3.3.1
Selecting the Network Address
Each TIWAY I Network Secondary must have a unique binary network address. The
range of valid addresses is 1 to 254 (0000 0001 to 1111 1110 on switches 1–8 of the
Network Address Selection dipswitch). Selecting addresses 0 or 255
(0000 0000 or 1111 1111) on the Network Address Selection dipswitch will cause the NIM
to initialize in a test mode, and the NIM will fail to operate properly. See Table 2A for
address values (bit weight) of each switch and Table 2B for addressing examples.
Table 3–2A Bit Weight
LSB
SW8
SW7
SW6
SW5
SW4
SW3
SW2
MSB
SW1
3.3.2
Selecting Network Configuration Parameters
The Network Configuration Parameters dipswitch is used to select the parameters that
define the network communication environment. Several switches on the Network
Configuration Parameters dipswitch are ignored during Local Line operation. These
switches are noted in the following descriptions.
TIWAY 1 Ti505 NIM User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table 2 Network Address Selection
Open
Closed
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
Table 3–2B Address Examples
1
25
SW8
Open
Open
SW7
Closed
Closed
SW6
Closed
Closed
SW5
Closed
Open
SW4
Closed
Open
SW3
Closed
Closed
SW2
Closed
Closed
SW1
Closed
Closed
203
Open
Open
Closed
Open
Closed
Closed
Open
Open
Installation
3-7

Advertisement

Table of Contents