NK TECHNOLOGIES AG1 Series Instructions

NK TECHNOLOGIES AG1 Series Instructions

Ground fault sensors with relay outputs, auto-reset

Advertisement

Quick Links

Specifications
Setpoint Range
AG1 Series: 5-100mA Field Adjustable
AG2 Series: 80-950mA Field Adjustable
AG3 Series:
Tri-Set, 5, 10 & 30 mA,
Jumper Select
Voltage Range
Up to 1,500 VAC (Monitored Circuit)
Frequency Range
50-400Hz (Monitored Circuit)
Output Options
(See Product Label)
Relay Output
1.0A @ 120 VAC, 2A @ 30 VDC
Solid State AC Switch
NOT COVERED
Solid State DC Switch
NOT COVERED
Response Time
150 mS @ 5% above setpoint.
100 mS @ 50% above setpoint.
Power Supply
Operates from 55-110% of nominal voltage
Nominal Voltages
120 VAC (50-400 Hz)
Green LED=Power
Optional Power
24VAC +/-15% or 24 VDC Operates +/- 20%
Power Consumption 2.5 Watts
Dimensions
2.5"H x 2.8"W x 1.5"D, (64x71x38mm),
aperture 0.75" (19mm) dia.
Case
UL 94V-O Flammability Rated
Environmental
5 to158 DegF (-15 to 70 DegC), 0-95% RH,
Non Condensing
Listings
UL 1053, Class 1 Recognized, CSA
Approved, CE Certified
Power Supply Notes
All low-current Ground-Fault Sensors are sensitive devices
that require reasonable care in system design to avoid false
trips caused by high electrical noise levels. Keep in mind that
the best way to reduce noise in a system is to suppress it at its
source.
1. Keep the sensor power isolated from noisy circuits.
2. Do not power the sensor with the same circuit that
switches contactors or other high current, inductive loads.
System Grounding
Good design practice and code require that all AC power
systems be grounded. AG Series sensors are designed to
work on grounded AC power systems. They may not operate
properly on ungrounded systems.
Model Number Key
AG 1-SDT1 -120-ENE -005
Output Type
SDT1
Setpoint Range
1 5-100mA, Adjustable
2 80-950mA, Adjustable
3 Tri-Set, 5, 10 & 30 mA, Jumper Select
AG Series Ground Fault Sensor
Know Your Power
Know Your Power
Other NK Technologies Products Include:
AC & DC Current Transducers
AC & DC Current Operated Switches
1φ & 3φPower Transducers
Current & Potential Transformers (CTs&PTs)
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Setpoint
005 to 950 Factory Adjusted
Setpoint in mA
(specify when
ordering)
TR3
Tri-Set, 5, 10 & 30
mA, Jumper Select
Options
ENE Normally Energized
DEN Normally De-energized
P o w e r S u p p l y
24U 24 VAC/DC
120 120 VAC
SPDT Relay (Form C)
1A @ 120 VAC, 2A @ 30 VDC
INSTRUCTIONS
AG1, 2 & 3 SERIES
Ground Fault Sensors
with Relay Outputs, Auto-Reset
Quick "How To" Guide
1. Run all current carrying conductors
through sensor window
A. Use an auxiliary CT if conductors do not fit. Con-
sult Factory for CT selection.
2. Mount the sensor to a surface if needed.
3. Connect output & power wiring.
A. Use up to 14 AWG copper wires.
B. Make sure power and load matches those shown on
the senors' label.
4. Test
A. Pressing the "TEST" button tests the sensors inter-
nal circuits. CAUTION: The output and any con-
nected loads will switch!

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES AG1 Series

  • Page 1 Specifications Model Number Key Setpoint Range AG1 Series: 5-100mA Field Adjustable AG 1-SDT1 -120-ENE -005 AG2 Series: 80-950mA Field Adjustable AG3 Series: Tri-Set, 5, 10 & 30 mA, Setpoint Jumper Select 005 to 950 Factory Adjusted INSTRUCTIONS Voltage Range Up to 1,500 VAC (Monitored Circuit)
  • Page 2 Description Installation & Wiring AG Series sensors work in the same environment as mo- Connect output wiring to the sensor. Be sure that the out- AG Series sensors monitor all current carrying wires in tors, contactors, heaters, pull-boxes, and other electrical en- put load is less than or equal to than the output rating on single or three phase systems to detect ground faults.

This manual is also suitable for:

Ag2 seriesAg3 series