Cooper Crouse-Hinds FSQ Series Installation & Maintenance Information

Cooper Crouse-Hinds FSQ Series Installation & Maintenance Information

Receptacle switch replacement

Advertisement

Available languages

Available languages

FSQ SERIES RECEPTACLE

SWITCH REPLACEMENT

Installation & Maintenance Information
Power to receptacle MUST be OFF.
Switch lever on receptacle MUST be in OFF position.

SWITCH COVER REMOVAL

Loosen cover set screw (turn in clockwise direction). Remove and set
cover aside so threads will not be damaged.

SWITCH OPERATING FORK REMOVAL

(FSQ3430 Series uses only one screw and lock washer).
Turn cover set screw in counterclockwise direction until receptacle
insulating body can be rotated.
Fully insert plug into receptacle and turn it clockwise until switch fork
is about in middle of opening.
Remove screw(s) plus lock washer(s) from fork and set screw(s) and
lock washer(s) aside for use later.
Remove operating fork.
Model M4 or M5
Attach wires to switch exactly the same as they were to old switch.
Install switch using screws and lock washers that were set aside.
Switch lever MUST be in OFF position and MUST be to left as
shown in sketch.
Check OFF position by inspection for open contacts on switch.
Replace switch operating fork using screw(s) and lock washer(s)
that were set aside.
NOTE: Start screws, then turn body using plug to put lever over
switch before securely tightening screw(s).
Check position of switch by turning plug to ON and back to OFF.
All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or
completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our
control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE
WARNING
25757A or 25744A
Switch (Shown in
OFF position)
Cooper Crouse-Hinds, LLC
PO Box 4999, Syracuse, New York 13221 • U.S.A.
Copyright© 2004, Cooper Industries, Inc.

SWITCH REMOVAL

Remove screws plus lockwashers from switch, setting them aside
for later use.
Make note of exact wiring pattern used for switch connections.
Disconnect all wires from switch and discard switch.
SWITCH REPLACEMENT
For FSQ models M2 and M3 use only:
Switch #D-118 (3 wire, 4 pole), or Switch #D-119 (2 wire, 3 pole)
See sketch below.
For FSQ models M4 and M5 use only:
Switch #25757A (3 wire, 4 pole), or Switch #25744A (2 wire, 3 pole)
See sketch below.
DO NOT INTERCHANGE SWITCHES.
Model M2 or M3
D-119 or D-118
Switch (Shown in
OFF position)

SWITCH COVER REPLACEMENT

With switch in OFF position turn cover set screw clockwise until
screw is below housing surface.
Tighten cover into body as far as possible.
Loosen enough so hole in cover lines up with set screw.
Turn set screw counterclockwise as far as possible, witch locks
cover in place.
Plug will now operate receptacle normally.
TURN POWER TO RECEPTACLE ON.
IF 748
WARNING:
Revised 09/04
Supercedes 03/80
IF 748
Revision 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FSQ Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Cooper Crouse-Hinds FSQ Series

  • Page 1 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.
  • Page 2 Crouse-Hinds et étant donné que les conditions d'utilisation échappent à notre contrôle, l'acheteur doit décider lui-même si le produit est approprié à l'usage qu'il entend en faire et assumer tous les risques et toutes les responsabilités de quelque nature que ce soit qui s'y rattachent. IF 748 Cooper Crouse-Hinds, LLC Révision 1 PO Box 4999, Syracuse, New York 13221 • États-Unis Révisé...
  • Page 3 All statements, technical information and recommendations contained herein are based on information and tests we believe to be reliable. The accuracy or completeness thereof are not guaranteed. In accordance with Cooper Crouse-Hinds "Terms and Conditions of Sale", and since conditions of use are outside our control, the purchaser should determine the suitability of the product for his intended use and assumes all risk and liability whatsoever in connection therewith.

Table of Contents