Alarms - Bell and Gossett 70E Installation, Operation & Maintenance Instructions Manual

Multiple pump & control pressure booster systems
Table of Contents

Advertisement

4.5.2

ALARMS

Overload X Failure
High Suction PSI
Low Suction PSI
High System PSI
Low System PSI
Water Level Low
Water Temp High
Pump X Off
Suction Trans Fail
System Trans Fail
Flow Trans Fail
Suction RTD1 Fail
System RTD2 Fail
Power Fail
Pump X Failure
Remote Contact Open
7 Day Timer Off
NOTES:
Bottom line only. No help message.
14
CONDITION
ALARMS
Check AMP draw, use manual reset if OK
High suction pressure – check suction
pressure and trip point
Low suction detected – check suction
pressure and trip point
High pressure detected in the system –
check trip point
Low pressure detected in the system –
check PRV and set point
Check water level in holding tank
Check water temperature
Need pump in system – if OK enable pump
Check wiring, piping, polarity, and continuity
Check wiring, piping, polarity, and continuity
Check wiring, piping, polarity, and continuity
Check wiring, continuity
Check wiring, continuity
Check cable connections and plug insertions
Check DP switch, impeller, coupler, motor
HELP MESSAGE

Advertisement

Table of Contents
loading

This manual is also suitable for:

70m

Table of Contents