Download Print this page
Jantar POPULUS P Series Quick Start Manual

Jantar POPULUS P Series Quick Start Manual

Advertisement

Quick Links

POPULUS P – ACCESS CONTROLLER
The Populus P is an access controller that controls up to 8 readers
and 4 outputs for electric strikes. It is designed for residential and
business buildings, offices, shops, etc.
The entire set-up procedure is carried out with the software. The
controller allows access for up to 16000 users. It is intended for
controlling entries, exits and passes of users in the system and
controlling sliding doors, ramp, el. strike, turning alarm on/off... It
needs to be set with BLOCKER, V7 or CODEKS software.
It may also be used as a standalone controller. In this case, the
entire set-up procedure is carried out with master card or code.
User cards and codes can either be registered or deleted. The
controller allows access for up to 500 users (1 master card + 500
user cards or codes).
The SDK is also available for this controller. If a user or software
producer wants to develop its own application, please contact us.
TECHNICAL DATA
POPULUS P-1-3P and POPULUS P-1-3P-NET
Readers
1x direct or Wiegand, 1x protocol
Inputs
1x door status, 1x button
Outputs
1x max. 0.5 A active=GND
Relays
1x 5A 60V DC
POPULUS P-2-3P and POPULUS P-2-3P-NET
Readers
2x direct or Wiegand, 2x protocol
Inputs
2x door status, 2x button
Outputs
2x max. 0.5 A active=GND
Relays
2x 5A 60V DC
POPULUS P-4-3P and POPULUS P-4-3P-NET
Readers
4x direct or Wiegand, 4x protocol
Inputs
4x door status, 4x button
Outputs
4x max. 0.5 A active=GND
Relays
4x 5A 60V DC
*if Populus P is in Spider mode, the same data applies
Common features
Input voltage
Output voltage
Primary fuse
Current consumption
Humidity
Dimensions (mm)
Operating temperature
Communication
Clock
Operation at an altitude of
Appliance class
Black line
POPULUS P – Access controller
110 – 230 V AC 50–60 Hz
13.8 V DC
(F100) T1AL, 250 V (5x20mm)
Up to 2W
10-80 %, non-condensing
222x222x80 (WxHxD)
From -20°C to 40°C
RS485 or Ethernet
Real time clock, battery backup
(max. ten hours)
<2000m
Class II - This is a class A
product. In a domestic
environment this product may
cause radio interference in which
case the user may be required to
take adequate measures.
CONNECTOR DESCRIPTION
Connectors are marked on the circuit board with AC, LAN, SYS,
COM, RDR and DOOR
.
CONNECTOR AC – Power supply
Contact
Description
1
AC
CONNECTOR LAN – Ethernet connection
Contact
Description
1
LAN
CONNECTOR SYS – backup battery connection
Contact
Description
1
BAT
2
GND
3
12V
4
GND
CONNECTOR COM – RS485 communication connection
Contact
Description
1
CA
2
CB
3
CA
4
CB
CONNECTOR RDR1, RDR2, RDR3, RDR4 – reader connection
Contact
Description
1
12V
2
GND
3
D0
4
D1
5
BUZ
6
LED
7
XA – RS485 XA line
8
XB – RS485 XB line
CONNECTOR DOOR1, DOOR2, DOOR3, DOOR4 – sensor,
button, el. strike and relay connections
Contact
Description
1
SWITCH
2
GND
3
BUTTON
4
12V
5
LOCK
6
NO
7
MIDDLE
8
NC
Power Supply
The controller can operate within a 110-230V AC, 50–60Hz input
range. The output power of the in-built power supply is 30W, 13.8V
fulltime. The power supply has protection against both short
circuits and current overload. In the event of protection activation,
the power will be switched off for 5s. If this is repeated 20 times,
the controller will switch off until electrical resetting takes place
(unplugging from mains voltage). This protection is activated if
external consumption exceeds 2A.
An appropriate disconnect device should be provided external to
the equipment.
A multi-strand/stranded flexible wires connected to
the unit mains input require ferrules.
Specification
Power supply
110 – 230 V AC
50–60 Hz
Specification
Ethernet
Specification
12 V DC from battery
Ground
Max. 0.5 A
Ground
Specification
RS485 A line
RS485 B line
RS485 A line
RS485 B line
Specification
12 V DC output
Ground
Data 0
Data 1
Buzzer output
LED output
For protocol reader
For protocol reader
Specification
Door status switch input
active=GND
Ground
Push button input
active=GND
12 V DC output
El. strike output
active=GND
Relay – open contact
Relay – middle
Relay – closed contact
5/2014
www.codeks.eu

Advertisement

loading

Summary of Contents for Jantar POPULUS P Series

  • Page 1 POPULUS P – Access controller CONNECTOR DESCRIPTION Connectors are marked on the circuit board with AC, LAN, SYS, COM, RDR and DOOR CONNECTOR AC – Power supply Contact Description Specification Power supply 110 – 230 V AC 50–60 Hz CONNECTOR LAN – Ethernet connection POPULUS P –...
  • Page 2 The RS485 communication bus is used between the controllers and and shut down at 10.5V. The charging time of an empty battery is Jantar software. Up to 128 controllers can be lined up into one approximately 4 hours. The charging voltage and current are 13.8 communication line.

This manual is also suitable for:

Populus p-1-3pPopulus p-1-3p-netPopulus p-2-3pPopulus p-2-3p-netPopulus p-2-3p-net-sPopulus p-4-3p ... Show all