CPS C3T User Manual

CPS C3T User Manual

15kv a three phase output
Table of Contents

Advertisement

Quick Links

CPS
C3T 15kVA three phase output
User Manual

Advertisement

Table of Contents
loading

Summary of Contents for CPS C3T

  • Page 1 C3T 15kVA three phase output User Manual...
  • Page 2 Pag. 52/53 MT-HC3TK15E1599NP-US 00...
  • Page 3: Table Of Contents

    4.8.5 Frequency converter (from 50 to 60Hz or vice versa) ..............26 Personalizations ......................27 4.10 Procedure to transfer the load from CPS onto maintenance by-pass......27 4.11 CPS and load shutdown ....................28 4.12 Block diagram ......................29 4.13 Components of the block diagrams ................
  • Page 4 This symbol indicates some important information which must be read with care. It is recommended to read this part of the manual. N.B. In the picture or table the word CPS means CPS. Pag. 52/53 MT-HC3TK15E1599NP-US 00...
  • Page 5 Protective equipment to be worn No maintenance operations must be carried out on the device without wearing the Personal Protective Equipment (PPE) described below. Personnel involved in the installation or maintenance of the equipment must not wear clothes with wide sleeves or laces, belts, bracelets or other items that may be dangerous, especially if they are metallic.
  • Page 6 Definition of “operator” and “specialized technician” The professional figure responsible for accessing the equipment for ordinary maintenance purposes is defined with the term operator. This definition covers personnel that know the operating and maintenance procedures for the equipment, and that have been: 1.
  • Page 7 GENERAL PRECAUTIONS This manual contains detailed instructions for the use, installation and start-up of the CPS . Read the manual carefully before installation. For information on using the CPS , the manual should be kept close at hand and consulted before carrying out any operation on the device.
  • Page 8: Storage

    STORAGE If the CPS is not to be installed immediately it must be stored within the original packaging and protected from moisture and weather. The area used to store the equipment must have the following characteristics: Temperature: -25°÷ + 60°C (-13°÷140°F)
  • Page 9: Positioning

    Positioning The air enters the CPS through ventilation grills located in the front door and exit through the fan grills located on the rear panel. The following should be taken into account when choosing a position for the CPS: ...
  • Page 10: Residual Current Detector (Rdc)

    (for example a differential breaker with an auxiliary relay is not suitable). However it is possible to install additional differential breakers on the output of the CPS, possibly coordinated with those on the input.
  • Page 11: Configuration With Single Mains Supply

    4.2.1 Configuration with single mains supply NOTE: The feed must be three-phase with neutral. The CPS cannot work without input neutral (*). F - For the installation of the protective devices on the input, refer to the “connection table”. (*)The operation without input neutral is admitted only with transformer (delta-star) on the input line .
  • Page 12: Backfeed Protection

    - EPO terminal board located on the CPS b - EPO switch (not provided). On the CPS , the jumper on the EPO terminals (page 16) must be removed, and the wires from the auxiliary contact of the button must be connected in place of the jumper.
  • Page 13: Mains, Load And Battery Connections

    THE CPSMUST NOT OPERATE WITHOUT AN EARTH CONNECTION Before making the connection, open all the switches on the device and ensure that the CPS is completely isolated from the power sources: battery and AC power line. More specifically, check that: - the CPS input line or lines are completely isolated;...
  • Page 14: External Battery Connections

    LOAD MAINS LINE External Battery connections BATTERY CABINET if present: The battery cabinet must be provided with a fuses to be connected to the CPS. max 3 battery cabinet SWBAT2 SWBAT3 Up to 3 battery cabinets can be connected in parallel, in accordance with the diagram below.
  • Page 15 CABINET DISCONNECTOR For systems with 4 or more battery cabinets, use a Battery switch cabinet where the cables can be parallel-connected (refer to the marketing department). For the sizing of the cables and connection procedures, refer to the “INSTALLATION DRAWING” attached to the battery cabinet. SWBAT1 SWBAT4 For back-up times requiring a greater number of Battery cabinets, contact the marketing department.
  • Page 16: Connection Of Signals And Remote Commands

    The CPS is factory-fitted with the EPO terminals shortcircuited. If this input is used, the CPS can be shut down in a hazardous situation from a remote position simply by pressing a button. If only the power supply is removed, for example by opening the switch of the power supply panel, the CPS will keep the load powered using the energy in the batteries.
  • Page 17: Rs232

    The position of the contacts shown is without the alarm present. The contacts can take a max. current of 1A with 250Vac. RL 1 RL 2 RL 3 IN 1 Please refer to APPENDIX A for the list of alarms and commands that can be programmed. The change of function may be made by the technical support personnel.
  • Page 18: Parallel (Optional)

    TFTP (to configure or update the device when connected to the network). The main function of this device is to integrate the CPS into the LAN network ensuring a high level of reliability of communication with the server to enable full management and control of the CPS.
  • Page 19: Remote Alarms (Optional Card)

    4.6.8 REMOTE PANEL (OPTIONAL) The remote panel allows the CPS to be monitored from a distance and the user to have a detailed overview of the state of the machine in real time. Using this device, it is possible to keep the electrical mains, output and battery measurements etc, under control and to detect any alarms.
  • Page 20: Swout And Swmb Aux - External Temperature Sensor(Optional)

    4.6.10 SWOUT and SWMB aux - External temperature sensor(optional). - 30 ÷ 80 kVA - A = connection to external output CPS switch auxiliary; B = connection to external bypass CPS switch auxiliary ; T = external temperature sensor connection.
  • Page 21 External temperature sensor (terminal T) Battery cabinet The use of the temperature sensor allows the CPS control logic to regulate the load voltage values and keep the battery working temperature constant. It is necessary to use the specific kit supplied by the manufacturer only: any uses which do not comply with the specifications may cause malfunctioning or breakage to the appliance.
  • Page 22 This page is left blank intentionally Pag. 52/53 MT-HC3TK15E1599NP-US 00...
  • Page 23: Start-Up Procedure

    After the start-up operations have been completed, perform a manual battery test: press button 3 and then 2 on the control panel. At the end of the test, after approx. 8 seconds, with the CPS started correctly and with the battery connected on the signals and control panel, the two green input and output LEDs must be on constant.
  • Page 24: Battery Operation Check

    Commands Panel should be constantly on. Check that the load connected to the CPS is powered. In this state, the power supplied to the load is the same as the energy that was previously accumulated in the batteries. Close input disconnector SWIN to return to normal operation.
  • Page 25: Operating Modes

    The various equipment operating modes are described below. setting The operating mode is set when the CPS is installed; it may be changed subsequently but this should always be done by a specialized technician. 4.8.1 On - line - factory setting - load always powered by inverter, in the event of an input mains failure the load continues to be powered from the inverter using the energy stored by the batteries.
  • Page 26: Standby-Off (With Mains Present The Load Is Not Powered)

    Standby-Off: if there is a mains power supply, CPS output is zero. The RECTIFIER remains on and keeps the battery charged. The output voltage is only present when the mains power supply fails. The system remains with output voltage = 0V while the voltage and the input frequency are within the acceptance field.
  • Page 27: Personalizations

    With several CPSs connected in parallel, follow the procedure described in the section on “bypass for maintenance” of chapter “Parallel version”. The sequences of operations to be carried out to place the CPS in maintenance bypass are shown below. The procedure varies depending on the initial state of the CPS.
  • Page 28: Cps And Load Shutdown

    After all the maintenance operations, restart the CPS following the instructions in the section on START-UP PROCEDURE (see page 23). Then open disconnector SWMB (if it was previously closed).
  • Page 29: Block Diagram

    4.12 Block diagram 4.13 MT-HC3TKE301406NP-US 00 pag 29/53...
  • Page 30: Components Of The Block Diagrams

    BATTERY This is the energy reserve to power the load when power is no longer supplied to the CPS. It is housed in one or more additional cabinets. The battery cabinet must be provided with a sectioning device and a protection device (magneto- thermal switch or disconnector with fuses).
  • Page 31 BATTERY into stabilized sinusoidal alternating voltage. The inverter output is isolated from the input and from the batteries by a galvanic isolation transformer. The inverter is always working, since the load connected to the CPS output is always powered by the INVERTER (in NORMAL OPERATION)
  • Page 32 This page is left blank intentionally. Pag. 52/53 MT-HC3TK15E1599NP-US 00...
  • Page 33: Cps In Parallel Configuration

    CPS. Each CPS has its own controller that continuously communicates with the whole system so as to guarantee the operation of the system. The cable transmits the signals from a “Master” CPS to the other “Slaves”...
  • Page 34: Electrical System Set-Up

    è definito.) remains valid with the addition of the information set out below. 5.2.1 Input The instructions seen in the first part of the manual for a single CPS remain valid; each unit must be protected with equivalent fuses or switches.
  • Page 35: External Maintenance By-Pass

    The new disconnector located on the by-pass line (Q2) must be provided with auxiliary contacts (one for each CPS). The position of the contact is opposite to the position of the switch, thus the contact must be closed when the disconnector is open.
  • Page 36: Mains, Load And Battery Connections

    An overload on the by-pass line of one CPS will lead to a deterioration of the components on that line, both internal and external to the CPS: that is, the disconnector cables and electronic power components.
  • Page 37: Power Connections Battery Side

    5.3.2 Power connections battery side. BATTERY CABINET if provided: In order for the battery cabinet to be connected to the CPS, it must be provided with a fuses device. Each CPS with its own battery cabinet max 3 battery cabinet...
  • Page 38 Several CPSconnected to the same battery TO CONNECT MORE CPS IN PARALLEL WITH ONLY ONE BATTERY: Between battery cabinets and the CPS must be positioned a Battery switches cabinet , to allow the single CPS maintenance, as shows the picture.
  • Page 39: Connection Of Signals

    The various CPSs are connected through the “signals RJ45-flat- adapter” parallel card, located in the lower part of the CPS (in the area for signal and command connections as shown in the section on SIGNALS and REMOTE COMMANDS).
  • Page 40 Using the cable with two RJ45 terminals provided with each CPS (A), make the connections as shown below: single CPS configured in parallel If it is required to use a CPS that has been configured as a parallel unit on its own, the signal card must be jumpered with the cable provided as shown below.
  • Page 41 UPS 2 UPS 2 UPS 1 To add other parallel CPSs, a “CPS PARALLEL CABLE” must be added for each new CPS connected. The signal connection must not be removed when one CPS is shut down MT-HC3TKE301406NP-US 00 pag 41/53...
  • Page 42: Start-Up Procedure

    CPS, which will send the information to the other units via the signal cable. G) Close SWMB of CPS 1 and check that the whole system switches onto the by-pass line (the bypass LED on unit1 will flash while it must be on steady on the other CPSs), then open switch SWMB again. Wait a few seconds then check that the CPS1 returns to “NORMAL OPERATION”.
  • Page 43: Operating Modes

    One battery for each CPS Each unit draws the energy from its own battery. At the end of its backup time each CPS excludes itself. The load remains unpowered if the duration of the mains outage is greater than the backup time of the whole system. When the mains is restored the system will restart automatically.
  • Page 44 3) Normal operation, Slave units with message “Parallel signal cable fault” on the panel N.B.: in this situation the load is powered correctly. All the CPS supply power to the load. Let us assume that the signal cables between CPSs 1, 3 and 2,3 are opened.
  • Page 45: By-Pass For Maintenance

    SWMB SWMB must not be closed on a CPS that is off and that is connected in parallel with other units operating normally. This operation may cause a fault on the CPSs which may create a dangerous voltage at the output.
  • Page 46 After a few seconds all the CPS will return to NORMAL OPERATION. Insertion and removal with CPSs operating (hot swap) The hot insertion and removal of the CPS can only take place if the system is configured with the RJ45 female/RJ45 female shielded adaptor cable (as shown in the figures below).
  • Page 47 Now switch on CPS 3 (the added CPS). With the lever of SW1 in the start position in one CPS only and the lever in the cont position on all the others, check that all the CPSs are operating normally and that the system is sharing the output power.
  • Page 48 This page is left blank intentionally. Pag. 52/53 MT-HC3TK15E1599NP-US 00...
  • Page 49: Maintenance

    Maintenance inside the CPS (trained personnel only) Maintenance inside the CPS may only be carried out by trained personnel. High voltage is present inside the CPS even when the power supply and the battery have been disconnected An electronic board contains lithium cell, this card and all the other card must be replace only by trained personel.
  • Page 50: Specifications

    “toxic waste”. SPECIFICATIONS SYSTEM rated power: [kVA] [kW] 13.5 leakage current max.: [mA] remote signalling: three volt free contacts (battery low, battery discharging, by-pass/fault), aux output 12Vdc 80mA standard: EPO (emergency power off), Nr.2 x RS232 interfaces Nr.1 I/0 expander card optional: parallel, 2 x netman plus or multicom cards 2 x remote alarm cards, modem, battery temperature sensor.
  • Page 51 INVERTER OUTPUT rated power p.f. 0,9 inductive: [kVA] active power pf 1: 13.5 [kW] rated voltage: 400 (380 – 415) 3 phase + N rated current (with 400V output)): phase voltage setting: 360 ÷ 420 V rated frequency: [Hz] 50 / 60 wave form: sinusoidal output voltage distortion...
  • Page 52: Appendixa - Remote Commands And Alarms Card

    Appendix A - remote commands and alarms card - Technical support personnel may give the COMMAND and the three ALARMS functions that are different to the standard configuration of the alarms card (see page 16) . The options available are listed below: ALARMS: DISTURBANCES ON BYPASS LINE MANUAL BYPASS, SWMB ON...
  • Page 53 To be used when the load may Forces the selection of the UPS support mains interference or Standby-ON operation. frequency variations and it is Standby ON This is done with the contact kept thus preferred to improve system closed; if reopened, the command is efficiency.

Table of Contents