CONNECTING VISTAKEY TRIGGER
The VistaKey has one trigger output (TB3 terminal 8) that
can accept a maximum current of 15mA from a source
voltage of 12VDC. It is a solid-state digital switch output
that may be used to operate small loads such as LEDs and
piezoelectric sounders. It can be configured as an output
committed to the access point or as an uncommitted output
for general use to control the on and off conditions of
external devices.
THIS DEVICE COMPLIES WITH PART 15 CLASS A
LIMITS OF FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS:
(1) IT MAY NOT CAUSE HARMFUL INTERFERENCE.
(2) IT MUST ACCEPT ANY INTERFERENCE THAT
MAY CAUSE UNDESIRED OPERATION.
THIS EQUIPMENT SHOULD BE INSTALLED IN
ACCORDANCE WITH THE NATIONAL FIRE
PROTECTION ASSOCIATION'S STANDARDS 70 &
74 (NATIONAL FIRE PROTECTION ASSOC.,
BATTERYMARCH PARK, QUINCY, MA. 02269).
PRINTED INFORMATION DESCRIBING PROPER
MAINTENANCE, EVACUATION PLANNING AND
REPAIR SERVICE IS TO BE PROVIDED WITH
THIS EQUIPMENT.
FOR ADDITIONAL RATINGS AND
SPECIFICATIONS, REFER TO
INSTALLATION INSTRUCTION
FOR THE VISTAKEY-SK.
WEEKLY TESTING IS REQUIRED
TO ENSURE PROPER OPERATION
OF THIS SYSTEM.
¬.¥l
K5312 04/00
1
2 3 4 5 6 7 8 9 10
TB 1
TB 3
VISTAKEY
VistaKey Summary of Connections
165 Eileen Way, Syosset, New York 11791
Copyright © 2000 PITTWAY CORPORATION
VISTAKEY PROGRAMMING AND TESTING
For detailed programming and testing information, please
refer to the procedures in the UL Listed VistaKey-SK
(Starter Kit) manual.
WARRANTY INFORMATION
Refer to the manual supplied with your alarm system for
warranty information.
14V MAX (12V @ 85-160mA Nominal)
GND
POLLING LOOP +
POLLING LOOP -
GND
ZONE A (DSM)
ZONE B (RTE)
ZONE C (General)
GND
POLE Door Strike/Mag Coil
N/C MAG COIL POWER
N/O DOOR STRIKE POWER
RELAY CONTACT RATINGS:
11 12
3A @ 28VDC MAX. (RESISTIVE LOAD)
K1
DOOR
READER INTERFACE CABLE
CONTROL
RELAY
RDR LED
(ORANGE)
1
GND
(BLACK)
2
DATA 1
(WHITE)
3
DATA 0
(GREEN)
4
GND
5
+5V
6
+12V
(RED)
7
8
TRIGGER (SEE NOTE 3)
+
NOTE 1: USE UL LISTED ENERGY CABLE FOR ALL CONNECTIONS.
NOTE 2: VISTAKEY TB3 TERMINAL 5 IS A GROUND AND MAY BE
USED INSTEAD OF TB3 TERMINAL 2. TB3 TERMINALS 2 AND 5 ARE
A COMMON GROUND.
NOTE 3: WHEN USING TRIGGER TO TURN ON AN LED OR BUZZER,
RETURN HIGH SIDE OF LED OR BUZZER TO TB3 TERMINAL 7.
TRIGGER RATING IS 15mA AT 12VDC.
TO ALARM SYSTEM
CONTROL PANEL
POLLING LOOP TERMINALS.
+ 12 VDC TO ONLY
ONE OF THESE INPUTS.
(FROM TB1-1)
NO
CONNECTION