Swann Flexcon In-Well Installation, Warnings, And Operation Instructions page 2

Advertisement

b
e f o r e
P
-
re
cHarGe adjustMent
This IN-WELL tank is shipped with a factory pre-charge as detailed below. The IN-WELL tank pre-charge must be adjusted
following the instructions in the Installation section of this manual, but must not exceed 80 psi. Any adjustments to the
factory pre-charge must be done prior to initial tank installation and with 0 psi pressure on the system. DO NOT ADJUST THE
PRE-CHARGE OF THE EXPANSION TANK WITH THE SYSTEM UNDER PRESSURE!
t
o adjust tank PrecHarGe
(Prior to Installation)
Remove the protective cap from the air valve. Check the tank pre-charge pressure using a standard tire pressure gauge.
If required add air to the tank using a manual bicycle tire pump until the proper pre-charge pressure is reached.
Replace the protective cap on the air valve.
t
o adjust tank PrecHarGe
(After Installation)
Disconnect power to the system pump. Drain the tank of
water by opening a faucet. Add or release air as required
(see above)
I
VARIABLE SPEED PUMP INSTRUCTIONS
The IN-WELL tank should be located in the pump drop pipe
5' to 20' below the pitless adaptor. This will allow the tank to be
centered in the well.
1. Determine operating pressure of water system and adjust
air pressure in the IN-WELL tank to pump manufacturer's
recommended pre-charge.
2. Pump is set in the well and wired to manufacturer's
recommendations.
3. Attach the IN-WELL tank to the drop piping.
4. Install the 5' to 20' final section of the pipe above the IN-WELL
tank and lower pipe into the well so that the IN-WELL tank is
positioned properly.
5. Install the pressure transducer either at the well or in the home
in accordance with the pump manufacturer's instructions. If there
is reference to the transducer being with-in 6' of pressure tank,
disregard. Since the IN-WELL tank is directly in line there is no
danger of water hammer.
6. Complete piping in accordance with all plumbing and electrical
codes.
7. Start system.
8. At start-up, pump may not function properly until all air is
removed from system. Cycle pump several times before any
adjustments are made. Once pump is running normally adjust to
desired pressure.
9. Attach information tag supplied to main shut off valve or
electrical wire in well.
I
n s t a l l a t I o n
Do not adjust the tank air pressure if there are
WarnInG
any visible signs of corrosion on the tank. If this
well tank shows any visible signs of corrosion or rusting, the tank must be
replaced immediately.
Failure to follow these instructions may result in
serious injury or death and or property damage.
n s t a l l a t I o n
CONSTANT PRESSURE VALVE INSTRUCTIONS
The INWELL tank with constant pressure valve should be placed
5' to 10' below the pitless adapter. The tank and valve should be
centered in the well casing. We do not recommend setting the top
of the pressure tank lower than 10' since this may result in the
constant pressure valve being lower than 20' in the well and could
cause low water pressure in the home.
1. Determine the operating pressure for the water system and set
the tank pre-charge 2 psi below the cut-in setting of the pressure
switch.
2. Pump is set in the well and wired to pump manufacturer's recom-
mendations.
3. Attach the constant pressure valve to the drop pipe string.
4. Attach a nipple between the constant pressure valve and IN-
WELL tank.
5. Attach the IN-WELL tank.
6. Install the 5' to 10' final section of the pipe above the IN-WELL
tank and lower pipe into the well so that the IN-WELL tank is posi-
tioned properly, continue with the normal installation.
7. Install the pressure switch and other fittings as required.
8. Start System: allow water to run to waste a few minutes to re-
move trapped air from water lines.
9. Close valve, if pump short cycles, increase switch setting slightly
until short cycling stops. (This may be a 2 to 5# increase in pres-
sure before the problem is corrected) there is no need to add addi-
tional air to the IN-WELL tank.
10. Attach information tag to main shut off valve.
We suggest that SQ-D model FYG2 50-70 be used when either a
50# or 60# Constant pressure valve is used. If a 30-50 or 40-60
model FYG1 is used, then the switch will have to be adjusted as
follows:
Adjust the differential setting of the switch to 26 PSI. For a 50#
valve, the setting should be 40-66. For a 60# valve, the setting
should be 45-71. (If the switch is a SQ D, tighten the short spring
three turns. This should increase the differential about 6 pounds. )
t
I
yPIcal
nstallatIons
VARIABLE
SPEED
PUMP
:
This well tank and the entire system must be checked annually by a qualified professional.
Visually examine the tank and its connection to the system piping looking for any signs of water leakage or corrosion on
the exterior of the tank or the connection.
WarnInG
If this water systems tank shows any visible signs of leaking, corrosion or rusting, the tank must be replaced immediately to avoid
personal injury or property damage. Do not adjust the tank air pressure if there are any signs of corrosion on the tank
Failure to follow these instructions may result in serious injury or death and or property damage.
(2)
CONSTANT
PRESSURE
VALVE
Pitless Adaptor
IN-WELL TANK
Installed 5-20 feet
below Pitless Adaptor
IN-WELL TANK
Variable Speed Pump
M
a I n t e n a n c e
Pitless Adaptor
IN-WELL TANK Installed
no more than 10 feet below
Pitless Adaptor
IN-WELL TANK
PIPE NIPPLE
CONSTANT PRESSURE VALVE
TO PUMP
(3)