Setting the IP address.................... 16 7.5.1 Setting the IP address via the web server ................ 16 7.5.2 Setting the IP address via Turck Service Tool .............. 17 Programming with TX VisuPro ................... 18 7.6.1 Transferring TX VisuPro to the device .................. 18 V01.00 | 2021/01...
We make every effort to ensure that these instructions are as informative and as clear as pos- sible. If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V01.00 | 2021/01...
TXF707-… Ident No. 100017841 Year/week of production A2048 Serial number (S.N.) AA… Internal version ID of the product (V) V… Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
45472 Mülheim an der Ruhr Germany Turck supports you with your projects, from initial analysis to the commissioning of your applic- ation. The Turck product database contains software tools for programming, configuration or commissioning, data sheets and CAD files in numerous export formats. You can access the product database at the following address: www.turck.de/products...
(e. g. mounting flange TXF-MT-…). The connection level of the device must only be accessible by means of a tool. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Product Description The device is designed in protection class IP67. One Ethernet port is available for connection to Ethernet. The device is supplied via Power- over-Ethernet (PoE). An M22 connector is available for connecting the Ethernet cable. In com- bination with a special IP67 PoE cable, the protection class IP67 is ensured. The device (except for TXF705) as a built-in WLAN antenna.
Specification Format FAT, FAT32 Max. size Limited by FAT32 specifications ≤ 4 GB for a single file ≤ 32 GB Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Make sure that the seal, which is included in the mounting accessories, is correctly seated. Observe IP classification of the accessories according to the corresponding data sheet. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Grounding the device The device is grounded via a shielded CAT 5 cable. Alternatively, the device is grounded using screws on the right and left side of the M22 flange on the rear of the device. General instructions for device grounding ...
The pre-assembled IP67 cables are available in different versions at www.turck.com. The voltage source must be designed to ensure the correct operation of the device (see “Tech- nical data”). Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
The Ethernet ports of the device are set to DHCP by default. During the initial commissioning, the IP address is therefore set via the system settings on the touch screen of the device, via a DHCP server in the network or via the Turck Service Tool. Web server login ...
Set the IP address, the subnet mask, etc. under Network interface and save the changes. Fig. 8: Webserver – network interface Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
7.5.2 Setting the IP address via Turck Service Tool Connect the device to the PC via the Ethernet interface. Open Turck Service Tool. Click Search or press [F5]. Fig. 9: Turck Service Tool – home screen Turck Service Tool shows the connected devices.
Create an update package with TX VisuPro and copy it to a USB stick. Connect the USB stick to the device using a suitable Y-splitter PoE cable with USB port (TXF-M22G-RJ45-5M-USB-1M [} 11]). Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Configuring The devices have an integrated User interface and a web server for configuring the system. The user interface is based on HTML pages accessible via port 443 using a Web browser (Fire- fox V.79 Chrome V.44 or higher). Alternatively, the system settings can be called and operated via a VNC client.
Page 20
("user”). The administrator has full access to the sys- tem settings (updates of the BSP and other system components). The standard user has some restrictions. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Operating DANGER Changing components Explosion hazard – Suitability for Class 1, Division 2 possibly impaired When replacing components, make sure that the suitability of the device for Class 1, Division 2 is not affected. Only use components that are suitable for use in Class 1, Division 2. ...
If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Observe our return acceptance conditions when returning the device to Turck. 12.1 Returning devices Returns to Turck can only be accepted if the device has been equipped with a Decontamination declaration enclosed. The decontamination declaration can be downloaded from https://www.turck.de/en/retoure-service-6079.php and must be completely filled in, and affixed securely and weather-proof to the outside of the packaging.
105.1 × 148.3 × 16.5 mm 131.6 × 195.2 × 16.5 mm 183.1 × 264.5 × 16.5 mm Weight 0.5 kg 0.7 kg 1.2 kg Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 25
TXF715-P3CV01 TXF721-P3CV01 Device Ident no. 100017847 100017849 Display/touch Display TFT color TFT color Touch Capacitive Capacitive Active image area 15.6" 21.1" Resolution (pixels) 1366 × 768 1920 × 1080 Format 16:9 16:9 Brightness 400 Cd/m² typ. 400 Cd/m² typ. Dimmable Yes (up to 0 %) Yes (up to 0 %) Viewing angle horizontal...
Page 26
Port: DC mains 0 % duration: 10 ms 20 fields × 1 s Test executed on the 24 VDC of the EUT EN 61000-4-29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...
Page 27
Display durability Backlight service life Durability at 25 °C, continuous Time to darken the display to min. 40000 hours (LED type) operation 50 % of the nominal value NOTE Prolonged use at an ambient temperature of 40 °C or higher may result in a deterior- ation in the quality, reliability and durability of the backlight.
CAN/CSA C22.2 No. 61010-1, 3rd Edition and CAN/CSA C22.2 No. 61010-2-201:18 cULus (UL File No. E484803) Class I, Division 2, Groups A, B, C and D Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com...