USER MANUAL
DFLEX SERIES
MUSX-EN-20-0
In compliance with the Rules and Standards of the European Union on Machine Safety,
it is essential to read this protocol carefully before installing any equipment
FISAIR S.L. C/Uranio, 20; PoI. Ind. Aimayr, 28330 San Martín de la Vega (Madrid) España.
Tel: (+34) 91 692 15 14 Fax: (+34) 91 691 64 56 | info@fisair.com| fisair.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DFLEX Series and is the answer not in the manual?

Questions and answers

Summary of Contents for fisair DFLEX Series

  • Page 1 FISAIR S.L. C/Uranio, 20; PoI. Ind. Aimayr, 28330 San Martín de la Vega (Madrid) España. Tel: (+34) 91 692 15 14 Fax: (+34) 91 691 64 56 | info@fisair.com| fisair.com...
  • Page 2 User Manual DFLEX Series | 2...
  • Page 3: Table Of Contents

    User Manual DFLEX Series | 3 Contents Introduction.................... 4 Safety Instructions .................. 6 2.1 Spanish ......................6 2.2 English ......................8 2.3 German ....................... 10 2.4 French ......................12 Transport and storage................14 Operating principle................15 Identification and coding of the model or equipment......16 5.1 Rating plates ....................
  • Page 4: Introduction

    User Manual DFLEX Series | 4 1. Introduction. To ensure the correct operation of your DFLEX dehumidifier, please read this manual carefully and keep it for future reference. If there is any part of this document that you do not understand, or if you have any questions about your dehumidifier, please contact us: FISAIR, S.L.U.
  • Page 5 FISAIR, o si los productos han sido modificados o alterados sin el consentimiento por escrito de FISAIR, o si tales productos han sido sometidos a un mal uso, mala manipulación, alteración, mantenimiento inadecuado o muestran consecuencias de accidente o utilización negligente.
  • Page 6: Safety Instructions

    User Manual DFLEX Series | 6 2. Notas de seguridad/Safety Instructions/Sicherheitshinweise/Notes de sécurité Spanish Lea con detenimiento estas notas de seguridad y examine el equipo a fin de familiarizarse con él antes de instalarlo, ponerlo en marcha o realizar operaciones de mantenimiento.
  • Page 7 User Manual DFLEX Series | 7 En general • Si nota que algo funciona mal o detecta fallos en el suministro de energía eléctrica, apague la unidad inmediatamente y tome medidas para asegurarse de que no se va a poner en marcha de nuevo. Los fallos deben ser corregidos inmediatamente.
  • Page 8: English

    User Manual DFLEX Series | 8 English Read these safety notes carefully and examine your equipment to familiarize yourself with it before installing, commissioning, or performing maintenance operations. The following symbols or messages, which may appear in this document or on your computer, warn of potential hazards, or provide information that can help you clarify or simplify a procedure.
  • Page 9 User Manual DFLEX Series | 9 General • If you notice a malfunction or detect power failure, turn the unit off immediately and ensure it cannot start up again. • Problems must be fixed immediately. • Use properly qualified personnel to carry out repair work, thus ensuring the safe operation of the unit.
  • Page 10: German

    User Manual DFLEX Series | 10 German Lesen Sie diese Sicherheitshinweise aufmerksam durch und prüfen Sie das Gerät, bevor Sie es installieren, in Betrieb nehmen oder Wartungsarbeiten durchführen. Die folgenden Symbole oder Meldungen können in diesem Dokument oder auf dem Gerät erscheinen, vor möglichen Gefahren warnen oder Informationen bereitstellen, die...
  • Page 11 User Manual DFLEX Series | 11 • einen sicheren Betrieb Geräts gewährleisten, dürfen Reparaturarbeiten nur von entsprechend qualifiziertem Personal durchgeführt werden. • Beachten Sie lokale Vorschriften, die den Einsatz dieses Luftentfeuchters regeln bzw. einschränken. Über den Betrieb des Geräts •...
  • Page 12: French

    User Manual DFLEX Series | 12 French Veuillez lire attentivement ces notes de sécurité et bien examiner l’appareil afin de vous familiariser avec lui avant son installation, sa mise en marche et les opérations de maintenance. Les symboles ou messages suivants peuvent apparaître dans le présent document ou sur la machine, pour prévenir de dangers éventuels ou apporter des informations...
  • Page 13 N’effectuez d’agrandissement n’installez d’équipement supplémentaire sur la machine sans l’accord préalable écrit de FISAIR. L’interrupteur sectionneur I1 doit être placé sur la position « 0 » et bloqué avec un cadenas pour accéder au plenum du ventilateur et/ou réaliser n’importe quelle action de maintenance sur la machine.
  • Page 14: Transport And Storage

    User Manual DFLEX Series | 14 3. Transport and storage. When in transit, the unit must be protected from impacts of any kind, and all possible measures must be taken to prevent malfunctions due to improper loading or unloading of the unit.
  • Page 15: Operating Principle

    User Manual DFLEX Series | 15 4. Operating principle. The FISAIR DFLEX series air dehumidifiers operate using a substance (silica gel) which adsorbs moisture from the air and is configured as a cylinder with many small channels of this material all running in the same direction as the air flow.
  • Page 16: Identification And Coding Of The Model Or Equipment

    CODING Rev01 28-02-19 PRODUCT DFRA / DFLEX DFRA-0900 E GF GF WS WS WS WS AE04 SERIES DFRA- DFLEX 0100 1100 0130 1300 0160 1700 0175 2100 0200 2900 0230 3500 0300 0400 0500 0650 MODEL 0900 REACTIVATION SYSTEM Electric coil Coil for hot water Hot Water coil + electric coil Coil for saturated steam...
  • Page 17 CODING PRODUCT DFRA / DFLEX POWER SUPPLY OPTIONS (NOT INCLUDED IN MECHANICAL DRAWINGS) Standard electrical power supply at 400V ±5% /III/50Hz Electrical power supply at 400V ±5% /III/50Hz Electrical power supply at 400V ±5% /III/60Hz Electrical power supply at 400V±5%/III+N/60Hz Electrical power supply at 440V ±5% /III/50Hz Electrical power supply at 440V±5%/III+N/50Hz Electrical power supply at 440V ±5% /III/60Hz...
  • Page 18: Rating Plates

    - Dry air fan motor, maximum power and current. - Reactivation fan motor, maximum power and current. - Place and date of manufacture. - Machine type. - According to which directive is designed. - To which FISAIR machines can be join (if applicable).
  • Page 19 - Nominal power for the equipment - Nominal current for the equipment. - Electrical wiring number - Name of the PLR configuration program (Programmable Logic Relay) - Place and date of manufacture Figure 2: Example of a DFLEX series ratings plate...
  • Page 20 User Manual DFLEX Series | 20 Figure 3: DFLEX series machine ratings plate location on control panel (visible from the outside) Figure 4: DFLEX series electric panel ratings plate location (on control panel after opening, on the reverse side)
  • Page 21: Main Components

    User Manual DFLEX Series | 21 6. Main components. Figure 5: Exploded diagram of DFLEX series main components Process air filtration module. Base unit. Dry air fan module. Basic support unit for desiccant rotor and for internal drying and regeneration air circuit cavities.
  • Page 22: Operating Parameters

    User Manual DFLEX Series | 22 7. Operating Parameters. The unit's performance features will be affected by the working conditions. If your unit needs to be operated under other working conditions, please contact us. FISAIR Dehumidifier Series Parameters DFLEX Dry Bulb temperature range of the 2°C to 55°C...
  • Page 23: Components Technical Data

    Rotor Desiccant Rotor (Silica Gel) chemical resistance Attention: The following chemicals will damage the DESICCANT ROTOR (SILICA GEL) or reduce its dehumidifying capacity. Note: Using the below chemicals with FISAIR DFLEX air dehumidifiers may invalidate the guarantee. INORGANIC COMPONENTS COMPONENTS...
  • Page 24: Installation

    User Manual DFLEX Series | 24 9. Installation. Location Before starting to install the unit, the following points need to be considered: • Check the degree of protection (IP rating) as shown in the dehumidifier manual (IP50 run for indoor installation, IP54 run for outdoor installation).
  • Page 25 User Manual DFLEX Series | 25 DFLEX-E and DFLEX-V service area dimensions: DFLEX-G service area dimensions:...
  • Page 26: Air Ducts

    User Manual DFLEX Series | 26 Air ducts IN VERTICAL DUCT RUN: IN HORIZONTAL DUCT RUN: INSULATED INSTALL A DRAIN (HOLE) SLOPE DOWN AWAY FROM THE DUCT AVOIDS AT THE LOWEST POINT TO OUTLET TO REMOVE THE CONDENSATION REMOVE CONDENSATION...
  • Page 27: Connecting Thermal Fluids: Steam Reactivation Battery

    User Manual DFLEX Series | 27 Connecting thermal fluids: steam reactivation battery For models with a reactivation battery for steam, thermal oil, superheated water or gas, the thermal fluid supply must be connected according to the regulations applicable in each case and according to good practice.
  • Page 28 User Manual DFLEX Series | 28 Power [kW] at Absolute Pressure Steam mass rate [kg/h] at Absolute of... Pressure of… AIR Q Model [Nm3/h] 3 bar 4 bar 5 bar 6 bar 3 bar 4 bar 5 bar 6 bar...
  • Page 29: Connecting The Gas Supply To The Gas Reactivation Heater

    User Manual DFLEX Series | 29 Connecting the gas supply to the gas reactivation heater Models with a gas reactivation heater must be connected to the gas supply according to the regulations applicable in each case and according to good practice.
  • Page 30 User Manual DFLEX Series | 30 Nominal values according to model: MODEL 1100 1300 1700 2100 2900 3500 Atm pressure 1013,25mbar 1013,25mbar 1013,25mbar 1013,25mbar 1013,25mbar 1013,25mbar q(v) air ±5% 2250Nm³/h 2700Nm³/h 3600Nm³/h 4500Nm³/h 6000Nm³/h 7200Nm³/h Feed pressure 40-60mbar 40-60mbar 40-60mbar...
  • Page 31: Connecting Thermal Fluids: Additional Batteries

    For heating batteries, the nominal values are calculated with a standard temperature drop in water of 20°C, entering at 70°C and exiting at 50°C. For calculating non-standard performance, please contact your FISAIR dealer. NB. Ensure that the air to be treated does not contain aggressive components that may...
  • Page 32 User Manual DFLEX Series | 32 Simple connection diagrams recommended for pre-cooling and post-cooling/heating batteries. Typical installation for constant flow: Typical installation for constant flow with water + glycol for risk of condensed water freezing on the surface of the heat exchanger:...
  • Page 33 User Manual DFLEX Series | 33 BF1: Pre-heating battery BR: Reactivation battery B2: Post-heating/cooling batteries. ST: Temperature probe C: Temperature controller. Sends a signal to the motor if adjustment is required. MV: Motor-valve operated by controller.
  • Page 34: Connection To The Mains Power Supply

    The line connection must be made at the power terminals of terminal block X1 (PE-L1- L2-L3) or directly on the terminals of the circuit breaker (depending on the model). Figure 11: Terminal block X1 for DFLEX series without PLR.
  • Page 35: Control And Signalling Connections

    Figure 12: Terminal block X1 for DFLEX series with PLR. Control and signalling connections All equipment with a Fisair electric control panel has the remote signalling card SEF-013, which provides remote information about the equipment status. The SEF-013 consists of 3 relays (NC-NA) identified on the terminal block as Rx1, Rx2 and Rx3.
  • Page 36 Terminals 22-23 Terminals 24-27 Terminals 24-25 Terminals 24-28 Terminals 24-29 If the equipment has PLR, please refer to the MMCSX (DFLEX Series Operating and Control Manual) for more information, as the operations of the different interlocks depend on the selected configuration.
  • Page 37: Flow Adjustment

    User Manual DFLEX Series | 37 Flow adjustment Steps for adjusting the process air flow (if the differential pressure sensor is not available): 1) Measure the differential pressure with a pressure gauge on the differential pressure ports located on the side of the basic unit (module 4).
  • Page 38: Differential Pressure Sensor

    User Manual DFLEX Series | 38 IMPORTANT: The reactivation fan has been designed to overcome a certain pressure or load loss. If this pressure or load loss is low, the closing of the reactivation damper for adjusting the nominal flow rate could produce areas of excessive heating in the elements of the heater.
  • Page 39 User Manual DFLEX Series | 39 The corresponding connections for measuring flow volume or drive pressure are shown next to the switch position: Flow rate Drive pressure STOP START P2=Patm Figure 7: Connections of the tubes to the sensor Calculation of the flow through the differential pressure of suction of the fan...
  • Page 40: Frequency Inverter Parameters

    [25-48] Standard Fan [25-48] DFLEX-2900 Powered Plug Fan [25-50] Standard Fan [25-50] DFLEX-3500 Powered Plug Fan [25-43] For the advanced configuration (PLR), please refer to the MMCSX (DFLEX Series Operating and Control Manual) since more parameters are to be changed.
  • Page 41: Commissioning

    User Manual DFLEX Series | 41 10. Commissioning. Once the equipment has been connected to the air ducts and mains power supply, as well as the thermal fluids and/or control elements, where appropriate, the equipment commissioning process should be done as follows: Firstly, identify the PLR (Programmable Logic Relay) on the control panel and/or wiring diagram.
  • Page 42 User Manual DFLEX Series | 42 If the equipment has PLR, please refer to the MMCSX (DFLEX Series Operating and Control Manual) to start the equipment. Otherwise, follow the instructions below: 1) Set switch I1. 2) Move the I2 switch to the selected position (manual or automatic) to start the dehumidifier.
  • Page 43 User Manual DFLEX Series | 43 To operate the PLR, refer to the MMCSX (Operation and Control Manual Series DFLEX) to start the equipment. 4) If it is the first time the equipment has been used: Check that the flow control dampers are at least 50% open.
  • Page 44: Maintenance

    User Manual DFLEX Series | 44 11. Maintenance The following service table is for guidance only, as the frequency will depend on the conditions of each installation. ACTION FREQUENCY Cleaning the filters According dehumidifier's instructions. Inspection of the wet air fan impeller(reactivation)
  • Page 45: Maintaining The Dessicant Rotor

    User Manual DFLEX Series | 45 11.1 Maintaining the dessicant rotor The desiccant rotor is the only component of the dehumidifier that needs special attention. The desiccant rotor fitted to these units does not require specific ongoing maintenance. The speed of rotation is very slow, and the bearings and desiccant material are designed for continuous operation.
  • Page 46: Maintenance Of Air Filters

    1) Turn off the dehumidifier and wait for it to cool down. 2) Extract the filters from the unit. 3) Wash the filters using neutral pH soap and water or replace them. 4) Only replace the filters when they are completely dry. Always use FISAIR filters or filters with equivalent properties.
  • Page 47: Declaration Of Conformity

    User Manual DFLEX Series | 47 12. Declaration of conformity...
  • Page 48: Guarantee

    User Manual DFLEX Series | 48 13. Guarantee...