TECNOELETTRA s.r.l. via D.Vioni n.5 – 42016 S. Rocco - Guastalla (RE) Tel.+39.0522.832004 Fax.+39.0522.832012
AT206 / AT206B "Quick installation guide"
General information
WARNING! Check that the product delivered exactly corresponds to the ordered
one.
Installation
Drilling template
(use the two screw anchor provided )
245mm
Internal Batterycharger with fuse
FCB = F500mA
Power electrical connections
Single-phase systems connections 2P
L
L
N
MAINS
GENERATOR
CT only if
available
Cod. Doc. MT2550041-rev.1.0 GB.doc
mail:
info@tecnoelettra.it
F1 = F6,3A Protection for the
auxiliary battery circuits 12Vdc
F2 = F2A Protection mains contactor
F3 = F2A Protection generator
contactor
Ø= 6mm
min. 10cm all around
N
L1 L2 L3 N
GENERATOR
L
N
LOAD
web:
www.tecnoelettra.it
TECHNICAL FEATURES
Nominal voltage battery ..........................................12Vdc
Maximum rated current ..........................................250mA
Maximum rated power ................................................ 3W
Operating range...............................................1017VDC
Nominal voltage generator/mains .......... 100 ÷ 265Vac L-N
Measuring range voltage appearing..............50 ÷ 450Vac
Frequency range ............................................... 45 65Hz
Degree of protection front board................................ IP65
Degree of protection of switchboard .......................... IP20
Operating temperature................................... -20 +50°C
Free space of
Storage temperature...................................... -30 +70°C
aeration reason =
Maximum rated humidity ..........................................90%
the switchboard
Three-phase systems connections 4P
L1 L2 L3 N
MAINS
CT only if
available
Description of the data shown on the label
In = nominal current
Imax = maximum rated current
KA = maximum breaking current against short circuit
Hz = frequency
KVA = apparent power (calculated at cos fi 0,8)
KW = active power
HP = horse power
V~ = maximum use voltage of the primaries
Vaux = maximum voltage of the auxiliary circuits
IP = degree of protection against external agents
Kg = approximate weight
Dim = dimensions Height x Width x Depth
Ser.n = serial number
Model = product code
Single-phase system 2P (max 5m)
I max
40A
51A
72A
89A
96A
Three-phase system 4P (max 5m)
I max
25A
32A
45A
56A
60A
L1 L2 L3 N
LOAD
UK
Cables sections
min. sec.
max sec.
2x 4mm²
2x 6mm²
2x 4mm²
2x 6mm²
2x 6mm²
2x 10mm²
2x 10mm²
2x 16mm²
2x 10mm²
2x 16mm²
min. sec.
max. sec.
1x 4mm²
1x 6mm²
1x 6mm²
1x 6mm²
1x 10mm²
1x 10mm²
1x 16mm²
1x 16mm²
1x 16mm²
1x 16mm²
1 / 4
Need help?
Do you have a question about the AT206 and is the answer not in the manual?
Questions and answers