Tool transformers

Advertisement

3.
SPECIFICATION
i
MODEL NO:
TR1000.V3
Input Voltage - 1ph AC
Output Voltage -
1ph AC
Output Rating - (VA)
Tool (Intermittent)
Output Rating - (VA)
Continuous
Output Sockets
4. OPERATION
4.1.
The Tool Rating (kVA) marked on the transformer data plate is the rating assuming a 25% duty factor on a 20 minute cycle i.e. 5
minutes equipment use followed by 15 minutes rest.
4.2.
Check the equipment rating and operation against the transformer rating. The transformer will supply intermittently used equipment
up to the plate rating but if the equipment is used continuously then the transformer rating should be halved. See Section 3.
4.3.
It is normal for the transformer to get warm during use, particularly if being used continuously, so care should be taken to place
only on surfaces that will not be damaged by the heat.
4.4.
A temperature sensitive cut-out switch is fitted to prevent overheating. If this switch trips, determine and rectify the cause of
overheating and allow time for the transformer to cool before pressing the reset button. (Located on one of the sides adjacent to the
output sockets)
4.5.
The transformer should be plugged directly into a 230V mains socket and should not be supplied via an extension lead. Any
necessary extension lead should be between the transformer and the tool/equipment. Extension leads are available from your
Sealey stockist.
IMPORTANT: The transformer is not double insulated and the safety screen between primary (230V) and secondary (110V) windings
is connected to the earth core of the power cable. For these reasons it is extremely important to confirm that the power socket to be
used is reliably and permanently earthed.
4.6.
Tool transformers can draw a very high initial current when switched on. If fuse failure occurs at switch-on check that the fuse is a
13 amp, anti-surge type. Any circuit breaker protecting the supply socket should have a type 4 tripping characteristic.
DO NOT exceed 1.5kV when flash testing.
8
4.7.
A plug suitable for the transformer output is available from your supplier under Sealey Model No: TR110VP.
WEEE REGULATIONS
Dispose of this product at the end of its working life in compliance with the EU Directive on Waste Electrical and Electronic Equipment
(WEEE). When the product is no longer required, it must be disposed of in an environmentally protective way. Contact your local solid
waste authority for recycling information.
ENVIRONMENT PROTECTION
Recycle unwanted materials instead of disposing of them as waste. All tools, accessories and packaging should be sorted, taken to
a recycling centre and disposed of in a manner which is compatible with the environment. When the product becomes completely
unserviceable and requires disposal, drain any fluids (if applicable) into approved containers and dispose of the product and fluids
according to local regulations.
Note: It is our policy to continually improve products and as such we reserve the right to alter data, specifications and component parts without prior
notice.
Important: No Liability is accepted for incorrect use of this product.
Warranty: Guarantee is 12 months from purchase date, proof of which is required for any claim.
Sealey Group, Kempson Way, Suffolk Business Park, Bury St Edmunds, Suffolk. IP32 7AR
01284 757500
© Jack Sealey Limited
TR1500.V3
TR2000.V3
230
230
110
110
1000
1500
600
900
1
2
01284 703534
Original Language Version
TR3000.V3
230
230
110
110
2250
3000
1250
1650
2
2
sales@sealey.co.uk
TR1000.V3, TR1500.V3, TR2000.V3, TR3000.V3 Issue 4 (3) 14/05/18