Wanco Two-Bearing Belt-Drive Generators Introduction Read before using WARNING Improper use of equipment could cause serious injury or death. Prior to using this equipment, carefully read, understand, and observe all instructions. This is an industrial-type electric generator. This equipment is potentially hazardous and could cause physical injury or even death if improperly used.
Wanco Two-Bearing Belt-Drive Generators Principle of operation 1.2.1 AB- and AR-Series On AB- and AR-Series generators, the generator stator and the main phase output winding have an auxiliary phase winding that is connected to a capacitor. The resultant current flow creates an alternating armature reaction that can be considered the combination of two rotating fields.
Wanco Two-Bearing Belt-Drive Generators Specifications 1.3.1 AB-Series All AB-Series models Shaft O.D. 0.875 (7/8) inch Keyway 0.1875 (3/16) inch Included Pulley Single pulley, B-size belt 1.3.2 AR-Series AR100 AR250M Shaft O.D. 1.0 inch 35mm Keyway 0.25 (1/4) inch 10mm Included...
Wanco Two-Bearing Belt-Drive Generators Where to obtain service Before calling for service, please have the generator model and serial number ready. This information is displayed on the serial number tag, which is adhered to the generator. Contact our service department using the following information: Wanco Inc.
Wanco Two-Bearing Belt-Drive Generators Safety Operating safety DANGER Explosion hazard. ■ NEVER operate generator in an explosive atmosphere or near combustible materials. ■ Keep generator, engine, fuel, and other combustibles away from sparks, open flame, and burning objects. ■ Before using an engine to power the generator, read engine manufacturer’s instructions.
Page 10
Wanco Two-Bearing Belt-Drive Generators WARNING Shock hazard. ■ Use extreme caution when working on or with electrical components. ■ Avoid contact with live terminals and receptacles. ■ The generator must be properly grounded according to all applicable electrical codes. ■...
Page 11
Wanco Two-Bearing Belt-Drive Generators ■ NEVER operate this equipment under the influence of drugs or alcohol. ■ Before operating, know the location of the nearest fire extinguisher, first aid kit, and emergency telephone. ■ Keep a fire extinguisher nearby and know its proper use.
Wanco Two-Bearing Belt-Drive Generators Storage and maintenance safety ■ When not in use, store equipment in a clean, dry location, out of the reach of children. ■ ALWAYS keep the generator in proper running condition. ■ Before servicing, ensure the power unit cannot be inadvertently started during service.
Wanco Two-Bearing Belt-Drive Generators Operation Before starting 3.1.1 Safety Before operating the Wanco Generator: ■ Read and be familiar with this instruction manual. ■ Read and follow all safety instructions (see Section 2, page 5). ■ If using an engine to power the generator, read the engine manufacturer’s instructions.
Wanco Two-Bearing Belt-Drive Generators Table 3-1 Minimum horsepower requirements Generator model Minimum horsepower AB25, AB25-Hydro, 5 HP AB30-Hydro AB50 8 HP AB60 11 HP AR100 18 HP AR250M 50 HP EC-Series Approximately 2 HP per 1000 watts Operating the generator with insufficient horsepower is considered improper use of the generator and will void the warranty.
Wanco Two-Bearing Belt-Drive Generators ■ All AB- and AR-Series generators are inherently regulated. By maintaining the appropriate speed as described above, the proper voltage of 120 or 240 volts will be delivered by the generator. Lowering the generator shaft speed decreases the voltage;...
Wanco Two-Bearing Belt-Drive Generators Figure 3-1 EC-Series connections, 60 Hz Single phase, 120/240 volts Single phase, 120/240 volts Parallel zigzag Double delta 8-11 10-12 1 10 5 12 9-11 N L1 Three phase, 120/208 volts Three phase, 277/460/480 volts Parallel star...
Page 17
Wanco Two-Bearing Belt-Drive Generators Three phase, 240 volts Series delta (no neutral) CT center tap L1 = Line L2 = Line L3 = Line CT = Center tap Do not use other connection terminals. For neutral connection, you must use the...
Wanco Two-Bearing Belt-Drive Generators This is not a do-it-yourself project and should only be done by a certified electrician or electrical contractor. Remove the top cover of the control box. Before adjusting the voltage, establish the proper speed using a frequency meter: ■...
Wanco Two-Bearing Belt-Drive Generators Figure 3-2 Sample installation Engine Belt Pulleys Generator Rubber mounts Common baseplate ■ When mounting the engine and generator, remember that most engine crankshafts turn counterclockwise (when viewing the engine shaft straight on). ■ Smaller pulleys require more belt tension to deliver sufficient horsepower.
Wanco Two-Bearing Belt-Drive Generators Figure 3-3 Equation for calculating pulley size The equation for determining pulley diameter is: Engine Speed Generator Pulley Diameter ---------------------------------------- - --------------------------------------------------------------- - Generator Speed Engine Pulley Diameter The equation can be solved for any variable using simple algebra.
Wanco Two-Bearing Belt-Drive Generators Figure 3-4 Maximum pulley distance from end of crankshaft Pulley Crankshaft 2 in. Max. (50mm) Figure 3-5 Slack run side, tensioner and brake Drive pulley Brake Slack run Tension roller Flexible coupling The generator can be directly coupled to an engine by means of a flexible coupling with a spider (rubber) insert, available from industrial supply sources.
Wanco Two-Bearing Belt-Drive Generators Figure 3-6 Flexible coupling Engine Generator Coupling Coupling Rubber insert 3.1.6 Standby installations The generator does not have output capacity to power an entire home or commercial enterprise. Most utility electric service for a home is in excess of 100 amperes at 240 volts, which far exceeds the output of the generator.
Page 23
Wanco Two-Bearing Belt-Drive Generators Safety concerns WARNING Shock hazard. Failure to isolate generator from power utility can result in death or serious injury. When using the generator for backup power: ■ Never connect the generator output to any live home or commercial electric circuits.
Page 24
Wanco Two-Bearing Belt-Drive Generators Emergency circuit isolation To address the possibility of overloading the generator, the building may be wired so emergency circuits are grouped together, rewired to a separate junction box, and connected to the generator through a manual transfer switch.
Wanco Two-Bearing Belt-Drive Generators Figure 3-7 Typical standby installation Outdoors Indoors Incoming utility To home high line electric Manual circuit transfer switch Power utility electric meter Connection Connection cord set Distribution (fuse) panel Engine-generator set on common baseplate and firm, flat surface 3.1.7...
Wanco Two-Bearing Belt-Drive Generators Operating the generator CAUTION Load on generator at startup or shutdown can damage equipment. Remove all electric loads from the generator before starting or stopping the engine. Before operating the generator, follow all instructions in Section 3.1.
Wanco Two-Bearing Belt-Drive Generators Appendix A Power requirements The information provided in this appendix is for reference only. Values presented here are not necessarily representative of all such equipment. Sizing the generator In most applications, the generator will provide power to devices that use a total wattage rating up to the rated wattage output of the generator.