2.3 - Panel wall mounting instructions ....................................9 3 - First starting of the product, use and description ...............................9 3.1 - Operation to do during the first starting of the AT206 panel ............................9 3.1.1 - How programming the time on the panel ................................9 3.2 - AT206 panel;...
Verify if the registration number reproduced on the technical card of the acquired model agrees with that one cut with the label of the “Marking CE” The Firm “TECNOELETTRA s.r.l.” will not think he is responsible for difficulties, breaks, accidents etc. due to the no knowledge or at any rate to the no application of the rules held in this manual.
- Never for any reason modify any part of the electric panel (connections, holes, electrical or mechanical devices, etc.) unless duly authorized to do so in writing by “TECNOELETTRA”: the responsibility deriving from any such action shall fall on the person doing it since he then in fact becomes its manufacturer.
1.4 - Important tips User tips on safety: N.B. The information contained in this manual may be changed without notice. Any damage caused in relation to the use of these instructions shall not be considered since they are only guidelines. We remind you that failure to observe the instructions we give could cause injury or damage.
In the event of damage due to transportation or delivery of the wrong model, call the firm that carried out the service and “TECNOELETTRA”. Before removing the packing from the electric panel, carefully read the user warnings given in this handbook.
2- AT206 PANEL DESCRIPTION This product permit to control all the functions about a generator • Engine command and protection module for diesel or gasoline generators • Measurement system for main electric values • Automatic control module for two different supply sources (Automatic Mains Failure) •...
2.2 - Product external and internal view with description Control board F1 = F4A F2 = F2A F3 = F2A Buzzer “B” for acoustic alarm “IMP” switch to supply 230Vac for auxiliary output. Predisposition for (OPTIONAL) magnetothermic switch or earth failure relay.
3 - FIRST STARTING OF THE PRODUCT, USE AND DESCRIPTION 3.1 - Operation to do during the first starting of the AT206 panel When you supply for the first time the panel, the display shows “U11” flashing, to remember you the time programmation (User menu, parameter U11).
3.2 - AT206 panel; LED indication decription Type of If flashing, it indicate that the measurement 4 digit multifunction engine is running and the If on, it showed by the display to show alarms are not enable. If on, indicates that...
3.4 - AT206 panel; function description BOARD IN RESET The generator can’t work. If the mains is ok, the mains contactor is closed. If the generator is running, when you change to this function mode the engine is stopped immediatly and the eventual alarms are resetted. The alarm can’t be resetted if the cause of alarm still remain.
Mains neutral: T4 Mains input Common earth Load output connection (Genarator, Mains, Load) Electrical drawing WARNING ! !: TA current WARNING ! !: transformer is Magnetothermic mounted only in switch is an AT206 panel type optional. Cod.Doc.2550041-REV 2.2.0 gb.doc Pagina 13...
T3+T4=Neutral. By this connection the max current of the contactor is Ith x 1,6 WARNING ! !: TA current WARNING ! !: transformer is Magnetothermic mounted only in switch is an AT206 panel type optional. Cod.Doc.2550041-REV 2.2.0 gb.doc Pagina 14...
WARNING !! If the installation of the product is not in accordance to the specifics descripted above, can cause problems in terms of functionality and can also compromises warranty conditions. Then Tecnoelettra srl won’t be responsible for any direct or not direct damage due to wrong installation.
5.4 - Advanced menu parameters Setup Description Range Default Group 1 Panel nominal data P1.01 Nominal frequence 50Hz= 0 60Hz=1 Current Trasformer ratio (CT 100/5 = 20) 1…2000 System (220V monophase, 220V triphase, 380V triphase) 0=230M 1=230T 2=400T Group 2 Engine start-up P2.01 500 rpm signal from alternator or gen.
Page 21
Group 7 Network parameters P7.01 Mains voltage minimum threshold (measured) 160 – 230Vac 195Vac Mains voltage maximum threshold (measured) 200 – 345Vac 260Vac Mains voltage time out of the limits 5 – 9999 sec 5 sec Mains voltage return time within the limits 5 –...
The prices are those specifically valid of the ruling price list, VAT excluded. Furthermore, they do not cover the costs of packing, carriage, delivery, custom duties and/or any other charges, unless stated otherwise. Except when agreed with TECNOELETTRA in writing, the ruling prices shall be applied to all deliveries beginning from January 1.