RM7888A 7800 SERIES RELAY MODULE
Terminal Number
G
Flame Sensor Ground
Earth G
Earth Ground
L2(N)
Line Voltage Common
3
Alarm
4
Line Voltage Supply (L1) 120 Vac (+10/-15%), 50/60 Hz (±10%)
5
Air Valve
6
Special Function 1
7
Limits Complete
8
Pilot Valve
9
Main Fuel Valve
10
Ignition
F(11)
Flame Sensor
12(B)
Firing Rate High Fire
13(R)
Firing Rate Common
14(W)
Firing Rate Low Fire
15
Firing Rate Modulate
16
Unused
17
Special Function 2
18
@Low Fire Input
19
Special Function 3
20
Special Function 4
21
Flame Proven
22
Shutter
1
The RM7888 must have an earth ground providing a connection between the subbase and the control panel or the
burner. The earth ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in
event of an internal short circuit. The RM7888 needs a low impedance ground connection to the equipment frame
which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF fre-
quencies, the connection must be made with minimum length conductors having maximum surface areas. Wide straps
or brackets are preferred rather than leadwires. Be careful to make sure that mechanically tightened joints along the
ground path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coat-
ings and are protected against mating surface corrosion.
2
2000 VA maximum connected load to RM7888A Assembly.
3
See Table 2 and 3 for load combinations.
IMPORTANT
A Flame Detection System that must be ordered separately is required for operation. To select your Plugin Flame
Signal Amplifier and applicable Flame Detector, see Table 4.
Pilot Fuel 8
C
B
F
No Load
D
D
No Load
a
Jumper Terminals 8 to 9 for direct spark ignition.
32-00214—01
Table 1. Terminal Ratings.
Description
1
60 to 220 Vac, current limited.
1
120 Vac, 1A pilot duty.
120 Vac, 9.8A FL, 58.8A LR (inrush).
120 Vac, 1 mA.
120 Vac, 9A.
3
3
3
60 to 220 Vac, current limited.
120 Vac, 75 VA Pilot Duty.
120 Vac, 75 VA Pilot Duty.
120 Vac, 75 VA Pilot Duty.
120 Vac, 75 VA Pilot Duty.
120 Vac, 1 mA.
120 Vac, 1 mA.
120 Vac, 1 mA.
120 Vac, 1 mA.
120 Vac, 2A pilot duty.
120 Vac, 0.5A.
Table 2. Combinations for Terminals 8, 9, and 10.
F
F
F
F
a
F
D
a
D
Main 9
4
Ratings
2
Ignition 10
No Load
No Load
A
A
A
A
A

Hide quick links: