Guidelines when connecting the electrical wiring..................38 8.1.3 Specifications of standard wiring components....................39 To connect the electrical wiring to the indoor unit ....................... 39 9 Finishing the indoor unit installation Installer reference guide CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 3
To perform a test run using the user interface ..................... 48 12 Hand-over to the user 13 Disposal 14 Technical data 14.1 Wiring diagram................................51 14.1.1 Unified wiring diagram legend ........................51 15 Glossary CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
The original documentation is written in English. All other languages are translations. Technical engineering data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required).
Indicates a situation that could result in minor or moderate injury. NOTICE Indicates a situation that could result in equipment or property damage. INFORMATION Indicates useful tips or additional information. Symbols used on the unit: CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Improper installation or attachment of equipment or accessories could result in electrical shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by Daikin. WARNING Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the Daikin documentation).
Corrosion of copper pipes or soldered parts may cause the refrigerant to leak. ▪ In bathrooms. Instructions for equipment using R32 refrigerant WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 8
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation (for example national gas regulation) and are executed only by authorised persons. WARNING If one or more rooms are connected to the unit using a duct system, make sure: ▪...
Page 9
Then use the graph or table for… <1.8 m Floor-standing units 1.8≤x<2.2 m Wall-mounted units ≥2.2 m Ceiling-mounted units 3 Use the graph or table to determine the minimum floor area. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 10
54.6 36.6 57.5 38.5 7.956 40.1 7.956 59.9 7.956 m Total refrigerant charge in the system Minimum floor area (a) Ceiling-mounted unit (= Ceiling-mounted unit) CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant. ▪ When the refrigerant system is to be opened, refrigerant MUST be treated according to the applicable legislation. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
The selection of the brine MUST be in accordance with the applicable legislation. WARNING Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, MUST be installed in the fixed wiring. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 14
After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely. ▪ Make sure all covers are closed before starting up the unit. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 15
Running the product in reversed phase can break the compressor and other parts. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage. Electrical installation (see "8 Electrical installation" [ 37]) DANGER: RISK OF ELECTROCUTION CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 17
This could result in electrical shock or fire. WARNING Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
▪ the spare SSID sticker located on the front grille. 1× 1× 1× 1× 1× 2× 2× 2× 1× 1× 1× CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 19
Spare SSID sticker. Do NOT throw away the spare sticker. Keep it in a safe place in case it is needed in future (e.g. in case the front grille was replaced attach it to the new front grille). CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
INFORMATION ▪ Daikin Industries Czech Republic s.r.o. declares that the radio equipment type inside of this unit is in compliance with Directive 2014/53/EU. ▪ This unit is considered as combined equipment according to the definition of Directive 2014/53/EU.
▪ Wireless LAN access point. ▪ Installed free Daikin Residential Controller application. To install the Daikin Residential Controller application 1 Open: ▪ Google Play for appliances using Android. ▪ App Store for appliances using iOS. 2 Search for Daikin Residential Controller.
Wall strength. Check whether the wall or the floor is strong enough to support the weight of the unit. If there is a risk, reinforce the wall or the floor before installing the unit. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
6.2 Opening the indoor unit 6.2.1 To remove the front panel 1 Hold the front panel by the panel tabs on both sides and open it. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
3 Remove 2 screws (class 15~42) or 3 screws (class 50~71) from the front grille. 4 Push down the 3 upper hooks marked with a symbol with 3 circles. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
4 Finish the installation by securing the mounting plate on the wall using M4×25L screws (field supply). Class 15~42 Class 50~71 INFORMATION The removed pipe port cover can be kept in the mounting plate pocket. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
2 Insert a wall embedded pipe into the hole. 3 Insert a wall cover into the wall pipe. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Pipe length. Keep drain piping as short as possible. ▪ Pipe size. If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
6.4.2 To connect the piping on right side, right-back, or right-bottom INFORMATION The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
6.4.4 To check for water leaks 1 Remove the air filters. 2 Gradually pour approximately 1 l of water in the drain pan, and check for water leaks. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Connecting the refrigerant piping to the outdoor unit ▪ Insulating the refrigerant piping ▪ Keeping in mind the guidelines for: Pipe bending Flaring pipe ends Using the stop valves CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Do NOT open the refrigerant stop valve before checking the refrigerant piping. When you need to charge additional refrigerant it is recommended to open the refrigerant stop valve after charging. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Cut exactly at right angles. Remove burrs. 3 Remove the flare nut from the stop valve and put the flare nut on the pipe. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
▪ Make electrical connections to the fixed wiring. ▪ All components procured on-site and all electrical construction MUST comply with the applicable legislation. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Place the round crimp-style terminal on the wire up to the covered part and fasten the terminal with the appropriate tool. Stranded conductor wire CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
1 Set the indoor unit on the mounting plate hooks. Use the " " marks as a guide. Mounting plate (accessory) Piece of packing material CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 40
9 Pull the wires to make sure that they are securely attached, then retain the wires with the wire retainer. 10 Shape the wires so that the service cover fits securely, then close the service cover. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Mounting plate (accessory) NOTICE ▪ Do NOT bend refrigerant pipes. ▪ Do NOT push the refrigerant pipes onto the bottom frame or the front grille. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
1 Attach the front panel. Align the shafts with the slots and push them all the way in. 2 Close the front panel slowly; press at both sides and at the centre. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 44
Finishing the indoor unit installation CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Indoor unit ON/OFF switch 6 Press the indoor unit ON/OFF switch while the operation lamp is blinking. Address jumper Address Factory setting After cutting with nippers CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Page 46
7 When the setting is complete, keep pressed for at least 5 seconds. Result: The user interface will return to the previous screen. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
The correct pipe size is installed and the pipes are properly insulated. The stop valves (gas and liquid) on the outdoor unit are fully open. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Explain the user how to properly operate the system and what to do in case of problems. ▪ Show the user what to do for the maintenance of the unit. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery. CTXM15+FTXM20~42+ATXM20~35R2/5V1B + FTXM50~71R2V1B + Installer reference guide ATXM50R2V1B Daikin room air conditioner 4P518023-8G – 2020.06...
Technical data 14 Technical data ▪ A subset of the latest technical data is available on the regional Daikin website (publicly accessible). ▪ The full set of latest technical data is available on the Daikin Business Portal (authentication required). 14.1 Wiring diagram 14.1.1 Unified wiring diagram legend...
Optional equipment Equipment made or approved by Daikin that can be combined with the product according to the instructions in the accompanying documentation. Field supply Equipment NOT made by Daikin that can be combined with the product according to the instructions in the accompanying documentation.
Page 56
DAIKIN ISITMA VE SOĞUTMA SİSTEMLERİ SAN.TİC. A.Ş. Gülsuyu Mahallesi, Fevzi Çakmak Caddesi, Burçak Sokak, No:20, 34848 Maltepe İSTANBUL / TÜRKİYE Tel: 0216 453 27 00 Faks: 0216 671 06 00 Çağrı Merkezi: 444 999 0 4P518023-8G Web: www.daikin.com.tr 2020.06 Verantwortung für Energie und Umwelt...