Specifications - LG ARNU18GS5 2 Series, ARNU24GS5 2 Series Manual

Lcs(light commercial system) indoor unit
Table of Contents

Advertisement

LCS(Light Commercial System) Indoor unit

2. Specifications

Type
Model
Cooling Capacity
Heating Capacity
Dimensions(WxDxH) Body
Rows x Columns x FPI
Coil
Face Area
Type
Motor Output x Number
Running Current
Fan
Air Flow Rate(H / M / L)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
Pipe Connections Gas Side
Drain Pipe(Internal Dia.)
Net Weight
Noise Level(Sound Press, 1m, H / M / L)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Color
Notes:-
1. Capacities are based on the following conditions:
Cooling
• Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
Heating
• Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting Piping Length 7.5m
• Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.
Unit
ARNU18GS5*2
kW
5.6
kcal/h
4,800
Btu/h
19,100
kW
6.3
kcal/h
5,400
Btu/h
21,500
mm
1,090 x 178 x 300
inch
42.9 x 7 x 11.8
2 x 15 x 20
m
3
0.26
Cross Flow Fan
W
20
A
0.2
CMM
12.0 / 10.5 / 9.0
cfm
424.0 / 371.0 / 318.0
Direct
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
mm(inch)
Ø6.35(1/4)
mm(inch)
Ø12.7(1/2)
mm(inch)
16(5/8)
kg(lbs)
12(26.5)
dB(A)
44 / 40 / 36
1, 220-240, 50
Ø, V, Hz
1, 220, 60
EEV
mm
2
CV1.5 x 3C
mm
2
CVV-SB 1.0~1.5 x 2C
Morning fog
* Model Name
A:Basic L:Plasma
Wall Mounted
ARNU24GS5*2
7.1
6,100
24,200
8.0
6,900
27,300
1,090 x 178 x 300
42.9 x 7 x 11.8
2 x 15 x 20
0.26
Cross Flow Fan
20
0.2
14.0 / 13.0 / 10.0
494.0 / 459.0 / 353.0
Direct
BLDC
Foamed polystrene
Resin Net(washable)
Fuse
Ø9.52(3/8)
Ø15.88(5/8)
16(5/8)
12(26.5)
46 / 41 / 38
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.0~1.5 x 2C
Morning fog
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m
l/s = CMM x 1000/60
Wall Mounted _ 2
3
/min x 35.3

Advertisement

Table of Contents
loading