SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 1. General 250.186 for application details (applies to SE-330 and SE-330HV). This is a combined manual for the following products: System charging current is the capacitive current that SE-330 Neutral-Grounding-Resistor Monitor • flows to ground when a bolted ground fault occurs. This current can be calculated or measured.
Page 5
NGR current will flow if the NGR is healthy. The SE-330 For the SE-330 and SE-330HV, relays K1, K2, and K3 will trip on ground fault if fault current exceeds the GF...
(V GF TRIP TIME (definite time) is adjustable from 0.1 to The SE-330 series will trip and indicate a resistor fault if 10.0 seconds for the SE-330 and SE-330HV, and from neutral voltage is greater than the V TRIP LEVEL setting 0.1 to 0.5 seconds for the SE-330AU.
Page 7
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 For the SE-330HV, the V TRIP LEVEL range is 100 to 10,000 V with switch S5 in the 100-kΩ (Vx1) position, and the range is 200 to 20,000 V with switch S5 in the 200-kΩ...
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Table 2. Typical Values for Tripping Systems (SE-330AU) SYSTEM VOLTAGE EARTH-FAULT TRIP LEVEL NEUTRAL-EARTHING RESISTOR (VOLTS) (AMPERES) TRIP SENSING LEVEL SE-CS30-X RESISTOR CURRENT RESISTANCE EFCT-X LINE TO LINE TO (VOLTS) (30-A LINE NEUTRAL (AMPERES) (OHMS)
K1 and to activate switch S2. Relay K1 will change FIGURE 1. SE-330 Configuration Switches. state when a resistor-fault or ground-fault trip occurs. Other trip functions can be assigned to K1 (SE-330 and SE-330HV only) using SE-MON330 software or via network communications.
The contacts will open in the and this may cycle the output relays. event of a trip, a loss of supply voltage, or a processor failure. In the fail-safe mode, SE-330 trips are not reset when the supply voltage is cycled. 2.1.6 Resistor-Fault Trip Time...
If switch S1 is set to K1 = PULSING, pulsing occurs when switch S3 or S4 is set to non-latching. SE-330 and SE- terminal 16 is connected to terminal 17. Relay K1...
Resistor-fault-trip reset can take up to one second. A resistor-fault trip-memory trip can take up to three Starting with SE-330 firmware version 2.60 and SE- seconds after the monitor powers up. MON330 software version 3.8, the SE-330 can be configured to show only critical diagnostic codes.
3.1 SE-330 Series Outline and panel cut-out dimensions for the SE-330 series are shown in Fig. 8. To panel mount the SE-330, insert it through the panel cut-out and secure it with the four included 8-32 locknuts and flat washers.
1000HV to moisture. See Figs. 13 and 14. The condensation. Sensing-resistor terminal R and its weather-protected ER-5WP shown in Fig. 16 is an connection to SE-330 terminal R, including interposing ER-5KV with moisture-resistant terminal covers. Use an terminal blocks, must remain dry.
Outline and mounting details for the EFCT- and SE-CS30-series current sensors are shown in Figures NOTE: The current-sensor insulation class is of no 26, 27, and 28 (compatible with SE-330 and SE-330HV, consequence if its secondary is grounded and the but must be used with SE-330AU).
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 TOP VIEW AND MOUNTING DETAIL NOTES: 1. DIMENSIONS IN MILLIMETERS [INCHES] 2. MOUNTING SCREWS: M6 OR ¼ IN. FRONT VIEW SIDE VIEW FIGURE 24. ELCT5-88 and ELCT30-88 Ground-Fault Current Sensors...
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 TOP VIEW AND MOUNTING DETAIL NOTES: 1. DIMENSIONS IN MILLIMETERS [INCHES] 2. MOUNTING SCREWS: M5 OR #10 FRONT VIEW SIDE VIEW FIGURE 25. ELCT5-31 and ELCT30-31 Ground-Fault Current Sensors.
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 FIGURE 29. RK-332 Remote Indication and Reset. FIGURE 30. PGA-0520 Analog Percent Current Meter.
An isolated ground bed can prevent a ground potential rise (GPR) from being transferred to remote equipment. If the G terminals on the sensing resistor and the SE-330 series are connected to an isolated ground, the SE-330 series will be exposed to the GPR. If the GPR is greater...
Do not manufacturer, model, and with varying environmental remove the SD card or power off the SE-330 until the conditions. The included microSD card has a DIAGNOSTIC LED has stopped blinking rapidly for at temperature rating of -25 to 85°C (-13 to 140°F).
Please consult local regulations regarding the use of batteries in electrical equipment. The SE-330, SE-330HV, and SE-330AU battery is not designed for user service or removal; please contact Littelfuse with any questions regarding battery...
Critical diagnostic code. GF LED : No Change, RF LED : ON, Assigned Relay:Trip The SE-330 was tripped by a signal from network communications. Press RESET to clear the trip. Remote Trip 1 L - 2 S - 1 L Critical diagnostic code.
Page 46
GF LED : No Change, RF LED : No Change, Assigned Relay :No Change SE-330 processor failed to start. Cycle supply. If problem persists, consult DIAGNOSTIC LED = Solid Red Littelfuse. K1: De-energized. Trip condition is still present. Locate and correct.
Power-Up Time ......3 s at 120 V ac AC Measurements ...... Discrete Fourier Trip Time SE-330 and SE-330HV ....12 to 60 s ± 1 s Transform.16 samples per cycle, SE-330AU ........10 s maximum 50 or 60 Hz Trip Mode SE-330 and SE-330HV ....
Page 48
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 NGR Open Mode ....... Sensitive or Standard Temperature 0 to 40°C ..50 Ω minimum Sensitive Trip Level ....130 to 200% of Temperature -40 to 60°C..75 Ω minimum Max NGR Resistance ..10000 Ω...
Page 49
Configuration ......... N.O. (Form A) SE-330AU: Operating Mode: Trip Level SE-330 and SE-330HV ....Fail-Safe or Non-Fail-Safe EFCT-x ........0.125, 0.25, 0.30, 0.40, SE-330AU ........Fail-Safe only 0.50, 1, 2, 3, 4, 5 A CSA/UL Contact Ratings ....8 A resistive 250 V ac, SE-CS30-x ......
Page 50
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Configuration ........N.C. (Form B) Tightening Torque ......0.5 to 0.6 N⋅m (4.4 to 5.3 lbf⋅in) Operating Mode ......Open when Healthy Ratings ........... 100 mA, 250 V (ac or dc) PWB Conformal Coating ....MIL-1-46058 qualified, Closed Resistance ......
Page 51
AS/NZS 2081.6:2011 – Earth Fault Protection Devices dc value AS/NZS 2081.8:2011 – NER Integrity Protection Devices Certification SE-330 and SE-330HV....CSA, Canada and USA NOTES: See sensing resistor specifications for applicable voltage limits. Accuracy included for EFCT-x and SE-CS30-x current sensors only.
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 This value can only be modified using SE-MON330 software. See ER-15KV: Section 4.2. Maximum Voltage ....8,400 Vac Use sensitive mode for AS/NZS 2081.8:2011 compliance. Maximum Current ....84 mA Standard mode is available when using NER Resistance ......
Compliance ........RoHS, IEC 60044-1 Extended Operating Temperature .. -55 to 60° C (-67 to 140° F) NOTES: SE-CS30-70: Electrical specifications have been verified at a Littelfuse lab. Current Ratio ......... 30:0.05 A Insulation ........600-V Class 6.3 Current Sensors Window Diameter ......
Page 54
Certifications ........cUL, CE ELCT5-88 Current Ratio ........5:0.05 A Insulation ........600-V Class Window Diameter ......88 mm (3.46 in.) Shipping Weight ......0.91 kg (2 lb) Certifications ........cUL, CE NOTES: Electrical specifications have been verified at a Littelfuse lab.
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 7. Ordering Information NOTE: Please refer to the SE-330 Product Change Notice (PCN) document for updated ordering information and new revision details, available at Littelfuse.com/SE-330. NOTE: The SE-330-SMA Surface Mount Adapter is available as an accessory only.
Page 57
SE-MON330 Software ..SE-330 Data-Display Program for PC, version 4.1 or higher NGR Monitor Set-Point Assistant ......Setting Guide NOTES: Profibus models only available on legacy SE-330. Includes Modbus TCP and EtherNet/IP protocols. Includes IEC 61850 protocol only. Available at Littelfuse.com/relayscontrols...
10 s if calibrated and the Littelfuse will (at Littelfuse option) repair, replace, or NGR Short Mode is set to Sensitive). refund the original purchase price of the SE-330 that is determined by Littelfuse to be defective if it is returned to h) Press RESET.
Short R1 (resistance total is 100,000 Ω) and wait for the resistor-fault trip time. NOTE: Use an isolation transformer if the test-voltage m) PASS: The SE-330 should trip on resistor fault. source does not provide dc continuity for the SE-330 resistance-measuring circuit.
9.3 Analog-Output Test Procedure: Test Equipment: ...... Multimeter with a mAdc a) Connect the ER sensing resistor to the SE- 330HV and calibrate the SE-330. scale. b) Disconnect the wire from sensing-resistor terminal N. A resistor-fault trip will occur. Procedure: c) Set the voltage source to 0 V.
The connection of the current-sensor secondary to the SE-330 is not polarity sensitive. c) Verify that the system is correctly grounded and that alternate ground paths do not exist that bypass the current sensor.
USB driver prior to running SE-MON330. DATE TEST RESULTS For an SE-330 (new revision) with a USB interface, SE- MON330 should be installed prior to connecting the SE- 330 so that the USB driver is properly installed. When the SE-330 is connected, a USB COM port will appear on the computer.
Once these parameters are confirmed, set the Essential Settings Verified parameter to Settings Verified. The Initial Configuration tab is shown when connecting to an SE-330 (firmware version 3.10 or higher) for the A2.2 Summary Tab first time (Fig. 35). This screen shows important settings...
The configuration tab displays all available items that 330. can be configured for the connected SE-330 (fig. 38). The GF Trip Level is set on the front-panel of the SE-330 or SE-330HV as a percentage of the CT-primary rating A2.4.1 Resistor fault (2 to 100).
Rev.11-B-121520 1% increments. The drop-down list displays the percentage along with the equivalent trip level current. For the SE-330 and SE-330HV (K1, K2, K3) and SE- The default setting is 15%. 330AU (K2, K3) The Effective CT Primary is based on the type of earth- fault CT used, and the connection to the SE-330.
5 s, and the minimum time is 1 s. If a request connection problems with the NTP Server, monitor the fails, no change is made to the SE-330 internal clock. SNTP Client status. The status indicates problems such as NTP Server not found, NTP Server not running, and A2.5 Event Records Tab...
A2.6.5 Remote Calibration drop-down menu, select voltage setting to specify the Vn trip level being used on the SE-330. Note that on the SE- To initiate a remote calibration (new revision SE-330 330 with USB, the voltage setting is updated series only), select Remote Calibration from the System automatically when the SE-330 is connected.
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 A2.7 Using Set-Point Assistant If an SE-330, SE-330AU, or SE-330HV is selected, the primary rating of the connected CT must be defined Selecting the Set-Point Assistant from the Help menu before a ground-fault-trip setting is recommended.
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Appendix B - SE-330, SE-330HV, SE-330AU Revision History SE-330, SE-330HV, SE-330AU REVISION HISTORY HARDWARE REVISION MANUAL MANUAL FIRMWARE REVISION (REVISION NUMBER RELEASE DATE REVISION ON PRODUCT LABEL) Dec 15, 2020 11-B-121520 3.10 SE-330 REVISION HISTORY (REFERENCE ONLY)
Page 75
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 SE-330HV REVISION HISTORY (REFERENCE ONLY) HARDWARE REVISION MANUAL MANUAL FIRMWARE REVISION (REVISION NUMBER RELEASE DATE REVISION ON PRODUCT LABEL) June 30, 2018 5-N-063018 2.60 October 18, 2017 5-M-101817 December 7, 2016 5-L-120716 2.55 2.54 September 21, 2016 5-K-092116 2.53...
Page 76
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 SE-330AU REVISION HISTORY (REFERENCE ONLY) HARDWARE REVISION MANUAL MANUAL FIRMWARE REVISION (REVISION NUMBER RELEASE DATE REVISION ON PRODUCT LABEL) 2.61 June 30, 2018 4-J-063018 2.60 October 18, 2017 4-I-101817 2.60 December 7, 2016 4-H-120716 2.55 2.54...
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Manual Revision History Revision 11-B-121520 Manual Updated to Include SE-330, SE-330HV, SE-330AU, and SE-MON330 Content. New Features Added for SE-330-Series Firmware V3.10. Revision 11-A-063018 General Manual Format and Many Sections Have Been Updated. Section 1 Descriptions for NGR Short Detection and Assignable Relays Added.
Page 79
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Hardware Revision Updated. Revision 10-E-010814 Section 6 Extended Operating Temperatures Added to All Sensing Resistors and SE-CS30 Current Sensors. Revision 10-D-112913 Section 6 CE Added to Sensing Resistors. Section 7 Ordering Information Updated. Revision 10-C-100813 Section 2 Section 2.8 Updated.
Page 80
Hardware Revision 10A Update to RTC Circuit. Hardware Revision 10 Updated SE-330 Platform to Include USB And MicroSD™ Interfaces, Programmable Trip Level (Mem) Feature, and ability to add future options. Real-Time Clock Added. Added Dual Cable and Fiber Ethernet Ports.
Page 81
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Firmware Revision History Firmware Revision 3.10 All Models: NGR Short Mode and NGR Open Mode Now Have Sensitive and Standard Selections. Added Additional Assignable Functions for K1, K2, And K3. Diagnostic Led Flash Mode Indicates When Unit Is Calibrated and NGR Short Mode Is Set to Sensitive.
Page 82
SE-330 Series Neutral-Grounding-Resistor Monitor Rev.11-B-121520 Firmware Revision 2.40 Added Support for Geo-Magnetic Filter. Added Support For 12 To 60 s Resistor-Fault Trip Time. Improved Log File Descriptions. IEC 61850 GOOSE Network Input Support Now Always Enabled. Improved Compatibility for Modbus TCP.