ABB PSTX30 Applications Manual page 11

Waste water pump
Table of Contents

Advertisement

3.2.3
Connecting Start and Stop
terminals to push buttons and PLC
Internal control voltage - Push buttons
The PSTX Softstarter has a built-in holding circuit and
does not require sustained signals on start input. Use
internal control supply voltage from terminals 20 or 21.
Connect start and stop terminals using conventional
circuit with push buttons. See Figure 6 and Figure 7.
Connect the white start push button as START and the
black stop push button as STOP in Figure 7.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
External control voltage - PLC
The softstarter can, if required, also be controlled with an
external 24 V DC source from a PLC or similar.
Connect the cables according to Figure 8 depending on
which type of control method is used.
WARNING
Terminal 13, 14 ,15, 16 and 17 should be
connected using 24V DC only. Other voltages
may damage the softstarter and the warranty may
no longer be valid.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
K6
Start Stop In0 In1 In2
GND
+24V
K6
Stop
In0 In1 In2
GND
+24V
1SFC132104M0201
6
Figure 6:
Start and Stop, terminals 13, 14, 18, 19, 20, 21
7
STOP
L
N
100-250V
50/60 Hz
K4
K5
Figure 7:
Holding circuit (pulse for start is enough)
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
8
START
L
N
100-250V
50/60 Hz
K4
K5
Figure 8:
Holding circuit with external control voltage
(pulse for start is enough)
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
| Application manual: Waste water pump | Connection
START
K6
Start Stop In0 In1 In2 DGND GND +24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
+
-
DC
STOP
K6
Start Stop
In0
In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
11