1.
Overview
The Cypress Envirosystems Wireless Pneumatic Thermostat (WPT) retrofits an existing
pneumatic thermostat to provide Direct Digital Control (DDC) like zone control
functionality at a fraction of the time and cost without disturbing occupants.
The WPT enables remote monitoring of zone temperature, branch pressure, remote
control of setpoints, and programmable setback or setup of the pneumatic HVAC
systems. It also enables integration with utility Demand Response programs.
The Wireless Pneumatic Thermostat repeater (RPT) is one of the components of WPT
wireless network. The RPT is used to extend the wireless range of the WPT network by
allowing more WPTs to be connected in each wireless network. When the WPT USB
Hub (HUSB) is located out of RF range of the WPT, multiple RPTs can be used to extend
the range. For more details, refer to WPT Wireless Network Planning Guide.
1.1.
Components
The WPT-810-RPT kit includes the following components:
Wireless repeater
Universal wall bracket
Mounting screws, #6 x 1" self-tapping (x2)
1.2.
Prerequisites for Installation
The WPT system relies on a wireless network for communication. The following tasks
must be completed before proceeding to RPT installation:
Wireless survey performed using the WPT-800-RKIT
Installation of the WPT Green Box
Installation of the HUSB
Assignment of network IDs and RPT IDs
Assignment of RPT locations
Run low voltage power to the RPT location
Manuals for the WPT, WPT Green Box, HUSB and other manuals related to the WPT
system can be found at http://www.cypressenvirosystems.com.
1.3.
Tools Required for Installation
Phillips-head screw driver
1/16" hex Allen wrench
RPT Installation Manual
Doc No. 910-00027-01 Rev 01
Page 1 of 12

Advertisement

loading
Need help?

Need help?

Do you have a question about the WPT-810-RPT and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Cypress Envirosystems WPT-810-RPT

  • Page 1 RPT Installation Manual Doc No. 910-00027-01 Rev 01 Overview The Cypress Envirosystems Wireless Pneumatic Thermostat (WPT) retrofits an existing pneumatic thermostat to provide Direct Digital Control (DDC) like zone control functionality at a fraction of the time and cost without disturbing occupants.
  • Page 2 RPT Installation Manual Doc No. 910-00027-01 Rev 01 RPT Basics 2.1. Turning on the RPT Connect a low voltage power supply (not included) to the 2-position connector inside the RPT. There is a connector for 12-24VAC power and another connector for 5-40VDC power.
  • Page 3 RPT Installation Manual Doc No. 910-00027-01 Rev 01 2.3.2. Programming Menu Programming Menu allows the installer to configure the network and RPT ID. Refer to Figure 2 for the menu structure. Page 3 of 12...
  • Page 4 RPT Installation Manual Doc No. 910-00027-01 Rev 01 Figure 2. RPT Menu Structure Page 4 of 12...
  • Page 5 RPT Installation Manual Doc No. 910-00027-01 Rev 01 RPT Installation The overall RPT installation procedure includes: Wire runs • Mounting the RPT • Configuring the RPT • ESD Handling Precautions Warning! The RPT contains ESD sensitive circuit cards and components, shown in Figure 3. •...
  • Page 6 RPT Installation Manual Doc No. 910-00027-01 Rev 01 3.1. Wire runs Cabling used to supply power should be a jacketed Class-2 type with a 20AWG minimum. Refer to Table 1 for recommended wire gauges based on cable lengths. Wire Length Up to 50’...
  • Page 7 RPT Installation Manual Doc No. 910-00027-01 Rev 01 2. Mount the RPT on the universal wall bracket using the captive screws. It is recommended to run the low voltage power wires through the large hole in the center of the repeater base plate. The wire should be strain relieved to prevent stress or fatiguing at the terminal strip connection points.
  • Page 8 RPT Installation Manual Doc No. 910-00027-01 Rev 01 Figure 6. Wall Bracket Cable Routing Recommendation 3. Connect the low voltage power wiring to the appropriate push-connector inside the repeater. The AC connector is non-polarity sensitive. The DC connector is polarity sensitive.
  • Page 9 RPT Installation Manual Doc No. 910-00027-01 Rev 01 The network ID cannot have a “0” value. 3. Press the middle button to confirm the network ID. This completes the programming of the network ID and the LCD display starts flashing the first digit, D1, of the RPT ID.
  • Page 10: Troubleshooting

    RPT Installation Manual Doc No. 910-00027-01 Rev 01 Troubleshooting The RPT is designed with the following diagnostic functions to detect and diagnose faults. Code Reason Solution Discovery Status: This display goes off automatically after a few This code indicates that the RPT is •...
  • Page 11 RPT Installation Manual Doc No. 910-00027-01 Rev 01 Repair The RPT does not have any replacement or repairable parts. Contact the original distributor of the unit for repair or warranty service. Note: Care should be taken to keep the unit dust-free during installation. Page 11 of 12...
  • Page 12: Technical Specification

    Storage Conditions 95% RH Max, Noncondensing Length: 5.56 inches (141 mm) Dimensions Width (including antenna): 5.56inches (141 mm) Depth: 2.1 inches (53 mm) Cypress Envirosystems 5883 Rue Ferrari, Suite 100 5883 Rue Ferrari San Jose, CA, 95138, USA Suite 100 info@cypressenvirosystems.com...