Toshiba BMS-TP0640ACE Manual page 32

Touch screen controller, tcs-net air conditioning control system
Table of Contents

Advertisement

(11) Door-lock input definition file
• File name: KEY_CH.DEF
• Enter door-lock input numbers (1-64), input device IDs, input channels, and signal logic (up to 64).
• When no door-lock input is used, do not enter it.
• An input device ID means the following:
0 to 7: I/O module device ID
10: general-purpose input in the touch panel
100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)
• Specify signal logic. [0: negative logic, 1: positive logic]
(12) Fire alarm input definition file
• File name: FIRE_CH.DEF
• Enter fire alarm input numbers (1-64), input device IDs, input channels, and signal logic (up to 64).
• When no fire alarm input is used, do not enter it.
• An input device ID means the following:
0 to 7: I/O module device ID
10: general-purpose input in the touch panel
100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)
• Specify signal logic. [0: negative logic, 1: positive logic]
(13) Emergency external output definition file
• File name: EMGOUT_CH.DEF
• Enter external emergency output numbers (1-64), output device IDs, and output channels (up to 64).
• When no external emergency output is used, do not enter it.
• An output device ID means the following:
0 to 7: I/O module device ID
20: general-purpose output in the touch panel
100 or more: digital I/O interface (Second digit: Intelligent Server No., first digit: Relay Interface No.)
(14) R.C. group/indoor setup file
• File name: AC_MAP.DEF
• R.C. group/indoor No., Intelligent Server No., Relay Interface No., outdoor system No., indoor unit
address, device type, block No., tenant No., area No., key No., fire alarm No.
• Device type
0: SMMS, SHRM, 1: SDI, DI, 2: HA interface
• Key No.
0: no door-lock interlocking, 1-64: When a signal is input from the number defined in (11), stop
command is sent to the system.
• Fire alarm No.
0: no fire alarm interlocking, 1-64: When a signal is input from the number defined in (12), stop
command is sent to the system.
• Indoor unit set in this file is header unit only.
(15) Indoor unit group config file
• File name: AC_GROUP.DEF
• R.C. group/indoor No., Intelligent Server No., Relay Interface No., outdoor system No., indoor unit
address, device type, outdoor unit No., header/follower, tenant No.
• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not
performed.
(16) Outdoor unit group config file
• File name: OUT_GROUP.DEF
• Outdoor unit No., Intelligent Server No., Relay Interface No., system No., outdoor unit address,
device type
• Used for energy monitoring and billing. No data is provided when energy monitoring and billing is not
performed.