Installation and Operating Specification FU Basic
0...100 % PWM
Control via external setting signal PWM
E1,1 E1,2
Danger due to electric current
Do not replug the jumper under voltage, observe the safety instructions!
Make sure the signal has the correct polarity!
Never apply line voltage to analog inputs!
5.8

Output voltage "10 V"

Voltage supply e.g. for speed setting by external potentiometer.
Connection: "10 V" - "GND" (max. load see Technical data und connection diagram).
It is not permissible to connect voltage outputs of several devices to each other!
It is not permissible to connect voltage outputs in the device to each other!
5.9

Voltage supply for external devices (+24V, GND)

A voltage supply is integrated for external devices e.g. a sensor (max. current load see technical
data).
In case of overload or short circuit (24 V – GND), the external power supply is shut down (multi-fuse).
The device performs a "Reset" and continues operation.
It is not permissible to connect voltage outputs of several devices to each other!
It is not permissible to connect voltage outputs in the device to each other!
5.10

Digital input "D1" for enable (device ON / OFF)

Electronic disconnection and Reset after motor fault via floating contact at terminals "D1"- "24V (input
resistance and voltage range
Function factory setting for "D1":
Device "ON" for closed contact.
Device "OFF" with opened contact.
Activation via floating contacts, a low voltage of approx. 24 V DC is connected.
Danger due to electric current
No disconnection (no potential isolation in accordance with VBG4 §6) in remote control of the
device!
Never apply line voltage to the digital input!
5.11

Relay outputs "K1"

An external fault indicator is available over the potential-free contact of the built-in relays (max. contact
rating
Technical data and connection diagram).
Function factory setting for "K1":
For operation the relay is energized, connections "13" and "14" are bridged. For fault the relay is de-
energized (
When switching off via enable (D1 = Digital In 1), the relay remains energized.
L-BAL-E187-GB 2004 Index 003
PWM
E1
D1 GND 10V
15...28 V
Technical data)".
Diagnostics / faults).
24V
E1,1 E1,2
PWM
f = 1...10 kHz
Part.-No.
13/22
Electrical installation
PWM
E1
D1 GND 10V 24V
(10 V)
31.01.12
i_jumper_if_basic_pwm.eps
10 k