Mineral Oils; Oil Filtering And Pollution; Not Applicable; Bolt Tightening - Nidec LEROY-SOMER LSA 52.2 MHV Installation And Maintenance Manual

Industrial range alternators - 4 pole
Table of Contents

Advertisement

Electric Power Generation

5.5.2.3 Mineral oils

Mineral oils containing special additives (diesel engine oils)
must have a Total Base Number (marked TBN or BN)
strictly below 40 mgKOH/g

5.5.2.4 Oil filtering and pollution

Following indications are related to the maximum
acceptable oil pollution level and to the oil filtering level
(filter efficiency) which has to be installed to obtain a clean
oil
Refer to Section 1 to get data about the used bearing
The viscosity change must remains within +/- 10% of a
fresh oil lubricant
Acid Number (TAN) : must not exceed 2
Acidity change must remains (TAN) +/- 0.5 mg KOH/g of a
fresh oil lubricant
Humidity ratio must remains below 0.05 %
This paragraph applies to bearings designed for high axial
thrust (tilting pads technology as used in bearings type
.....A).or oil lubricated anti friction bearing :
Maximum acceptable pollution:
following ISO 4406 : 17/15/12
following NAS 1638 classe 7
Filtering level to ensure :
β
following ISO 16889 :
10
This paragraph applies to standard bearings with low axial
thrust , self lub or oil circulation (as types E..Z.K ; E..Z.Q) :
Maximum acceptable pollution:
following ISO 4406 : 18/16/13
following NAS 1638 class 9
Filtering level to ensure (oil circulation bearing):
β
following ISO 16889 :
25
Installation and maintenance
LSA 52.2 MHV
Industrial Range Alternators - 4 pole
=
100
(filtering 10μ)
(
c
)
=
100
(filtering 25μ)
(
c
)

5.6 Not applicable

5.7 Not applicable

5.8 BOLT TIGHTENING

5.8.0 General

It is recommended to use a Liquid thread lock compound
on any fixing screws, or plugs (except for electrical contact)
which have been untighten or dismantled during any
operation.
A medium strength thread locker as or similar as "Loctite
242" ; or "Omnifit 100M" (from Henkel)

5.8.1 Steel screw in steel tapping

If no torque value is specified into the concerned chapter
the following values can be used for fixation of parts metal
onto metal
Bolt : Steel / Steel
(with medium strength thread locker)
Ø nominal
Torque
(mm)
(N.m)
3
1,0
4
2,3
5
4.6
6
7.9
8
19.2
10
37.7
12
64.9
14
103
16
160

5.8.2 Plugs

If no torque value is specified into the concerned chapter
the following values can be used for plugs tightening
Steel and copper alloy Plugs
(medium strength thread locker)
Ø nominal
Torque
(inches)
(N.m)
G3/8
30
G1/2
40
G3/4
60
G1
110
a
5654 en - 2017.10 /
Ø nominal
Torque
(mm)
(N.m)
18
222
20
313
22
430
24
540
27
798
30
1083
33
1467
36
1890
Ø nominal
Torque
(inches)
(N.m)
G1 ¼
160
G1 ½
230
G2
320
G2 ½
500
28

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LEROY-SOMER LSA 52.2 MHV and is the answer not in the manual?

Table of Contents

Save PDF