Panduit NET-ACCESS S-Type Installation Instructions Manual
Panduit NET-ACCESS S-Type Installation Instructions Manual

Panduit NET-ACCESS S-Type Installation Instructions Manual

Server cabinets

Advertisement

Quick Links

STOP
READ ALL OF THE FOLLOWING INSTRUCTIONS BEFORE
REMOVING
CM599L
CABINET
N
-A
S-Type Server Cabinets
ET
CCESS
TOOL LIST
-Phillips screwdriver
-Flatblade screwdriver
-22mm socket wrench
-15mm socket wrench
-13mm socket wrench
-8mm socket wrench
-48" level
FROM SKID
-7mm socket wrench
-T30 Torx bit
-T25 Torx bit
-6mm Allen key
-2.5mm Allen key
-Wire cutter

Advertisement

Table of Contents
loading

Summary of Contents for Panduit NET-ACCESS S-Type

  • Page 1 CM599L STOP READ ALL OF THE FOLLOWING INSTRUCTIONS BEFORE CABINET REMOVING FROM SKID S-Type Server Cabinets CCESS TOOL LIST -Phillips screwdriver -7mm socket wrench -T30 Torx bit -Flatblade screwdriver -22mm socket wrench -T25 Torx bit -15mm socket wrench -6mm Allen key -13mm socket wrench -2.5mm Allen key -8mm socket wrench...
  • Page 2 The recommended practices are based on average conditions. Panduit makes no representation or warranty, express or implied, nor assumes any responsibility for the accuracy or completeness of these installation instructions. Panduit does not guarantee any favorable results nor assume any liability for damages, improper installation, system failures, or any other problems that could arise in connection with the use of these installation instructions.
  • Page 3 © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L IMPORTANT SAFETY INFORMATION WARNING CABINET TIPPING HAZARD This cabinet can easily be tipped. Use extreme caution when unpacking or moving the cabinet. Use at least [2] persons to remove cabinet from pallet and move cabinet into position (refer to page 5).
  • Page 4: Table Of Contents

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L TABLE OF CONTENTS-NET ACCESS S-TYPE SERVER CABINETS General Cabinet Operation Packaging Material Removal ......................5 Leveling............................6 Floor Mounting ..........................7 Ganging (front of cabinet)......................8 Ganging (rear of cabinet) ....................... 9 Grounding ............................ 10 Equipment Rail Adjustment......................
  • Page 5: Packaging Material Removal

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Packaging Material Removal “Shipping Hold Down Bracket” Doubles as Floor Mounting Bracket. Retain bracket if floor mounting is desired. (see Page 7) • Remove all stretchwrap and protective cardboard from outside of cabinet •...
  • Page 6: Leveling

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Leveling • Ensure that [4] Leveling Legs are fully retracted • Slide Cabinet into final position • Lower the [4] Leveling Legs until the cabinet weight is fully supported by only the leveling legs •...
  • Page 7: Floor Mounting

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L WARNING CABINET TIPPING HAZARD Mount cabinet to floor before equipment is installed in cabinet. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT. Floor Mounting •...
  • Page 8: Ganging (Front Of Cabinet)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L WARNING CABINET TIPPING HAZARD Ganging of cabinets only provides limited stability to the cabinets, and is not a substitute for proper leveling or floor mounting of cabinets. Ensure that cabinets are properly mounted to floor before equipment is installed in cabinet. (See page 7) FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
  • Page 9: Ganging (Rear Of Cabinet)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L WARNING CABINET TIPPING HAZARD Ganging of cabinets only provides limited stability to the cabinets, and is not a substitute for proper leveling or floor mounting of cabinets. Ensure that cabinets are properly mounted to floor before equipment is installed in cabinet. (See page 7) FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
  • Page 10: Grounding

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L DANGER ELECTRICAL SHOCK HAZARD Each cabinet must be connected to the Common Bonding Network (CBN). FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT. Grounding •...
  • Page 11: Equipment Rail Adjustment

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L WARNING FALLING EQUIPMENT HAZARD Remove all equipment installed onto equipment rails before performing any adjustments to equipment rail spacing. FAILURE TO FOLLOW THESE INSTRUCTIONS CAN LEAD TO SERIOUS INJURY, DEATH, OR DAMAGE TO YOUR EQUIPMENT.
  • Page 12: Equipment Rails (Zero Ru Quicknet™ Patching Adapter Installation)

    Equipment Rails (Zero RU QuickNet™ Patching Adapter Installation) • Insert plastic Patching Adapters by snapping adapter into rear-facing surface of rear equipment rails. • Patching Adapters accommodate Panduit QuickNet™ Copper and Fiber Cabling Systems (optional) • Included on select 600mm wide S-Type cabinet configurations Insert Patching Adapters (snap into equipment rails) For Technical Support: www.panduit.com/resources/install_maintain.asp...
  • Page 13: Overhead Cable Openings

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Overhead Cable Openings • Remove Bezel Insert to allow for overhead cable entry • Cut [8] tabs with wire cutter to open large cable openings - OPTIONAL • Install M10 threaded rod into [6] tapped holes for 1070mm deep cabinets or [9] tapped holes for 1200mm deep cabinets, if desired •...
  • Page 14: Cable Management Fingers (Sn15F, Sn25F)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Cable Management Fingers (SN15F, SN25F) • Insert tabs of Cable Management Finger into mounting slots of cabinet post • Slide Cable Management Finger inward to lock into place Cable Managment Finger -Insert tabs into cabinet post -Slide inward to lock in place For Technical Support: www.panduit.com/resources/install_maintain.asp...
  • Page 15: Ccl3 - Combination Lock Swing Handle Installation

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L CCL3 - Combination Lock Swing Handle Installation Combination Lock Swing Handle Operation • Default combination: “0,0,0” • Set [3] dials to correct combination, or use key to open handle SET NEW COMBINATION •...
  • Page 16: Single Hinge Door (Removal And Installation)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Single Hinge Door (Removal and Installation) • VIEW 1 Pull down Compression Sleeve at top door hinge • VIEW 1 Pull Single Hinge Door away from cabinet so that Top Hinge Screw fits through cutout of door •...
  • Page 17: Single Hinge Door (Door Handle Direction Reversal)

    Loosen Cam Screw to reposition Door Cam and Cam Stop to outside of door. Tighten Cam Screw • With Door Handle repositioned, secure Door Handle Backing Plate to Door Handle • Remove PANDUIT label and re-attach in correct orientation near top of door • Reinstall Single Hinge Door per instructions on Page 15 VIEW 3...
  • Page 18: Rear Split Doors (Removal And Installation)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Rear Split Doors (Removal and Installation) • Open Rear Split Doors to approximately 90º • Lift Rear Split Doors up pull doors away from cabinet frame • REVERSE STEPS to install Rear Split Doors For Technical Support: www.panduit.com/resources/install_maintain.asp...
  • Page 19: Side Panel - (Distinguishing Features -- Also Reference Instructions V00029Cm)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Side Panel - (Distinguishing Features -- also reference instructions V00029CM) Original Cabinet Current Cabinet MUST USE THESE S21SPS, S22SPS, S51SPS, S52SPS MUST USE THESE S21SPSE, S22SPSE, S51SPSE, S52SPSE PART NUMBERS: PART NUMBERS: S81SPS, S82SPS, S11SPS, S12SPS...
  • Page 20: Hinged Side Panels (Removal/Installation And Adjustment - Optional)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Hinged Side Panels (Removal/Installation and Adjustment - optional) • Pull [2] Spring Loaded Hinge Pins to release Rear Side Panel from cabinet frame • Pull [4] Spring Loaded Hinge Pins to release Front Side Panel from cabinet frame •...
  • Page 21: Pdu Bracket Adjustment

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L PDU Bracket Adjustment • PDU brackets are height-adjustable if PDU spacing other than the factory position is desired. • Remove [2] M5 Torx Screws per bracket, as shown below • Reposition brackets at desired distance, ensuring that mounting flange of PDU bracket rests on the outside of cabinet post.
  • Page 22: Cable Management/Pdu Bracket Adjustment (Optional)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Cable Management/PDU Bracket Adjustment (optional) • Cable Management/PDU brackets are height-adjustable if PDU spacing other than the factory position is desired. • Remove [4 -or- 6] M5 Torx Screws from bracket, as shown below •...
  • Page 23: Cabinet Sealing

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Cabinet Sealing Install [6] Latch Plugs [3 upper, and 3 lower] into the door latch cut-outs to the front side of the cabinet only. Install [2] foam seals to the upper and lower frame. Seal should be pressed up against the Equipment Rails, behind the latch plugs.
  • Page 24: Front And Rear Floor Seal Installation (Vertical Exhaust Duct Only)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Front and Rear Floor Seal Installation (Vertical Exhaust Duct ONLY) • Install Floor Seal to front or rear of cabinet frame using (2) M10x20mm Bolts. (Flange on floor seal will face outward away from the cabinet.)
  • Page 25: Top Of Cabinet Cable Manager Installation

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Top of Cabinet Cable Manager Installation • Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit). • Remove (2) M5x0.8 button head screws (use T25 Torx bit) from front and rear of Cable Manager base.
  • Page 26: Top Of Cabinet Cable Manager Installation (For Vertical Exhaust Ducts)

    © Panduit Corp. 2016 INSTALLATION INSTRUCTIONS CM599L Top of Cabinet Cable Manager Installation (for vertical exhaust ducts) IMPORTANT - INSTALL VERTICAL EXHAUST DUCT PRIOR TO INSTALLING REAR VERTICAL WALL • Disassemble front fascia assemblies (packaged in cabinet) by removing (2) M5x0.8 button head screws (use T25 Torx bit).
  • Page 27 INSTALLATION INSTRUCTIONS CM599L © Panduit Corp. 2016 THIS PAGE IS INTENTIONALLY BLANK For Instructions in Local Languages E-mail: and Technical Support: techsupport@panduit.com Phone: www.panduit.com/resources/install_maintain.asp 866-405-6654 www.panduit.com Page 27 of 27...