General Notes Introduction These operating instructions describe the installation, operation and programming of EcoControl DO10. We recommend that, whilst familiarising yourself with the operation of the unit aided by this manual, you have immediate access to the operable controller in order to perform the functions and combinations as described. As certain functions are interrelated, it is advisable to follow the instructions in the given order.
General Description View of the unit Mains switch > Terminal box Internal view F1: Fuse M0.08A F2: Fuse T4A (visible type fuse 20 x 5) F3: Fuse M0.2A 2/17...
Description of the display and operating features A On/Off switch E "ENTER" key Only the surface-mounted variant is equipped with an Confirm inputs and trigger functions via the ENTER key. On/Off switch. Use this switch to switch the unit on or off. F Arrow keys B LC Display Use these keys to operate the menu drive in the display...
Draining has been activated, remaining time 145 minutes. Draining 145m Desalination Desalination has been activated, remaining time 1 minute and 28 sceonds. mm:ss 1:28 LED desalination is also lit. The * for an active dosing output can also be displayed. Error Messages In addition to the displayed error messages, the red LED “Alarm”...
Terminal Block Identification Functions (IN = input, OUT = output) Terminal Type Function Comment Mains protective earth Mains, N = Neutral Mains input Mains, L = Live 230 - 240 V AC 3x Neutral, switched Mains voltage, max. 4 A 3x Live, switched Desalination valve, c - contact Volt-free relay output...
Description of the Relay Outputs Please ensure that the outputs are volt-free. AV desalination valve Connect the desalination valve (solenoid or motor valve) to this relay output. The idle position of the relay is the same in the case of a currentless controller and in the operating position: Contact to terminals 10-11.
AL error message output ("Alarm"), continued Statuses which always trigger an error message: Voltage loss Programming-dependent error messges: Dosing medium container empty Desalination valve remains open Desalination valve remains closed See page 8 for further descriptions of error messages and programming. Description of the Signal Inputs Note Only connect the signal inputs "WM", "LL"...
LL dosing medium container empty Connect a float switch or similar device here to monitor the dosing medium container. Enter the desired effect of the contact (active as normally closed or normally open) and set the delay time used for testing º...
Programming BASIC PROGRAM º Basic program "M" Password input Enter password The programming menu is protected by a 3-digit password (number between 000 and 999) in order to prevent unauthorised programming intervention. PASSWORD INPUT º Basic program º Password input Enter the password under "M"...
Manual desalination / TEST For simulation, commissioning or testing purposes it is possible to manually open the desalination valve: Select the option “Manual desalination“ in the menu “Service” and open the desalination valve via the “ENTER” key. The display “Des. val. OPEN” is shown until you exit the manual function via the ”ENTER” or “M” key and thus close the desalination valve.
Functions FCT. EMPTY Funct. empty (LL input) The “LL" input is designed as a level transmitter input for the “EMPTY“ level of the dosing Norm.closed medium container. Program the desired effect of the contact, the delay and the alarm function. Norm.open If the input is active after the test time “Delay“, an error message occurs.
Extras LANGUAGE Language German Selection of the desired display language: English At present these four “standard” languages available. However, other languages are available if desired by customers. French Italian PASSWORD Password Changing the entered password: New: SERVICE menu Request and change current settings and statuses of the unit in the service menu. Manual desalination MAN.DESALINAT.
Operating info OPERATING INFO You can request the current counter statuses here. Desalinations Desalination Operating hours Displays the number of desalinations since the last counter reset. WM total Reset In this menu you have to reset the regeneration meter to the initial value via the “Reset WM desalination (ENTER) “key.
Diagnosis DIAGNOSIS The diagnosis menu displays the current statuses of the inputs and outputs. For test purposes (e.g. during commissioning), the output statuses can be manually manipulated via Output the ” – ” and “ • ” keys. Please ensure that downstream plant parts cannot be damaged. Active statuses (switched relay, switched input) are displayed as “on”, inactive statuses as Input “off”, e.g.:...
Menu structure ECO-Control DO10 Last update: 11.04.05 Operation Desalination 12.32m 12:03 DESAL.TIME DESALINATION mm:ss 02:30 Desal.time Start volume START VOLUME ENTER M - key BASIC PROGRAM 02000 l Password input PROGRAM VALUES DOSING Desalination Litre/Impulse LITRE/IMPULSE ENTER MENU Dosing MAN.DESALINAT. MAN.DESALINAT.
Conformity: EN 50081-1, EN 50082-2, EN 61010-1 10 - 45 / C Ambient temperature: Dimensions EcoControl DO10: W x H x D = 175 x 165 x 135 mm Weight: approx. 0.8 kg We reserve the right to make changes in the interest of constantly improving our products! Art.-Nr.:xxxxx...