Operating and installation Manual Smoke Detector Type RM-O-3-D For controlling fire and smoke protection dampers General building inspectorate approval Z-78.6-125 Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
Explanation of the symbols of This operating manual describes the smoke this manual extraction device in the variants: • RM-O-3-D for 24 V DC Supply Voltage Danger! • RM-O-3-D for 230 V AC Supply Voltage Marking a risk to life and limb by electrical In order to ensure the complete function of the voltage.
Safety and Intended Use General safety information Intended Use The smoke detector RM-O-3-D is used to control Only qualified personnel may carry out the work described on the smoke extraction device. Only and trigger fire or smoke dampers to prevent the...
② early stage. ③ ④ The smoke detector RM-O-3-D is used to control and trigger fire and smoke dampers. It works ⑤ according to the scattered-light principle and detects the smoke independently of temperature, so that fire dampers close even before the triggering temperature has been reached.
> 90% – Alarm LED off 2) The alarm position triggered by smoke (event or maintenance) can only be canceled by pressing the LED blinking push button after the smoke detector is smoke free again. Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
• Smoke detector is Packaging missing Dispose of packaging material properly • Data not transmitting after unpacking. Alarm relay 250 V 2 A contact (trip, 24 V DC 100 W contamination) Mass 0,7 kg Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
When using the FK-EU as overflow flap, in accordance with the building inspectorate approval Z-6.50-2031: install the smoke detector RM-O-3-D in the upper inspection opening of the fire damper. Assembly sequence:: 1. Place adapter ③ on inspection cover ② and...
5. Connect the fire damper electrically to the smoke detector, see "Electrical installation" on page 10. Dimensions Auslösung / relase Verschmutzung / pollution Betrieb / operation Test / Reset Typ RM-O-3-D Rauchauslöseeinrichtung ~ 95 ~ 40 Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
In the range of the permissible switching capacity (see page 7), the fan can also be switched off via the smoke release device. For higher switching power, auxiliary relays must be used. Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
OPEN position. Note Fire dampers with magnetic release devices can only be opened manually on site. All operating, warning and alarm functions are described on page 4. Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)
For repair only original spare parts may be used. After a repair, a functional test must be carried out, see "Function test / commissioning" on page 11.. ① ② ③ Operating Instructions RM-O-3-D / Publication no. M375DD8 (08/2015)