Flushing And Calibration Flowchart - Tokheim TQM Manual

Table of Contents

Advertisement

Component Technical Manual
3.6.1
Start
Run FP until
fuel comes
out of nozzle
Clean pump
nozzle
Flush FP with
40 Liters
Calibration 1
Calibration 2
Yes
1 = 2
Adjust
2
Document Ref 942175-001 Rev 3

FLUSHING AND CALIBRATION FLOWCHART.

The flowchart below illustrates the flushing and calibration instructions.
and
filter
Adjust
Yes
OK
No
Yes
OK
No
No
1
TQM Meter for Fuel Dispensers
1
Calibration 3
Yes
OK
No
Yes
2 = 3
No
Calibration 4
Yes
OK
No
Check
installation /
Replace
meter
(defective)
Stop
2
Calibration 3
Yes
OK
No
Adjust
Calibration 4
Yes
OK
No
Check
installation /
Replace
meter
(defective)
OK = within acceptable
tolerance limits
Page 3-7

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TQM and is the answer not in the manual?

Related Products for Tokheim TQM

Table of Contents

Save PDF