  • Page 1 Operating Manual Motor Controller BA-EKE 1.04 – 03/2020 EKE 10-0070-5E-IM...
  • Page 2 Make sure that the warning labels are kept in a legible condition and replace missing or damaged labels. NICOTRA Gebhardt reserves the right to change without notice. Information is also available from: Nicotra Gebhardt GmbH Gebhardstraße 19-25...
  • Page 3 Trained in rendering first aid. Use for intended purpose only The equipment may be used only for the application stated in the manual and only in conjunction with devices components recommended authorized Nicotra Gebhardt GmbH. EN - 3 of 39...
  • Page 4 European EMC Directive The EC-Controller is supplied exclusively in connection with products of the company Nicotra Gebhardt. The unit is fully integrated in the corresponding products or will be delivered together with the products. After correct installation it complies to the requirements of the EMC directive, according to the EMC product standard for electrical drives with variable speed EN 61800-3.
  • Page 5 Safety Instructions The following warnings, cautions and notes are provided for your safety and as a means of preventing damage to the product or components at the connected machines. This section lists warnings, cautions notes, which apply generally when handling the Nicotra Gebhardt EC-Controller,...
  • Page 6 Repair Warning Repairs on equipment may only be carried out by Nicotra Gebhardt. Before opening the equipment for access, disconnect the power supply and wait for at least 5 minutes until the DC-link capacitor is completely...
  • Page 7: Table Of Contents

    Table of Contents Overview ........................8 General Information ....................8 Features ........................8 Installation ........................9 Ambient Operating Conditions ................. 9 Mechanical Dimensions ..................10 Optional Fan......................11 Overview Connectors and Operating Elements ............12 Assembling ......................15 Electrical Installation ....................16 Commissioning ......................24 Reset to Factory Default ..................24 Motor Identification ....................25 Fan Selection ......................27 Analogue/Digital Inputs ..................28...
  • Page 8: Overview

    1 Overview 1.1 General Information The Nicotra Gebhardt EC-Controller EKE10-0070-5E-IM is an inverter for controlling the speed of motor-impeller-units with BLDC or induction motors (IM). Due to its sensorless field oriented control algorithm the motors are driven in any duty point at the optimum field angle.
  • Page 9: Installation

    2 Installation Warnings Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the set-up, installation, commissioning and operation of the product should carry out work on the device/system.
  • Page 10: Mechanical Dimensions

    2.2 Mechanical Dimensions Figure 1: Device dimensions Figure 2: Drill pattern Installation EN - 10 of 39...
  • Page 11: Optional Fan

    2.3 Optional Fan The EKE10 provides the possibility to mount an additional fan if the cooling may not be enough inside the application. Figure 3: EKE10 with optional fan mounted Figure 4: Required fan size Note It is recommended to use a fan with minimum 25 m /h (15 cfm).
  • Page 12: Overview Connectors And Operating Elements

    2.4 Overview Connectors and Operating Elements 2.4.1 Connectors Power Control Motor Modbus LE D Figure 5: Connector overview Installation EN - 12 of 39...
  • Page 13 2.4.2 DIP Switches The interface PCB provides DIP switches for fan selection purpose and to enable special funtions. Figure 6: Position of DIP switches Position Additinal Conditions Function DIP6 OFF Fan selection 1..5 This switch must be OFF during normal operation! •...
  • Page 14 2.4.3 Status LED To indicate the device status the EKE10 provides a dual colour LED (red and green): Status LED Function Indication State Green Ready slow flashing (1s period) Device ready (speed= 0) Device ready (speed>0) fast flashing (0,1s period) Loading of motor parameters Yellow Warning...
  • Page 15: Assembling

    2.5 Assembling Warnings Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the set-up, installation, commissioning and operation of the product should carry out work on the device/system.
  • Page 16: Electrical Installation

    2.6 Electrical Installation Warning The inverter must always be grounded. If the inverter is not grounded correctly, extremely dangerous conditions may arise within the inverter, which could be potentially fatal. Make sure that the grounding connection between PCB and basic housing part is applied correctly! To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions.
  • Page 17 2.6.1 Pin Assignment 2.6.1.1 Power Connector X1 Type Name Function Screw or cage clamp Protective earth maximum 2,5mm (13 AWG) Neutral N Phase L Table 4: Power connection with X1 2.6.1.2 Motor Connector X2 Type Name Function Screw or cage clamp Protective earth maximum 2,5mm (13 AWG)
  • Page 18 Power N L PE Motor 10 9 8 7 6 5 4 3 2 1 Control 3 2 1 Modbus Figure 7: Configuration of connectors 2.6.2 Application Examples 2.6.2.1 Connection of Power and Motor Power N L PE 1~230VAC 50/60Hz Figure 8: Mains connection Installation EN - 18 of 39...
  • Page 19 Motor Figure 9: Motor connection 2.6.2.2 Analogue Interface The analogue interface can be operated by two ways: • External voltage 0..10 Vdc • Potentiometer (using the 10Vdc source of the EKE10) Caution When using external voltage signal, the voltage must not exceed the limits given at the Technical Data page.
  • Page 20 10 9 8 7 6 5 4 3 2 1 3 2 1 24Vdc Figure 11: Speed control by external voltage signal 10 9 8 7 6 5 4 3 2 1 Enable 24Vdc Figure 12: Touch mode, all 3 inputs configured as digital input Installation EN - 20 of 39...
  • Page 21 2.6.2.3 Modbus RTU Interface 10 9 8 7 6 5 4 3 2 1 3 2 1 24Vdc Modbus Master Figure 13: Operation in Modbus mode Note Using the Modbus interface to monitor operating parameters is possible also in analogue mode. Installation EN - 21 of 39...
  • Page 22 2.6.3 Wiring Guidelines In standard case the fan will be delivered with an unshielded motor cable commonly used for power wiring of the motor close to the converter. 2.6.3.1 Installation Directly to the Fan Housing Using the original motor cable is intended for standard applications, where the location conditions allow the mechanical assembling of the controller EKE10 close or directly to the fan.
  • Page 23 2.6.3.2 Installation with Long Motor Cable Warning Risk of electrical shock! All motor wires will carry high voltages when the controller is powered. In applications where the motor cable is not long enough, the motor cable can be extended under the following conditions (see Figure ): 1.
  • Page 24: Commissioning

    3 Commissioning Warning The inverter must always be grounded. If the inverter is not grounded correctly, extremely dangerous conditions may arise within the inverter, which could be potentially fatal. Make sure that the grounding connection between PCB and basic housing part is applied correctly! To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions.
  • Page 25: Motor Identification

    3.2 Motor Identification The EKE10 is able to identify the motor parameters (stator resistance, inductance, rotor resistance) by itself during an identification run. For the preinstalled fans it is already done and the parameters are stored. A new identification should be performed when: •...
  • Page 26 3.2.2 Create and Identify 3 Party Motor Note The position 0 of the motor table is intended to be occupied with 3 party motor because this position is not used for preinstalled motors: • Permanent Magnet Synchronous Machines (PMSM) • Induction Machine (IM) After creation of new motor the EKE10 will perform motor identification automatically.
  • Page 27: Fan Selection

    Fan Selection Warning Choose the correct fan type with care, otherwise overload or damage of motor and controller can result. Number DIP1..DIP5 Fan Type Number DIP1..DIP5 Fan Type free TZP 04-0215-EC (configurable) DDMB 7/7 DDMB DDMB 9/7T free (DDMB 9/7T) DDMB 9/9 RZP 11-200-EC DDMB 9/9T...
  • Page 28: Analogue/Digital Inputs

    3.4 Analogue/Digital Inputs 3.4.1 Configuration of Inputs The three analogue/digital inputs of the EKE10-0070-5E-IM are based on the same hardware and can be configured as analogue or digital input. The following functions can be configured: • Analogue speed set point •...
  • Page 29 3.4.2 Characteristic of Analogue Inputs Analogue Motor Operation Remark Input 0-0,5 V Stop 0,5-10 V Motor runs according to the under notice of the programmed analogue signal value minimum speed 10 V Motor runs at maximum speed Table 14: Characteristic of analogue inputs n_max n_min 100%...
  • Page 30 3.4.3 Configuration of Outputs The EKE10 provides two programmable digital outputs, OUT1 and OUT2. 3.4.3.1 Programming of the Output Functions Caution The dry contacts are solid state relays (Photo-MOS) with 30Vcd maximum voltage. When using external supply, the voltage must not exceed the limits given at the Technical Data page.
  • Page 31: Change Motor Pwm Frequency

    3.4.3.2 Bit Assignment Register 40024 (Config_OUT) Config OUT2 Config OUT1 Table 16: Bit assignment Config_OUT register 40024 Default setting: OUT1: Error signal OUT2: Running signal N > Nmin 3.4.4 Important Modbus Registers for Interface Configuration Register Name Range Default Value 40007 Password 0..65535...
  • Page 32: Error Handling

    Error Handling Code Name Latch Stop Entering Condition Errors Motor error Motor parameter invalid or motor iden- tification fails Motor error Over current output module DC-link LOW error Internal power supply defective Mains brownout error Mains voltage low EEPROM error Internal memory error DC-link HIGH error Internal power supply defective...
  • Page 33: Technical Data

    4 Technical Data Electrical Characteristics Value Unit Comments Nominal operating voltage 230 (+/-10%) Input frequency 50/60 Rated input power 2000 cos =0,99 Rated input current Efficiency >94 at rated power Power factor (cos ) >0,98 at rated power Total harmonic distortion current (THDC) <8 at rated power Recommended fuse...
  • Page 34: Modbus Rtu Specification

    4.5 Modbus RTU Specification 4.5.1 Protocol Interface Modbus RTU with RS485 Supported baud rates 9600, 19200, 38400, 57600 baud Supported parities none, odd, even Data bits Stop bits Address range 1..247 (programmable via Modbus) 03 – Read output register 04 – Read input register Supported function codes 06 –...
  • Page 35 4.5.2 Register 4.5.2.1 Input Register Name Range Remark 30001 Error code / status 30002 Operation mode 0 = Modbus Default: 1 1 = Analogue 2 = Constant Airflow 3 = Process Control 30003 Fan type 0..31 Depending on switch DIP1-5 (binary coded) 30004 Current speed 0..10000 rpm...
  • Page 36 0: counter clockwise 30057 Analogue input value 2 (ADIN2) 0..1000 1000 = 10V 30058 Analogue input value 3 (ADIN3) 0..1000 1000 = 10V Table 24: Modbus input register Technical Data EN - 36 of 39...
  • Page 37 4.5.2.2 Output Register Name Range Default 40001 Set status 2 = wink 9 = store configuration register 10 = reset interface controller 11 = reset error 13 = initialise firmware update DSP 40002 Operation mode 0 = Modbus 1 = Analogue 2 = Constant Airflow 3 = Process Control 40003...
  • Page 38: Electro-Magnetic Compatibility (Emc)

    The motor controller EKE10-0070-5E-IM is supplied exclusively in connection with products of the company Nicotra Gebhardt. The unit is fully integrated in the corresponding products or will be delivered together with the products. After correct installation it complies to the requirements of the EMC directive 2004/108/EG, according to the EMC product standard for electrical drives with variable speed EN 61800-3.
  • Page 39: Notes

    6 Notes Notes EN - 39 of 39...