Installation Instructions PolyPro Single-Wall Gas Vent System for Category II & IV Gas-Burning Appliances...
Page 2
A MAJOR CAUSE OF VENT RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE THAT POLYPRO® BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS. WARNING WARNING CARBON MONOXIDE POISONING Risk of carbon monoxide poisoning HAZARD.
PolyPro Single-Wall Gas Vent System For the most up-to-date installation instructions, see www.duravent.com CONTENTS LISTING............. 4 APPLICATION.
• LISTING Use soapy water to lubricate gaskets. • Listed to ULC S636 Never use Petroleum base lubricants. Rated Class IIA, IIB, and IIC vent system If these directions and those of the appliance maximum temperature 230°F (110 °C) manufacturer differ, follow the more maximum positive pressure 15 in-w.c.
WARNING IMPORTANT CARBON MONOXIDE POISONING HAZARD Failure to follow these installation To prevent possible recirculation of flue instructions could result in personal gases, the installer must consider the injury or death effects of prevailing wind conditions, eddy zones, nearby buildings, JOINT CONNECTIONS obstructions, or other obstacles such as Verify the gasket is seated evenly inside the...
APPLIANCE CONNECTION: 2" - 4" If the appliance has a PVC/CPVC female outlet use the Appliance Adapter/ PVC LOCKING BAND Adapter and Clamp. (Fig.4) • PUSH DOWN If the appliance has a PVC/CPVC MALE TO LOCK Male outlet use a matching PVC/ VERIFY GASKET IS CPVC coupling to convert to a SEATED IN FEMALE...
INSTALLATION TO APPLIANCE Pipe lengths may be cut to length (Fig.6). Use an alternate clamp (Fig.4- PPS-PAC / PPS-LBC) for the connection if a locking button (Fig.3) is removed. • Cut square (not at an angle) to the 5/8" end of the pipe. 1/4"...
FIRESTOPS (Fig. 9) Multi-Story: Consult local building or other Firestops are required at each ceiling/ applicable codes for requirements in your floor penetration including an attic. area. In the U.S., NFPA 211 10.6.3 (2013) Firestops are not required at the roof states: “Vents that pass through the floors deck penetration.
pipe is to be installed on the exhaust TERMINATION outlet. Once securely installed to exterior, verify STORM COLLAR exhaust pipe cannot be removed from termination cap. FLASHING Stainless Horizontal (Fig.16) Cut opening in the wall. Add Trim Plates and locking band (if SUPPORT CLAMP applicable) to final pipe length before installing.
max length rectangle, 4 vent runs max per Install gaskets into Co-Linear Adapter (if support. The listing requires clearance holes applicable). (Fig.13) no larger than 5 1/8" Dia, with spacing 1 3/4" Connect Co-Linear Adapter to apart. termination (if applicable). (Fig.19) 10.
HANGER MOUNTED TO TOP OF SUPPORT, M&G DURAVENT BELOW POLYPRO STORM COLLAR CHIMNEY CAP GASKET TERMINATION PLATE SEAL AS REQ'D COMBUSTION AIR INTAKE- FLEX HANGER BRACKET AND HARDWARE M&G DURAVENT POLYPRO Figure 22 FLEX CLAMP EXHAUST SYSTEM ALUM FLEX AIR INTAKE (Fig.23) AIR INTAKE Important: This section only applies to FLEX...
POLYPRO WARRANTY M&G DuraVent, Inc. (“DuraVent”) provides this warranty for PolyPro® for ten years. Subject to the limitations set forth below, DuraVent warrants that its products will be free from defects in material or manufacturing, if properly installed, maintained and used. DuraVent products are fully warranted if installed only by a professional installer.