exceeded error
64
Low level of main battery or mains power supply
failure
128
Low level of backup battery
256
Additional input alarm
512
Improper flow direction
1024
Flowmeter signal too weak (air)
2048
Flowmeter measuring system damaged
4096
No communication with the flow transducer
16384 Improper module 1
32768 Improper module 2
9
Response
time
conf.
<10 s
<10 s
<10 s
<10 s
<10 s/<24 h
<24 h
<1 s
<1 min
<1 min
<1 min
<1 min
<10 s
<10 s