Technical Data; General Data; Electrical Data - Grundfos 185 Installation And Operating Instructions Manual

Change-over device
Table of Contents

Advertisement

10. Technical data

WARNING
Toxic material
Death or serious personal injury
Observe the values stated in the technical data
section.

10.1 General data

10.1.1 Flow rate and medium
Medium
Flow rate
up to 200 kg/h (gas)
Chlorine
up to 600 kg/h (liquid)
10.1.2 Connections
Inlets
Groove flange DN 25, PN 40 EN1092-1
Outlets
Tongue flange DN 25, PN 40 EN1092-1
10.1.3 Pressure and temperature
Max. operating pressure
Testing pressure (factory test of the change-over
device)
Ambient temperature (operation, transport and
storage)
10.1.4 Materials
Pipe
Low-carbon steel
Valve
Steel, stainless steel, PTFE
Manometer
Low-carbon steel, silver
Gasket
IT, asbestos-free
10.1.5 Weight
Model
Weight
185-1
20 kg
185-2
30 kg

10.2 Electrical data

10.2.1 Valves and control cabinet
Control cabinet
variants
Motor valve variants
Power consumption
10.2.2 Servomotors of the motor valves
Construction
Driving torque
Actuating time
Actuating angle
Enclosure class
Insulation class
16 bar
Nominal current
20 bar
0 to +40 °C
Power consumption
10.2.3 Control cabinet
Enclosure class
Weight
Contact outputs
230 V, 50/60 Hz
115 V, 50/60 Hz
230 V, 50/60 Hz
115 V, 50/60 Hz
~100 W
Part-turn actuator
25 Nm
15 s at 50 Hz
12 s at 60 Hz
90 °
IP65
B
230 V:
0.08 A at 50 Hz
0.09 A at 60 Hz
115 V:
0.16 A at 50 Hz
0.18 A at 60 Hz
12 VA
IP54
8 kg
Potential-free contact outputs for:
Error message
Motor valve of container battery 1 open
Motor valve of container battery 2 open
Indication for manual mode
Indication for automatic mode
Max. load:
250 VAC: 7 A
220 VDC: 0.1 A
30 VDC: 7 A
15