Cautions and Hints that apply to certain specific chapters are listed at the beginning of the relevant chapters. Please read the information carefully, since it is provided for your own personal safety and it will also help prolong the service life of your product. Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 3 von 24...
Page 4
Protect the device against physical shocks and vibration during transport and storage. Also be sure to protect it against water (rainfall) and excessive temperatures. Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 4 von 24...
Page 5
All devices of the FC 200 series are manufactured according DIRECTIVE 2011/65/EU on the restriction of the use of certain hazardous substances in electrical and electronic equipment under consideration of the following harmonized standard: EN 50581:2012. Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 5 von 24...
“error” contact1 for acknowledged, but still existing faults Error “new error” contact2 for new, unacknowledged faults programmable as low-active or high-active maximum contact load: 60V/500mA (peak AC / DC) Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 6 von 24...
Temperature Warning Do not use device outside temperature range of 0°C … 40°C (32°F … 104°F) Electromagnetic Radiation Warning Do not use the device near sources of electromagnetic radiation. Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 8 von 24...
4.2 Mechanical Installation 4.2.1 Wall-Mounted Style dimensions in mm drill pattern in mm 4.2.2 Counter-Sunk Style required mounting section: 137x68 mm Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 9 von 24...
Error-Relay 1 (1) for acknowledged, but still existing faults (new) Error-Relay 2 (2) for new, unacknowledged faults programmable as NC or NO maximum contact load: 60V/500mA (peak AC / DC) Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 11 von 24...
Page 12
+10V (Power Supply for Sensor / Potentiometer) maximum load in total (with Group 2) 20mA (peak AC / DC) +24V (Power Supply Sensor) maximum load in total (with Group 2) 100mA (peak AC / DC) Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 12 von 24...
Page 13
Connect up to 100 subscriber with RS485 Interface Line 2 Connect up to 100 subscriber with RS485 Interface WARNING! Handling of unused PINs according to specification of applied EC-fan supplier! Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 13 von 24...
Potentiometer for speed setting by 0…10V Internal enable of control General connection day/night - shift – external timer Utilization error/new error by costumer FMS with external 24V (~) supply Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 14 von 24...
/ green Net B orange green white / green white / orange used Ground All other wires All other wires (view to the RJ45 plug from front to the contacts) Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 15 von 24...
Error 2 red alternating for new, unacknowledged faults Operating Levels 3 operating levels (Monitor / Operator / Administrator) Timer Programmable Scheduler for set-point shift of single fans and assigned groups Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 16 von 24...
#2 defined fan group to Controller „Group“ if needed adapt further controller settings choose Controller 1 or Controller 2 „Control Controller“ „Set Day“ Set Control value in % „Start Controller“ Start Controller with “Day-setting” Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 17 von 24...
(100 / Line) Maximum line length 400m (per Line) Baud rate according type of subscriber cable (recommended) Cat. 5 isolating voltage against 2,5 kV (overvoltage class 2) internal circuit Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 19 von 24...
All claims for damage must be reported immediately. 7.3 Service Technical queries about the FC 200 under: Nicotra Gebhardt GmbH Gebhardtstraße 19-25 Telephoneon: +49 (0)7942 / 101 - 0 74638 Waldenburg Germany E-Mail: Info.ng.de@regalbeloit.com Operating Manual “FAN Commander 200” ECE 03-0200-5E-MG Seite 20 von 24...