Zumtobel ONLITE central EPD 2 Quick Manual page 2

Advertisement

Available languages

Available languages

ONLITE central EPD 2
Art.-Nr: 24 161 074
1. Description
Undervoltage monitor for three-phase mains (each phase towards
neutral) provided with invariable preset threshold, preset hysteresis
and integrated test button.
The device can also be used to monitor a single phase. Then,
the unused entries have to be connected to a connected phase,
otherwise the device would functionally indicate the missing
voltage.
If the consumer causes an inverse voltage that is higher then
the preset threshold, the device will not release an error signal.
When actuating the test button the output relay will drop out.
The output relay R is activated (red LED lis lighting) when the
measured voltage of all connected phases exceeds the preset
value including hysteresis. When the voltage of one of the
connected phases falls below the preset value, the output relay
will drop out again (red LED does not light).
2. Declaration of Conformity
The device was tested according to the applicable standards.
Conformity was proofed. The declaration of conformity is available
on the Zumtobel Homepage.
Notes Regarding Device Description
These instructions include indications for use and mounting of
the device. In case of questions that cannot be answered with
these instructions please consult supplier.
For the installation of the device it applies to the equipment installer
or the user to meet the national directions.
Safety Instructions
Keep the applicable directions for industrial safety and prevention
of accidents as well as the local rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation
or maintenance of the devices.
The information of these instructions have to be read and under-
stood by every person using this device.
Zumtobel Lighting GmbH | Schweizer Strasse 30 | A-6851 Dornbirn
T + 43 (0) 55 72 390-0 | F +43 (0) 55 72-22826
info@zumtobel.info | zumtobel.com
Continuation Declaration of Conformity
Warning of dangerous electrical voltage Danger
means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.
Qualified Personnel
Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their work.
This includes for example:
• Qualification to connect the device according to the local
specifications and the local regulations and a qualification to
put this device into operation, to power it down or to activate
it by respecting the internal directions.
• Knowledge of safety rules.
• Knowledge about application and use of the device within the
equipment system etc.
3. Technical Data
Input
supply voltage
3N 400/230 V, 50 Hz
tolerance
-30 % up to +10 %
nominal frequency
50 Hz
nominal consumption
16 VA (1.7 W)
recovery time
<300 ms
drop-out voltage
<85 % of the supply voltage
release delay
fixed, about 100 ms
Shunt circuit
measurement input
contacts N-L1-L2-L3
= supply voltage
overload capacity
3N~ 459/265 V
threshold
invariable, 195 V AC (UN x 0.85)
hysteresis
invariable, about 5 %
Accuracy
basic accuracy
±4 % (of full scale value)
repeat accuracy
±1 %
temperature influence
0.1 % / °C
Output
output contact
2 potential free
changeover contacts
contact material
Ag/Ni 90/10
breaking capactiy
aligned, distance <5 mm
750 VA (3 A/250 V AC)
not aligned, distance >5 mm 1250 VA (5 A/250 V AC)
fuse protection
5 A
mechanical endurance
20 x 10
switching cycles
6
electrical endurance
2 x 10
5
switching cycles
at 1000 VA ohmic load
switching frequency
max. 60/min. at 100 VA
ohmic load
max. 6/min. at 1000 VA
ohmic load
(complies to IEC 947-5-1)
isolation per IEC 60664-1
rated isolation voltage
250 V AC
rated surge voltage
4 kV
overvoltage category
III
pollution degree
2
Housing
Dimensions W x H x D
35 x 71 x 65 mm
Weight
30 g
Mounting position
any
Mounting
standard rail TH35 per IEC 60715
Mounting in series
without space
Material
Housing
Polyamide 6.6 V0
Terminal blocks
Polyamide 6.6 V0
Cover plate
Polycarbonate
Type of protection (IEC 60529)
Housing
IP40
Terminal blocks
IP20
Terminal blocks
Module connection
Input/Output
max. AWG 12 (4.0 mm²)
solid wire
max. AWG 14 (2.5 mm²)
stranded wire
Wire diameter
min. 0.3 mm up to max 2.7 mm
Temperature range
Operation
-25 °C ... +55 °C
Storage
-25 °C ... +70 °C
Display
Green LED ON
Supply Voltage is applied
Red LED ON/OFF
Status of the output relay
4. Wiring Diagram
5. Connection Diagram
L1 – L2 – L3
phase contacts
N
contact for neutral
11 – 12 – 14
21 – 22 – 24
output contacts
(2 changeover contacts)
6. Function Diagramm
hysteresies
7. Display and Operating Elements
1 green LED
operating display
2 red LED
status display of the
output relay
3 Test-Button
to check the function of the
connected safety chain. When
keeping the button pressed,
the output relay drops out
and simulates a failure.
8. Mounting
Power down the equipment
Mount the module on standard rail (TH35 per IEC 60715 in junction
boxes and/or on distribution panels).
Installation
Electric installation and device termination shall be done
by qualified persons only, by respecting all applicable
specifications and regulations.
Strip the wire by 7 mm, attach an end sleeve if necessary, insert
the wire into the contact and tighten the terminal screw with a
screwdriver.
Mat.-Nr: 00 108 541 MONTANL ONLITE central EPD 2