Appendix B Building Your Own Power Cable - Maple Systems OIT3200 Installation Manual

Table of Contents

Advertisement

24
Building Your Own Power Cable
When building your own power cable, slide the two ferrite shield beads that were included in the
connector kit from Maple Systems onto the cable shield wire before inserting the wire into Pin 3 of
the power connector. These ferrite shield beads are required for CE compliance and noise immunity.
1.50"
[38.1]
.30"
[7.6]
Shield
power connector (supplied with the OIT).
WIRE LIST
OIT
Wire Color
Signal
Pin #
1
RED
+12V to 30VDC
2
BLACK
Signal Ground
3
SHIELD
Chassis Ground
1010-0081A, REV 04
Appendix B
18AWG Shielded (RED/BLACK)
Recommended
3/8" Heatshrink, 2.0" Long
(Covers ferrite beads)
CONNECTOR is a three-position
3
2
1
Push screwdriver into
RECTANGULAR holes
to open wire clamps.
(Note: There is an optional set
of holes on the bottom side.)
Figure 19 Power Connector Pin-Out
2 Ferrite beads
(supplied with the OIT)
Power Connector
Push stripped wire into ROUND
holes while holding clamps
open with a screwdriver.
OIT3200/3250
2.00"
[50.8]
0.30"
[7.6]
Shield
RED
1
2
BLK
3
SHIELD
0.5"
[12.7]

Advertisement