CO2 SENSOR WITH LIGHT CELL
3
1
INPUT
INSTALLATION
Place the OCL DLC 1.1 digital lighting controller outside the climate room, connect the included power adaptor to POWER. To correctly
measure the CO2 level, place the CO2 sensor in the climate room. Together, the Controller, Power supply and the Sensor regulate the
CO2 generator or bottle. Certain conditions need to be met to ensure correct operation of the CO2 sensor.
50 CM
Copyright 2018 | All Rights Reserved
2
OUTPUT
INPUT
The CO2 sensor needs to be in the direct vicinity of the CO2 source and should
be placed within at least 50cm of the source. Place the sensor about 1 meter
above the floor. It is recommended not to place the CO2 sensor above the
CO2 generator or bottle, or in the direct airflow of fans, as this will influence the
measurements.
PLEASE MAKE SURE THAT THE CO2 SENSOR IS IN THE LIGHT:
The sensor needs to detect light, in order to be able to correctly measure the
CO2 level in the climate room. The light cell itself is not visible but is behind the
grooves of the sensor casing. Insert [1] the plug of the CO2 generator or the CO2
pressure reducing valve into the "POWER SUPPLY" [2]. The green LED [3]
indicator lights up when a CO2 dosage is given.
100 CM
The UTP-cable is plugged into the OCL DLC1.1 port of the lighting controller
marked "CO2". Subsequently plug the UTP-cable supplied in the "INPUT" port
of the power supply with led indicator. Then plug the other CO2-cable supplied
in the "OUTPUT" of the power supply with led indicator thereby connecting the
CO2-sensor.
The CO2-generator or the pressure reducing valve can now be connected to
the "POWER SUPPLY" with led indicator.
CO2
http:/ /www.ocl-lighting.com

Advertisement

loading

Summary of Contents for OCL CO2 SENSOR

  • Page 1 Place the OCL DLC 1.1 digital lighting controller outside the climate room, connect the included power adaptor to POWER. To correctly measure the CO2 level, place the CO2 sensor in the climate room. Together, the Controller, Power supply and the Sensor regulate the CO2 generator or bottle.
  • Page 2 For calibration a level of 400ppm is needed. Before calibration, the sensor needs to be warmed up by inserting it in an electrical output for at least 5 minutes. The CO2 sensor should be placed in a CO2 neutral environment, like a garden, a balcony or if these are not available, a sealed and well ventilated room for at least 8 hours.