SAFETYLINK'S GUIDELINES

Prior to ladder assembly, refer below SafetyLink's installation guidelines and considerations based on AS1657:2018.
1. Minimum clearances from ladders to permanent
objects must be:
-200mm at the back.
-50mm at the sides.
-750mm at the front. Preferred 900mm.
-350mm either side of front centre.
3. Maximum allowable height between top
landing and roof shall not be exceed 300mm.
Additional steps will be required for heights
over 300mm.
Ref: SafetyLink Pty Ltd Permanent Ladder System
2. The distance from the bottom landing to the top of
the first rung shall not be less than 90% (270mm)
of the above rung spacings of 300mm.
4. Top rung shall be at same height as landing
Return to Table of Contents