RDT FloodMaster RS-094-MK6 Manual page 4

Plenum-rated water heater / tank leak detection & automatic shut-off system

Advertisement

TRANSFORMER MOUNTING INSTRUCTIONS
The kit contains a cover plate for a standard junction box. The cover has a hole or knock out in the center. It
is designed such that the transformer can be mounted to it and then screwed into the junction box.
1. To mount the transformer to the cover, carefully route its primary wires through the hole in the cover.
2. Tilt the cover so that the head of the retaining screw on the transformer is over the cover.
3. Back the screw out until the cover slips under the threaded end of the retaining screw.
4. Tighten the screw until the transformer is secured on the cover. The threaded end of the screw is designed
to press against the cover to hold the transformer in place.
OUTPUT SIGNAL CONNECTIONS
The unit also provides output signal capabilities (SPDT Relay Output Contact) for connection to a home
security panel or for use with an appropriate relay to control a secondary device, such as a pump. See
Figure 1 for wiring diagram.
Normally Closed Circuit – Terminal Pins 3 & 4
OPERATION & SYSTEM RESET
In the event the system activates, locate the source of the leak, remove the sensor from the water and
dry the metal contacts on the bottom. Correct the problem causing the leak and replace the sensor in the
desired leak detection location once again as required. Press and release the "Reset" button on the receiver
to open the valve and begin the flow of water again. The green "Power" indicator light on the receiver will
flash once to confirm the reset.
MAINTENANCE
Test the system annually per the function test (install step 7) to ensure correct operation and maintain product
warranty status. At a minimum, exercise (press and release) the "Reset" button on the receiver annually.
EMERGENCY MANUAL VALVE OPERATION
The unit is equipped with an emergency feature for the manual rotation of the valve. Disengage the actuator
from the valve and manually changing the valve to open or closed as follows:
1. Turn off the main power to the transformer.
2. Stabilize the water feed line by grabbing it in one hand near the valve. While grasping the actuator
housing in the other hand, pull the actuator housing away from the water feed line.
3. Using an appropriate hand tool (such as a pliers), clamp down on valve stem and turn in the appropriate
direction until the desired position is achieved. Note the top of the stem is slotted to indicate valve position
(in line with water flow would indicate open valve; slot across water line would indicate closed valve).
4. Before remounting the actuator, return the valve to the original position prior to the manual rotation.
5. Remount the actuator and restore the main power to the transformer.
6. Test for correct operation per the function test listed in install step 7.
NEED INSTALLATION OR SETUP ASSISTANCE?
Call toll-free: 888-771-4929 or visit www.RelianceDetection.com/support/RS-094
© Copyright 2020 Reliance Detection Technologies, LLC – A Madison Company
203-488-2684 or 888-771-4929
27 Business Park Drive, Branford, CT 06405
www.RelianceDetection.com
All specifications subject to change without notice.
ECN # 11386, 07/2020, MF108, RevB
Normally Open Circuit – Terminal Pins 4 & 5
info@RelianceDetection.com

Advertisement

loading